CHBC Structural Regulations set performance‑based, preservation‑sensitive rules (Ch. 8‑7) to evaluate and strengthen gravity and lateral systems of qualified historical buildings.

Last reviewed: July 6, 2026

Overview

This chapter of the California Historical Building Code (CHBC) provides alternative, performance‑oriented structural rules for buildings designated as qualified historical buildings or properties. Its purpose is to allow preservation‑sensitive solutions while maintaining a minimum level of structural performance to prevent partial or total collapse; see the chapter purpose, intent and scope in §8‑701.1–.3 for the foundational policy language.

Practically, the regulations require a qualified structural survey (§8‑703) and evaluation of gravity, wind and seismic capacity (§8‑705), and they set the lateral‑load evaluation criteria and limits (Chapter §8‑706). The CHBC permits reasonable alternatives to regular code provisions (including limited reductions in prescribed forces) but retains limits for certain occupancies and safety conditions; see §8‑702 and the load and seismic provisions in §8‑705–§8‑706.

The approach is intentionally flexible and performance‑based: preserving historic fabric and allowing archaic materials where appropriate (see Chapter 8‑8), while requiring corrective strengthening when members or systems are judged likely to produce life‑threatening collapse. The CHBC is to be applied only to qualified historic buildings as defined elsewhere in Part 8 and used in conjunction with the regular code when required.

In this section

Code references

Grounded in the retrieved California Historical Building Code — click a citation to read the verbatim passage:

  • CHBC § 8-7 High relevance — show source text

    12 2025 CALIFORNIA HISTORICAL BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    8-7 STRUCTURAL REGULATIONS

    SECTION 8-701 PURPOSE, INTENT AND SCOPE

    8-701.1 Purpose. The purpose of the CHBC is to provide alternative regulations to the regular code for the structural safety of buildings designated as qualified historical buildings or properties. The CHBC requires enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.

    8-701.2 Intent. The intent of this chapter is to encourage the preservation of qualified historical buildings or structures while providing standards for a minimum level of building performance with the objective of preventing partial or total structural collapse such that the overall risk of life-threatening injury as a result of structural collapse is low.

    8-701.3 Application. The alternative structural regulations provided by Section 8-705 are to be applied in conjunction with the regular code whenever a structural upgrade or reconstruction is undertaken for qualified historical buildings or properties.

    SECTION 8-702 GENERAL

    8-702.1 The CHBC shall not be construed to allow the enforcing agency to approve or permit a lower level of safety of structural design and construction than that which is reasonably equivalent to the regular code provisions in occupancies which are critical to the safety and welfare of the public at large, including, but not limited to, public and private schools, hospitals, municipal police and fire stations and essential services facilities.

    8-702.2 Nothing in these regulations shall prevent voluntary and partial seismic upgrades when it is demonstrated that such upgrades will improve life safety and when a full upgrade would not otherwise be required.

    SECTION 8-703 STRUCTURAL SURVEY

    8-703.1 Scope. When a structure or portion of a structure is to be evaluated for structural capacity under the CHBC, it shall be surveyed for structural conditions by an architect or engineer knowledgeable in historical structures. The survey shall evaluate deterioration or signs of distress. The survey shall determine the details of the structural framing and the system for resistance of gravity and lateral loads. Details, reinforcement and anchorage of structural systems and veneers shall be determined and documented where these members are relied on for seismic lateral resistance.

    8-703.2 The results of the survey shall be utilized for evaluating the structural capacity and for designing modifications to the structural system to reach compliance with this code.

    8-703.3 Historical records. Past historical records of the structure or similar structures may be used in the evaluation, including the effects of subsequent alterations.

    SECTION 8-704 NONHISTORICAL ADDITIONS AND NONHISTORICAL ALTERATIONS

    8-704.1 New nonhistorical additions and nonhistorical alterations which are structurally separated from an existing historical building or structure shall comply with regular code requirements.

    8-704.2 New nonhistorical additions which impose vertical or lateral loads on an existing structure shall not be permitted unless the affected part of the supporting structure is evaluated and strengthened, if necessary, to meet regular code requirements.

    Note: For use of archaic materials, see Chapter 8-8.

    SECTION 8-705 STRUCTURAL REGULATIONS

  • CHBC § 8-604 High relevance — show source text

    2025 CALIFORNIA HISTORICAL BUILDING CODE 11

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ACCESSIBILITY

    SECTION 8-604 EQUIVALENT FACILITATION

    Use of other designs and technologies, or deviation from particular technical and scoping requirements, are permitted if the application of the alternative provisions contained in Section 8-603 would threaten or destroy the historical significance or characterdefining features of the historical building or property.

    1. Such alternatives shall be applied only on an item-by- item or a case-by-case basis.
    2. Access provided by experiences, services, functions, materials and resources through methods including, but not limited to, maps, plans, videos, virtual reality and related equipment, at accessible levels. The alternative design and/or technologies used will provide substantially equivalent or greater accessibility to, and usability of, the facility.
    3. The official charged with the enforcement of the standards shall document the reasons for the application of the design and/or technologies and their effect on the historical significance or character-defining features. Such documentation shall be in accordance with Section 8-602.2, Item 2, and shall include the opinion and comments of state or local accessibility officials, and the opinion and comments of representative local groups of people with disabilities. Such documentation shall be retained in the permanent file of the enforcing agency. Copies of the required documentation should be available at the facility upon request.

    Note: For commercial facilities and places of public accommodation (Title III entities).

    Equivalent facilitation for an element of a building or property when applied as a waiver of an ADA accessibility requirement will not be entitled to the Federal Department of Justice certification of this code as rebuttable evidence of compliance for that element.

    12 2025 CALIFORNIA HISTORICAL BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    8-7 STRUCTURAL REGULATIONS

    SECTION 8-701 PURPOSE, INTENT AND SCOPE

    8-701.1 Purpose. The purpose of the CHBC is to provide alternative regulations to the regular code for the structural safety of buildings designated as qualified historical buildings or properties. The CHBC requires enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.

    8-701.2 Intent. The intent of this chapter is to encourage the preservation of qualified historical buildings or structures while providing standards for a minimum level of building performance with the objective of preventing partial or total structural collapse such that the overall risk of life-threatening injury as a result of structural collapse is low.

    8-701.3 Application. The alternative structural regulations provided by Section 8-705 are to be applied in conjunction with the regular code whenever a structural upgrade or reconstruction is undertaken for qualified historical buildings or properties.

    SECTION 8-702 GENERAL

    8-702.1 The CHBC shall not be construed to allow the enforcing agency to approve or permit a lower level of safety of structural design and construction than that which is reasonably equivalent to the regular code provisions in occupancies which are critical to the safety and welfare of the public at large, including, but not limited to, public and private schools, hospitals, municipal police and fire stations and essential services facilities.

    8-702.2 Nothing in these regulations shall prevent voluntary and partial seismic upgrades when it is demonstrated that such upgrades will improve life safety and when a full upgrade would not otherwise be required.

  • CHBC § 8-6 High relevance — show source text

    CHAPTER 8-6 ACCESSIBILITY . . . . . . . . . . . . . . . . . . . . . . . . 11

    Section

    8-601 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 11

    8-602 Basic Provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    8-603 Alternatives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    8-604 Equivalent Facilitation. . . . . . . . . . . . . . . . . . . . . . . . . . 12

    CHAPTER 8-7 STRUCTURAL REGULATIONS. . . . . . . . . . . . . 13

    Section

    8-701 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 13 8-702 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    8-703 Structural Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-704 Nonhistorical Additions and

    Nonhistorical Alterations . . . . . . . . . . . . . . . . . . . . . . . 13

    8-705 Structural Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . 13 8-706 Lateral Load Regulations. . . . . . . . . . . . . . . . . . . . . . . . 14

    CHAPTER 8-8 ARCHAIC MATERIALS AND METHODS OF

    CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . 15

    Section

    8-801 Purpose, Intent and Scope . . . . . . . . . . . . . . . . . . . . . . 15 8-802 General Engineering Approaches. . . . . . . . . . . . . . . . . 15 8-803 Nonstructural Archaic Materials. . . . . . . . . . . . . . . . . . 15

    8-804 Allowable Conditions for Specific Materials . . . . . . . 15 8-805 Masonry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 8-806 Adobe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    8-807 Wood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    8-808 Concrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

  • CHBC § 8-702.2 High relevance — show source text

    8-702.2 Nothing in these regulations shall prevent voluntary and partial seismic upgrades when it is demonstrated that such upgrades will improve life safety and when a full upgrade would not otherwise be required.

    SECTION 8-703 STRUCTURAL SURVEY

    8-703.1 Scope. When a structure or portion of a structure is to be evaluated for structural capacity under the CHBC, it shall be surveyed for structural conditions by an architect or engineer knowledgeable in historical structures. The survey shall evaluate deterioration or signs of distress. The survey shall determine the details of the structural framing and the system for resistance of gravity and lateral loads. Details, reinforcement and anchorage of structural systems and veneers shall be determined and documented where these members are relied on for seismic lateral resistance.

    8-703.2 The results of the survey shall be utilized for evaluating the structural capacity and for designing modifications to the structural system to reach compliance with this code.

    8-703.3 Historical records. Past historical records of the structure or similar structures may be used in the evaluation, including the effects of subsequent alterations.

    SECTION 8-704 NONHISTORICAL ADDITIONS AND NONHISTORICAL ALTERATIONS

    8-704.1 New nonhistorical additions and nonhistorical alterations which are structurally separated from an existing historical building or structure shall comply with regular code requirements.

    8-704.2 New nonhistorical additions which impose vertical or lateral loads on an existing structure shall not be permitted unless the affected part of the supporting structure is evaluated and strengthened, if necessary, to meet regular code requirements.

    Note: For use of archaic materials, see Chapter 8-8.

    SECTION 8-705 STRUCTURAL REGULATIONS

    8-705.1 Gravity loads. The capacity of the structure to resist gravity loads shall be evaluated and the structure strengthened as necessary. The evaluation shall include all parts of the load path. Where no distress is evident, and a complete load path is present, the structure may be assumed adequate by having withstood the test of time if anticipated dead and live loads will not exceed those historically present.

    8-705.2 Wind and seismic loads. The ability of the structure to resist wind and seismic loads shall be evaluated. Wind loads shall be considered when appropriate, but need not exceed 75 percent of the wind loads prescribed by the regular code. The evaluation shall be based on the requirements of Section 8-706.

    8.705.2.1 Any unsafe conditions in the lateral-load-resisting system shall be corrected, or alternative resistance shall be provided. When strengthening is required, additional resistance shall be provided to meet the minimum requirements of the CHBC. The strengthening measures shall be selected with the intent of meeting the performance objectives set forth in Section 8-701.2. The evaluation of structural members and structural systems for seismic loads shall consider the inelastic performance of structural members and their ability to maintain load-carrying capacity during the seismic loadings prescribed by the regular code.

    8.705.2.2 The architect or engineer shall consider additional measures with minimal loss of, and impact to, historical materials which will reduce damage and needed repairs in future earthquakes to better preserve the historical structure in perpetuity. These additional measures shall be presented to the owner for consideration as part of the rehabilitation or restoration.

    2025 CALIFORNIA HISTORICAL BUILDING CODE 13

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    STRUCTURAL REGULATIONS

  • CHBC § 8-706 High relevance — show source text

    SECTION 8-706 LATERAL LOAD REGULATIONS

    8-706.1 Seismic forces. Strength-level seismic forces used to evaluate the structure for resistance to seismic loads shall be based on the R -values tabulated in the regular code for similar lateral-force-resisting systems including consideration of the structural detailing of the members where such R -values exist. Where such R -values do not exist, an appropriate R -value shall be rationally assigned considering the structural detailing of the members.

    Exceptions:

    1. The forces need not exceed 0.75 times the seismic forces prescribed by the regular code requirements.
    2. For Risk Category I, II or III structures, near-fault increases in ground motion (maximum considered earthquake ground motion of 0.2 second spectral response greater than 150 percent at 5 percent damping) need not be considered when the fundamental period of the building is 0.5 seconds in the direction under consideration.
    3. For Risk Category I or II structures, the seismic base shear need not exceed 0.30W.
    4. For Risk Category III or IV structures, the seismic base shear need not exceed 0.40W.

    8-706.1.1 When a building is to be strengthened with the addition of a new lateral force resisting system, the R -value of the new system can be used when the new lateral force resisting system resists at least 75 percent of the building’s base shear regardless of its relative rigidity.

    8-706.1.2 Evaluation and seismic improvement of unreinforced masonry bearing wall buildings shall comply with the California Existing Building Code (CEBC), Appendix Chapter A1 2013 Edition, and as modified by the CHBC.

    Exceptions:

    1. Alternative standards may be used on a case-by-case basis when approved by the authority having jurisdiction. It shall be permitted to exceed the strength limitation of 100 psi in Section A108.2 of the CEBC when test data and building configuration supports higher values subject to the approval of the authority having jurisdiction.
    2. CEBC Section A102.2 shall not apply to Qualified Historical Buildings in Risk Category III buildings and other structures whose primary occupancies are public assembly with an occupancy load greater than 300.

    8-706.1.3 All deviations from the detailing provisions of the lateral-force-resisting systems shall be evaluated for stability and the ability to maintain load-carrying capacity at the expected inelastic deformations.

    8-706.2 Existing building performance. The seismic resistance may be based upon the ultimate capacity of the structure to perform, giving due consideration to ductility and reserve strength of the lateral-force-resisting system and materials while maintaining a reasonable factor of safety. Broad judgment may be exercised regarding the strength and performance of materials not recognized by regular code requirements. (See Chapter 8-8, Archaic Materials and Methods of Construction.)

    8-706.2.1 All structural materials or members that do not comply with detailing and proportioning requirements of the regular code shall be evaluated for potential seismic performance and the consequence of non-compliance. All members that would be reasonably expected to fail and lead to collapse or life threatening injury when subjected to seismic demands shall be judged unacceptable, and appropriate structural strengthening shall be developed.

    8-706.3 Load path. A complete and continuous load path, including connections, from every part or portion of the structure to the ground shall be provided for the required forces. It shall be verified that the structure is adequately tied together to perform as a unit when subjected to earthquake forces.

  • CHBC § 8-705.1 High relevance — show source text

    8-705.1 Gravity loads. The capacity of the structure to resist gravity loads shall be evaluated and the structure strengthened as necessary. The evaluation shall include all parts of the load path. Where no distress is evident, and a complete load path is present, the structure may be assumed adequate by having withstood the test of time if anticipated dead and live loads will not exceed those historically present.

    8-705.2 Wind and seismic loads. The ability of the structure to resist wind and seismic loads shall be evaluated. Wind loads shall be considered when appropriate, but need not exceed 75 percent of the wind loads prescribed by the regular code. The evaluation shall be based on the requirements of Section 8-706.

    8.705.2.1 Any unsafe conditions in the lateral-load-resisting system shall be corrected, or alternative resistance shall be provided. When strengthening is required, additional resistance shall be provided to meet the minimum requirements of the CHBC. The strengthening measures shall be selected with the intent of meeting the performance objectives set forth in Section 8-701.2. The evaluation of structural members and structural systems for seismic loads shall consider the inelastic performance of structural members and their ability to maintain load-carrying capacity during the seismic loadings prescribed by the regular code.

    8.705.2.2 The architect or engineer shall consider additional measures with minimal loss of, and impact to, historical materials which will reduce damage and needed repairs in future earthquakes to better preserve the historical structure in perpetuity. These additional measures shall be presented to the owner for consideration as part of the rehabilitation or restoration.

    2025 CALIFORNIA HISTORICAL BUILDING CODE 13

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    STRUCTURAL REGULATIONS

    SECTION 8-706 LATERAL LOAD REGULATIONS

    8-706.1 Seismic forces. Strength-level seismic forces used to evaluate the structure for resistance to seismic loads shall be based on the R -values tabulated in the regular code for similar lateral-force-resisting systems including consideration of the structural detailing of the members where such R -values exist. Where such R -values do not exist, an appropriate R -value shall be rationally assigned considering the structural detailing of the members.

    Exceptions:

    1. The forces need not exceed 0.75 times the seismic forces prescribed by the regular code requirements.
    2. For Risk Category I, II or III structures, near-fault increases in ground motion (maximum considered earthquake ground motion of 0.2 second spectral response greater than 150 percent at 5 percent damping) need not be considered when the fundamental period of the building is 0.5 seconds in the direction under consideration.
    3. For Risk Category I or II structures, the seismic base shear need not exceed 0.30W.
    4. For Risk Category III or IV structures, the seismic base shear need not exceed 0.40W.

    8-706.1.1 When a building is to be strengthened with the addition of a new lateral force resisting system, the R -value of the new system can be used when the new lateral force resisting system resists at least 75 percent of the building’s base shear regardless of its relative rigidity.

    8-706.1.2 Evaluation and seismic improvement of unreinforced masonry bearing wall buildings shall comply with the California Existing Building Code (CEBC), Appendix Chapter A1 2013 Edition, and as modified by the CHBC.

    Exceptions:

  • CHBC § 8-706.3 High relevance — show source text

    8-706.3 Load path. A complete and continuous load path, including connections, from every part or portion of the structure to the ground shall be provided for the required forces. It shall be verified that the structure is adequately tied together to perform as a unit when subjected to earthquake forces.

    8-706.4 Parapets. Parapets and exterior decoration shall be investigated for conformance with regular code requirements for anchorage and ability to resist prescribed seismic forces.

    An exception to regular code requirements shall be permitted for those parapets and decorations which are judged not to be a hazard to life safety.

    8-706.5 Nonstructural features. Nonstructural features of historical structure, such as exterior veneer, cornices and decorations, which might fall and create a life safety hazard in an earthquake, shall be evaluated. Their ability to resist seismic forces shall be verified, or the feature shall be strengthened with improved anchorage when appropriate.

    8-706.5.1 Partitions and ceilings of corridors and stairways serving an occupant load of 30 or more shall be investigated to determine their ability to remain in place when the building is subjected to earthquake forces.

    8-706.5.2 Seismic forces used to evaluate and improve nonstructural components and their anchorage, where required, shall comply with ASCE 41 or need not exceed 0.75 times the seismic forces prescribed by the requirements of the regular code.

    14 2025 CALIFORNIA HISTORICAL BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    8-8 ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION

    SECTION 8-801 PURPOSE, INTENT AND SCOPE

    8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.

    8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.

    8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.

    SECTION 8-802 GENERAL ENGINEERING APPROACHES

    Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.

    SECTION 8-803 NONSTRUCTURAL ARCHAIC MATERIALS

  • CHBC § 8-1001 High relevance — show source text

    Section

    8-1001 Purpose and Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 8-1002 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 8-1003 Site Relations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    APPENDIX A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    HISTORY NOTE APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    2025 CALIFORNIA HISTORICAL BUILDING CODE ix

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    x 2025 CALIFORNIA HISTORICAL BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    8-1 ADMINISTRATION

    Note: The California Historical Building Code, Part 8 of Title 24, governs for all qualified historical buildings or properties in the State of California.

    SECTION 8-101 TITLE, PURPOSE AND INTENT

    8-101.1 Title. These regulations shall be known as the California Historical Building Code and will be referred to herein as “the CHBC.”

    8-101.2 Purpose. The purpose of the CHBC is to provide regulations for the preservation, restoration, rehabilitation, relocation or reconstruction of buildings or properties designated as qualified historical buildings or properties (as defined in Chapter 8-2). The CHBC is intended to provide solutions for the preservation of qualified historical buildings or properties, to promote sustainability, to provide access for persons with disabilities, to provide a cost-effective approach to preservation, and to provide for the reasonable safety of the occupants or users. The CHBC requires enforcing agencies to accept solutions that are reasonably equivalent to the regular code (as defined in Chapter 8-2) when dealing with qualified historical buildings or properties.

    8-101.3 Intent. The intent of the CHBC is to facilitate the preservation and continuing use of qualified historical buildings or properties while providing reasonable safety for the building occupants and access for persons with disabilities.

    SECTION 8-102 APPLICATION

    8-102.1 Application. The CHBC is applicable to all issues regarding code compliance for qualified historical buildings or properties. The CHBC may be used in conjunction with the regular code to provide solutions to facilitate the preservation of qualified historical buildings or properties. The CHBC shall be used by any agency with jurisdiction and whenever compliance with the code is required for qualified historical buildings or properties.

    1. State or local enforcing agency. The state or local enforcing agency shall apply the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, reconstruction, rehabilitation, relocation or continued use of a qualified historical building or property when so elected by the private property owner.
    2. **State agencies.
  • CHBC § 8-101.1 Medium relevance — show source text

    8-101.1 Title. These regulations shall be known as the California Historical Building Code and will be referred to herein as “the CHBC.”

    8-101.2 Purpose. The purpose of the CHBC is to provide regulations for the preservation, restoration, rehabilitation, relocation or reconstruction of buildings or properties designated as qualified historical buildings or properties (as defined in Chapter 8-2). The CHBC is intended to provide solutions for the preservation of qualified historical buildings or properties, to promote sustainability, to provide access for persons with disabilities, to provide a cost-effective approach to preservation, and to provide for the reasonable safety of the occupants or users. The CHBC requires enforcing agencies to accept solutions that are reasonably equivalent to the regular code (as defined in Chapter 8-2) when dealing with qualified historical buildings or properties.

    8-101.3 Intent. The intent of the CHBC is to facilitate the preservation and continuing use of qualified historical buildings or properties while providing reasonable safety for the building occupants and access for persons with disabilities.

    SECTION 8-102 APPLICATION

    8-102.1 Application. The CHBC is applicable to all issues regarding code compliance for qualified historical buildings or properties. The CHBC may be used in conjunction with the regular code to provide solutions to facilitate the preservation of qualified historical buildings or properties. The CHBC shall be used by any agency with jurisdiction and whenever compliance with the code is required for qualified historical buildings or properties.

    1. State or local enforcing agency. The state or local enforcing agency shall apply the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, reconstruction, rehabilitation, relocation or continued use of a qualified historical building or property when so elected by the private property owner.
    2. State agencies. All state agencies shall apply the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, rehabilitation, safety, relocation, reconstruction or continued use of qualified historical buildings or properties.

    8-102.1.1 Additions, alterations and repairs. It is the intent of the CHBC to allow nonhistorical expansion or addition to a qualified historical building or property, provided nonhistorical additions shall conform to the requirements of the regular code (as defined in Chapter 8-2).

    8-102.1.2 Relocation. Relocated qualified historical buildings or properties shall be sited to comply with the regular code or with the solutions listed in the CHBC. Nonhistorical new construction related to relocation shall comply with the regular code. Reconstruction and restoration related to relocation is permitted to comply with the provisions in the CHBC.

    8-102.1.3 Change of occupancy. For change of use or occupancy, see Chapter 8-3, Use and Occupancy.

    8-102.1.4 Continued use. Qualified historical buildings or properties may have their existing use or occupancy continued if such use or occupancy conformed to the code or to the standards of construction in effect at the time of construction, and such use or occupancy does not constitute a distinct hazard to life safety as defined in the CHBC.

    8-102.1.5 Unsafe buildings or properties. When a qualified historical building or property is determined to be unsafe as defined in the regular code, the requirements of the CHBC are applicable to the work necessary to correct the unsafe conditions. Work to remediate the buildings or properties need only address the correction of the unsafe conditions, and it shall not be required to bring the entire qualified historical building or property into compliance with regular code.

  • CHBC § 3104F.5 Medium relevance — show source text

    3104F.5 Nonstructural components, nonbuilding structures and building structures. Nonstructural components, nonbuilding struc- tures and building structures at MOTs shall be assessed for Level 2 seismic performance (see Section 3104F.2.1). Consideration shall be given to the adequacy and condition of supports and attachments (or anchorage), strength, flexibility, relative displacement, P-delta effects, and seismically-induced interaction with other components and structures.

    3104F.5.1 General. Nonstructural components are mechanical, electrical and architectural components (such as piping/pipelines, loading arms, lifting equipment (winches and cranes), spill prevention equipment, pumps, instrumentation and storage cabinets, and lighting fixtures) that may be required to resist the effects of earthquake.

    Nonbuilding structures (such as gangways, hose towers and racks) are self-supporting structures that carry gravity loads and may be required to resist the effects of earthquake, but are not building structures (such as control rooms). For building structures, see Section 3104F.5.6.

    Critical systems are nonstructural components, nonbuilding structures or building structures that shall remain operational or those whose failure could impair emergency operations following an earthquake, to prevent major oil spills and to protect public health, safety and the environment. A seismic assessment of the survivability and continued operation (related to personnel safety, oil spill prevention or response) during a Level 2 earthquake (see Table 31F-4-1) shall be performed for critical systems, including but not limited to, fire protection, emergency shutdown and electrical power systems.

    3104F.5.2 Seismic assessment. For existing (E) nonstructural components, nonbuilding structures and building structures and their supports and attachments, seismic assessment shall be performed in accordance with CalARP [4.8] or ASCE Guidelines [4.9], except for piping/pipelines which shall be evaluated per Section 3109F. If seismic evaluation and/or strengthening are required, it shall be performed in accordance with Section 3104F.5.2.1.

    For new (N) nonstructural components, nonbuilding structures and building structures and their supports and attachments, seis- mic evaluation and design shall be performed in accordance with Section 3104F.5.2.1, except for piping/pipelines which shall be evaluated per Section 3109F.

    3104F.5.2.1 Seismic evaluation, strengthening and design. For evaluation, strengthening and design of nonstructural compo- nents, nonbuilding structures and building structures, seismic forces (demands) shall be obtained from Section 3104F.5. The seismic adequacy of nonstructural components shall be demonstrated as specified in ASCE/SEI 7 [4.1]. Structures shall be analyzed in accordance with Section 3107F.5. Supports and attachments shall be assessed in accordance with Sections 3107F.7.

    3104F.5.3 Contribution to global response of MOT structures. Nonstructural components, nonbuilding structures and building structures permanently attached to MOT structures, including, but not limited to, pipelines, loading arms, hose towers/racks, raised platforms, control rooms and vapor control equipment, may affect the global structural response. In such cases, the seismic charac- teristics (mass and/or stiffness) of the nonstructural components, nonbuilding structures and building structures shall be considered _in computing global seismic response of the MOT structures.

  • CHBC § 8-503 Medium relevance — show source text

    2025 CALIFORNIA HISTORICAL BUILDING CODE 9

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    SECTION 8-503 ESCAPE OR RESCUE WINDOWS AND DOORS

    Basements in dwelling units and every sleeping room below the fourth floor shall have at least one openable window or door approved for emergency escape which shall open directly into a public street, public way, yard or exit court. Escape or rescue windows or doors shall have a minimum clear area of 3.3 square feet (0.31 m [2] ) and a minimum width or height dimension of 18 inches (457 mm) and be operable from the inside to provide a full, clear opening without the use of special tools.

    SECTION 8-504 RAILINGS AND GUARDRAILS

    The height of railings and guard railings and the spacing of balusters may continue in their historical height and spacing unless a distinct hazard has been identified or created by a change in use or occupancy.

    10 2025 CALIFORNIA HISTORICAL BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    8-6 ACCESSIBILITY

    SECTION 8-601 PURPOSE, INTENT AND SCOPE

    8-601.1 Purpose. The purpose of the CHBC is to provide alternative regulations to facilitate access and use by persons with disabilities to and throughout facilities designated as qualified historical buildings or properties. These regulations require enforcing agencies to accept alternatives to regular code when dealing with qualified historical buildings or properties.

    8-601.2 Intent. The intent of this chapter is to preserve the integrity of qualified historical buildings and properties while providing access to and use by persons with disabilities.

    8-601.3 Scope. The CHBC shall apply to every qualified historical building or property that is required to provide access to persons with disabilities.

    1. Provisions of this chapter do not apply to new construction or reconstruction/replicas of historical buildings.
    2. Where provisions of this chapter apply to alteration of qualified historical buildings or properties, alteration is defined in California Building Code (CBC), Chapter 2.

    8-601.4 General application. The provisions in the CHBC apply to local, state and federal governments (Title II entities); alteration of commercial facilities and places of public accommodation (Title III entities); and barrier removal in commercial facilities and places of public accommodation (Title III entities). Except as noted in this chapter.

    SECTION 8-602 BASIC PROVISIONS

    8-602.1 Regular code. The regular code for access for people with disabilities (Title 24, Part 2, Vol. 1, Chapter 11B) shall be applied to qualified historical buildings or properties unless strict compliance with the regular code will threaten or destroy the historical significance or character-defining features of the building or property.

    8-602.2 Alternative provisions. If the historical significance or character-defining features are threatened, alternative provisions for access may be applied pursuant to this chapter, provided the following conditions are met:

    1. These provisions shall be applied only on an item-by-item or a case-by-case basis.
    2. Documentation is provided, including meeting minutes or letters, stating the reasons for the application of the alternative provisions. Such documentation shall be retained in the permanent file of the enforcing agency.

    SECTION 8-603 ALTERNATIVES

  • CHBC § 323-9843 Medium relevance — show source text

    State Librarian [SL]

    library.ca.gov csllaw@library.ca.gov (916) 323-9843 Public Library Construction & Renovation

    2025 CALIFORNIA HISTORICAL BUILDING CODE v

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    HOW TO DETERMINE WHERE CHANGES HAVE BEEN MADE

    Symbols in the margins indicate where changes have been made or language has been deleted.

    This symbol indicates that a change has been made.

    • This symbol indicates deletion of language.

    vi 2025 CALIFORNIA HISTORICAL BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PART 8 CONTAINS ALTERNATIVE REGULATIONS

    FOR QUALIFIED HISTORICAL BUILDINGS

    The California Historical Building Code (CHBC) is unique among state regulations. The authoring of the original CHBC required state agencies promulgating regulations for building construction to work in harmony with representatives of other design and construction disciplines. The result was a totally new approach to building codes for historical structures, which maintains currently acceptable life safety standards. These regulations are also unique in that they are performance oriented rather than prescriptive. The provisions of the CHBC are to be applied by the enforcing authority of every city, county, city and county, or state agency in permitting repairs, alterations and additions necessary for the preservation, rehabilitation, relocation, related construction, change of use or continued use of a qualified historical building. The authority for use of the CHBC is vested in Sections 18950 through 18961 of the Health and Safety Code. Section 18954 states, “The building department of every city or county or other local agency that has jurisdiction over the enforcement of code within its legal authority shall apply the alternative standards and regulations adopted pursuant to Section 18959.5 in permitting repairs, alterations, and additions necessary for the preservation, restoration, rehabilitation, safety, moving, or continued use of a qualified historical building or structure. A state agency shall apply the alternative regulations adopted pursuant to Section 18959.5 in permitting repairs, alterations, and additions necessary for the preservation, restoration, rehabilitation, safety, moving, or continued use of a qualified historical building or structure.” However, be aware that in order to use the CHBC, the structure under consideration must be qualified by being designated as an historical building or structure. Section 18955 states, “For the purposes of this part, a qualified historical building or structure is any structure or property, collection of structures, and their related sites deemed of importance to the history, architecture, or culture of an area by an appropriate local or state governmental jurisdiction. This shall include historical buildings or structures on existing or future national, state or local historical registers or official inventories, such as the National Register of Historic Places, State Historical Landmarks, State Points of Historical Interest, and city or county registers or inventories of historical or architecturally significant sites, places, historic districts, or landmarks. This shall also include places, locations, or sites identified on these historical registers or official inventories and deemed of importance to the history, architecture, or culture of an area by an appropriate local or state governmental jurisdiction.” The regulations of the CHBC have the same authority as state law and are to be considered as such. Liability is the same as for prevailing law. The intent of the CHBC is to save California’s architectural heritage by recognizing the unique construction problems inherent in historical buildings and by providing a code to deal with these problems.

Frequently asked questions

When do the CHBC structural rules apply?

The CHBC structural provisions apply to buildings designated as qualified historical buildings or properties and when the owner or enforcing agency elects to use Part 8 solutions for preservation, repair, alteration, relocation or continued use; see the CHBC application and administration provisions.

How much can seismic and wind forces be reduced under the CHBC?

Seismic and wind evaluations may be scaled under CHBC rules—for example, wind loads need not exceed 0.75 of the regular‑code wind loads, and seismic forces used for evaluation need not exceed 0.75 of regular‑code seismic forces in many cases; Chapter §8‑706 lists the detailed exceptions and caps (including base shear limits expressed as fractions of W).

Are archaic materials and historic construction methods allowed?

Yes. Chapter 8‑8 of the CHBC provides the framework for using archaic materials and methods, including how allowable strengths are assigned, testing expectations, and the need for an informed architect or engineer to document and justify assigned strength values.