Title 24 · California Energy Code

Acceptance testing, Certified Lighting Controls Acceptance Test Technician (CLCATT) and documentation

Before a building gets occupancy, required lighting controls must be functionally tested and certified using the NA7 procedures and a Certificate of Acceptance; if Part 1 requires certification those tests must be run and documented by a Certified Lighting Controls Acceptance Test Technician (CLCATT) who includes their certification ID on the certificate.

Last reviewed: July 6, 2026

What the code requires — 2–4 sentences

Before final occupancy is granted, indoor and outdoor lighting controls required by Part 6 must be acceptance‑tested and a Certificate of Acceptance submitted showing the systems meet the Acceptance Requirements. The acceptance tests referenced in the code are the tests in the Reference Nonresidential Appendices (for example NA7.6 and NA7.8) and the acceptance testing required by § 130.4 and § 160.5(e) must, when certification is required by Part 1, be performed by a Certified Lighting Controls Acceptance Test Technician (CLCATT). The CLCATT must disclose a valid CLCATT certification identification number on the Certificate of Acceptance and complete certificate documentation in accordance with § 10‑103(a).

The single most important rule: Lighting controls required by Part 6 must be functionally acceptance‑tested and certified before occupancy; when Part 1 requires certification the testing must be performed and documented by a CLCATT.

Requirements in detail

Who must perform the tests

  • The acceptance testing specified in § 130.4 and § 160.5(e) must be performed by a Certified Lighting Controls Acceptance Test Technician (CLCATT) when certification is triggered by Title 24, Part 1 (Section 10‑103.1). The CLCATT must disclose a valid CLCATT certification identification number on the Certificate of Acceptance. If employed, the CLCATT must be employed by a Certified Lighting Controls Acceptance Test Employer.

What systems / controls require acceptance testing

  • Indoor and outdoor lighting controls installed to comply with Part 6 (examples listed): automatic daylighting controls, lighting shut‑OFF controls, demand response lighting controls, outdoor lighting controls, and systems qualifying for the Institutional Tuning Power Adjustment Factor. The code directs testing protocols to Reference Nonresidential Appendix NA7.6 (indoor/demand/daylight tests) and NA7.8 (outdoor tests).

When testing and paperwork are required

  • Tests must be completed and a Certificate of Acceptance submitted to the enforcement agency before an occupancy permit is granted. Installation certificates (separate but related) are required to demonstrate plan/installation compliance per § 10‑103(a). The CLCATT signs and completes Certificate of Acceptance fields per the Part‑1 requirements.

What must appear on the Certificate(s)

  • A Certificate of Acceptance must certify that the equipment and systems meet the Acceptance Requirements and must include the CLCATT’s certification identification number when a CLCATT performed the testing. Installation Certificates are required for lighting control systems and must certify compliance with applicable Part 6 requirements and the applicable NA7.7 installation certification appendices.

Decision table — Quick reference for the control points

Decision / dimension Key value(s) Code Reference
Who performs acceptance testing when Part‑1 certification required Certified Lighting Controls Acceptance Test Technician (CLCATT) (and employer rules for employees) § 130.4(c)
Which controls require testing Daylight responsive, shut‑OFF, demand responsive, outdoor controls, systems using Institutional Tuning PAF (tests in NA7.6 / NA7.8) § 160.5(e)1
When to submit Certificate Before occupancy permit § 160.5(e)1
What certificate must include (when CLCATT used) CLCATT certification identification number; completed Certificate of Acceptance per § 10‑103(a)4 § 130.4(c) and § 160.5(e)3
Test procedures reference Tests per Reference Nonresidential Appendix NA7.6 (indoor/demand/daylight) and NA7.8 (outdoor) § 160.5(e)1
Small‑scale alteration exception Acceptance testing not required where controls are added to control 20 or fewer luminaires (see exceptions to alteration provisions) Alterations exceptions (see cross references)

How the CLCATT requirement is documented in the code

  • The code explicitly ties the technician requirement to Part 1 certification triggers: when Title 24, Part 1 requires certification of acceptance testing, the tests in § 130.4 (nonresidential lighting controls) and § 160.5(e) (multifamily common areas and other Part 6 controls) must be performed by a CLCATT and the CLCATT must provide a valid certification ID on the Certificate.

Exceptions & special cases

  • Alterations with controls added to 20 or fewer luminaires are not required to comply with the acceptance testing requirements of § 160.5(e) (this appears as an exception in the alteration provisions). If your project triggers other alteration thresholds (10% / 50% replacement rules), different acceptance or luminaire requirements may apply — always check the alteration exceptions and thresholds referenced in the code.
  • Factory‑tested, factory‑calibrated equipment sometimes has narrower functional testing requirements in the NA7 appendices; the code and the NA7 appendices contain the specific exceptions.
  • If the CLCATT is operating as an employee, they must be employed by a Certified Lighting Controls Acceptance Test Employer (employment vs. independent contractor is distinguished in the code).

Common mistakes

  • Assuming submittal of an installation certificate alone satisfies acceptance testing — the code requires a separate Certificate of Acceptance documenting the acceptance test results before occupancy.
  • Leaving the CLCATT ID blank — when a CLCATT performs the test the certificate must list the valid CLCATT certification identification number.
  • Not following the NA7 test procedures — the code requires testing per the referenced NA7 procedures (e.g., NA7.6 for indoor/demand/daylight, NA7.8 for outdoor). Running different functional checks without aligning to NA7 may not meet the acceptance criteria.
  • Failing to confirm whether Part 1 certification is triggered — the requirement for CLCATT only applies when Part 1 requires certification; otherwise acceptance testing still applies but the Part 1 CLCATT specific rule is not triggered. Verify Section 10‑103.1 triggers.

Worked example — concrete scenario with numbers

Scenario: New 4‑story multifamily building has a common‑area corridor lighting system with 60 luminaires and daylight sensors plus demand‑response capability. The owner seeks final occupancy.

  1. Does acceptance testing apply? Yes — indoor lighting controls serving common areas are listed under § 160.5(e)1 and must be certified as meeting NA7.6 Acceptance Requirements before occupancy.
  2. Who must perform the tests? Because Title 24, Part 1 requires certification of the acceptance testing, the tests identified in § 160.5(e) must be performed by a CLCATT, who must provide their CLCATT certification ID on the Certificate of Acceptance.
  3. What tests will be run? Daylight responsive control tests (NA7.6.1), lighting shut‑OFF and demand response tests as applicable (NA7.6.2 / NA7.6.3), and corridor control functional checks per NA7.6. The CLCATT follows the NA7.6 procedures and documents results.
  4. Paperwork and timing: The completed Certificate of Acceptance, including the CLCATT ID and completed test results, is submitted to the enforcing agency before issuance of the occupancy permit per § 160.5(e)1 and Part 1 procedures.
  5. Exception check: Because 60 luminaires are involved (more than the 20‑luminaire alteration exception), the acceptance testing requirement applies — the exception for ≤20 luminaire control additions does not apply.

Related provisions

  • § 130.4 — Acceptance testing for lighting controls (see requirement to use CLCATT where Part 1 certification applies).
  • § 130.4(c) — CLCATT identification and certificate completion requirements.
  • § 160.5(e) — Lighting control acceptance, test references (NA7.6 / NA7.8), Certificate of Acceptance timing and installation certificate requirements.
  • § 10‑103(a) — Certificate of Acceptance and installation certificate submission procedures that the CLCATT uses to submit documentation.
  • Reference Nonresidential Appendix NA7.6 / NA7.8 — The specific test procedures to be executed for indoor/demand/daylight and outdoor controls (referenced by § 160.5(e)1).

If you need the exact NA7 test procedure steps or the Certificate of Acceptance form fields (the code references the NA7 appendices and § 10‑103 forms), say so and I will extract and summarize those Appendix/Part‑1 form details next. The code text requires those procedures and the CLCATT ID but the step‑by‑step NA7 procedures and the actual Certificate form are in the referenced appendices and Part 1 documents.

Code references

Grounded in the retrieved California Energy Code — click a citation to read the verbatim passage:

  • § 6.4. High relevance — show source text
    1. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and
    2. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4.
    3. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5.

    (b) Lighting control installation certificate requirements. To be recognized for compliance with Part 6 an installation certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable:

    1. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6 it complies with the applicable requirements of Section 110.9; and complies with Reference Nonresidential Appendix NA7.7.1.

    2. Certification that when an energy management control system is installed to function as a lighting control required by Part 6 it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with Reference Nonresidential Appendix NA7.7.2.

    3. Reserved.

    4. Reserved.

    5. Certification that interlocked lighting systems used to serve an approved area comply with Section 140.6(a)1; and comply with Reference Nonresidential Appendix NA7.7.4.

    6. Certification that lighting controls installed to earn a lighting power adjustment factor (PAF) comply with Section 140.6(a)2; and comply with Reference Nonresidential Appendix NA7.7.5.

    2025 CALIFORNIA ENERGY CODE 101

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

    1. Certification that additional lighting wattage installed for a videoconference studio complies with Section 140.6(c)2Gvii; and complies with Reference Nonresidential Appendix NA7.7.6.

    (c) When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 130.4 shall be performed by a certified lighting controls acceptance test technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a certified lighting controls acceptance test employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved acceptance test technician certification provider. The CLCATT shall complete all certificate of acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.

    Note: Authority cited: Sections 25402, 25402.1 and 25213, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code .

    SECTION 130.5—ELECTRICAL POWER DISTRIBUTION SYSTEMS

  • § 6.4. High relevance — show source text

    F. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and G. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4. H. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5. 2. Lighting control installation certificate requirements. To be recognized for compliance with Part 6, an Installation Certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable: A. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6, it complies with the applicable requirements of Section 110.9 and complies with Reference Nonresidential Appendix NA7.7.1.

    B. Certification that when an energy management control system is installed to function as a lighting control required by Part 6, it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 160, 170 and 180, and complies with Reference Nonresidential Appendix NA7.7.2. C. Certification that interlocked lighting systems used to serve an approved area comply with Section 170.2(e)2A and comply with Reference Nonresidential Appendix NA7.7.4. D. Certification that lighting controls installed to earn a lighting power adjustment factor (PAF) comply with Section 170.2(e)2B and comply with Reference Nonresidential Appendix NA7.7.5.

    E. Reserved.

    1. When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 160.5(e) shall be performed by a Certified Lighting Controls Acceptance Test Technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a Certified Lighting Controls Acceptance Test Employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved Acceptance Test Technician Certification Provider. The CLCATT shall complete all Certificate of Acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.

    NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .

    SECTION 160.6—MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEMS

    Multifamily buildings shall comply with the applicable requirements of Sections 160.6(a) through 160.6(e).

    (a) Service electrical metering. Each electrical service or feeder that provides power to the common use areas (interior and exterior) shall have a permanently installed metering system that measures electrical energy use in accordance with Table 160.6-A.

    Exception to Section 160.6(a): Service or feeder for which the utility company provides a metering system for the multifamily building that indicates instantaneous kW demand and kWh for a utility-defined period.

    232 2025 CALIFORNIA ENERGY CODE

  • § 140.6 High relevance — show source text

    2025 CALIFORNIA ENERGY CODE 101

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

    1. Certification that additional lighting wattage installed for a videoconference studio complies with Section 140.6(c)2Gvii; and complies with Reference Nonresidential Appendix NA7.7.6.

    (c) When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 130.4 shall be performed by a certified lighting controls acceptance test technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a certified lighting controls acceptance test employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved acceptance test technician certification provider. The CLCATT shall complete all certificate of acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.

    Note: Authority cited: Sections 25402, 25402.1 and 25213, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code .

    SECTION 130.5—ELECTRICAL POWER DISTRIBUTION SYSTEMS

    Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 130.5(a) through 130.5(e).

    (a) Service electrical metering. Each electrical service or feeder shall have a permanently installed metering system which measures electrical energy use in accordance with Table 130.5-A.

    Exception 1 to Section 130.5(a): Service or feeder for which the utility company provides a metering system that indicates instantaneous kW demand and kWh for a utility-defined period.

    Exception 2 to Section 130.5(a): Electrical power distribution systems subject to California Electrical Code Article 517.

    TABLE 130.5-A—MINIMUM REQUIREMENTS FOR METERING OF ELECTRICAL LOAD Col2 Col3 Col4 Col5
    METERING FUNCTIONALITY ELECTRICAL
    SERVICES RATED
    50 kVA OR LESS
    ELECTRICAL SERVICES
    RATED MORE THAN 50 kVA
    AND LESS THAN OR EQUAL
    TO 250 kVA
    ELECTRICAL SERVICES
    RATED MORE THAN 250 kVA
    AND LESS THAN OR EQUAL
    TO 1000 kVA
    ELECTRICAL
    SERVICES RATED
    MORE THAN 1000
    kVA
    Instantaneous (at the time) kW
    demand
    Required Required Required Required
    Historical peak demand (kW) Not required Not required Required Required
    Tracking kWh for a user-definable
    period
    Required Required Required Required
    kWh per rate period Not required Not required Not required Required
  • § 10-103.1 High relevance — show source text
    1. When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 160.5(e) shall be performed by a Certified Lighting Controls Acceptance Test Technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a Certified Lighting Controls Acceptance Test Employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved Acceptance Test Technician Certification Provider. The CLCATT shall complete all Certificate of Acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.

    NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .

    SECTION 160.6—MANDATORY REQUIREMENTS FOR ELECTRIC POWER DISTRIBUTION SYSTEMS

    Multifamily buildings shall comply with the applicable requirements of Sections 160.6(a) through 160.6(e).

    (a) Service electrical metering. Each electrical service or feeder that provides power to the common use areas (interior and exterior) shall have a permanently installed metering system that measures electrical energy use in accordance with Table 160.6-A.

    Exception to Section 160.6(a): Service or feeder for which the utility company provides a metering system for the multifamily building that indicates instantaneous kW demand and kWh for a utility-defined period.

    232 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS

    TABLE 160.6-A—MINIMUM REQUIREMENTS FOR METERING OR SUBMETERING OF ELECTRICAL LOAD Col2 Col3 Col4 Col5
    METERING
    FUNCTIONALITY
    **ELECTRICAL SERVICES1 **
    RATED 50 KVA OR LESS
    **ELECTRICAL SERVICES1 **
    RATED MORE THAN 50
    KVA AND LESS THAN OR
    EQUAL TO 250 KVA
    **ELECTRICAL SERVICES1 **
    RATED MORE THAN 250
    KVA AND LESS THAN OR
    EQUAL TO 1000 KVA
    **ELECTRICAL SERVICES1 **
    RATED MORE THAN
    1000 KVA
    Instantaneous (at the time) kW
    demand
    Required Required Required Required
    Historical peak demand (kW) Not required Not required Required Required
    Tracking kWh for a user-
    definable period
    Required Required Required Required
    kWh per rate period Not required Not required Not required Required
    1. “Electrical services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size
    to the common use areas.
    1. “Electrical services” applies to the building service-entrance rating or to the submetering service.
  • § 160.5 High relevance — show source text

    5-B, 160.5(c)2, 160.5(d), 160.5(e), 170.2(e)2B, Table 170.2L, 180.2(b)4B Astronomical time-clock control Table 140.6-C, 150.0(k)3A, 160.5(a)3A, Table 170.2-M Automatic daylighting controls 110.9(b)2, 130.1(d), 130.1(f)3, 6, 140.6(a)2L, G, 160.5(b)4D, F, 170.2(e)2B, 180.3(b)4B Automatic lighting controls 140.6(a)2G, 170.2(e)2B Automatic scheduling controls 130.2(c)2, 160.5(c)2B Automatic time switch control 120.2(e)1, 120.6(b)3A, 130.1(f)5, 130.3(a)1, 130.3(a)2, 130.5(d)1, 150.0(k)3, 160.3(a)2D, 160.5(a)3A, 160.5(b)4F, 130.6(d)1 Certified Lighting Controls Acceptance Test Technician (CLCATT) 130.4(c), 160.5(e)3 Continuous dimming 140.6(a)2H, L, Table 140.6-A, 160.5(b)4D,Table 160.5-B, 170.2(e)2B, Table 170.2-L Control requirements for indoor lighting system alterations Table 141.0-F, Table 180.2-E

    Countdown timer switch 130.1(c)2,160.5(b)4C, 160.6(d)1 Daylight dimming plus OFF control Table 140.6-A, Table 170.2-L Daylighting controls 110.9(b)2, 130.1(d), 140.6(a)2L, Table 141.0-F, 160.5(b)4D, 170.2(e)2B, Table 180.2-E Delay settings 110.9(b)2A Dimmer 110.9(b)3, 130.3(a)2B, 150.0(k)1E, 150.0(k)2B, F,160.5(a)1E, 160.5(a)2B, F, 160.5(d)2B Existing luminaire 130.2(b), 141.0(b)2L, 160.5(c)1, 180.2(b)4B Holiday shutoff 110.9(b)1A, 130.1(c)4 Indoor lighting controls 130.1, 150.0(k)2, 160.5(a)2, 160.5(b)4 Infrared sensor 140.6(a)2I, 170.2(e)2B Light sensor 110.9(b)2C Lighting circuits 141.0(b)2I, 180.2(b)4B Lighting control acceptance 130.4, 160.5(e)

  • § 160.5 High relevance — show source text

    (e) Lighting control acceptance and installation certificate requirement. Multifamily common use areas shall comply with the applicable requirements of Sections 160.5(e)1 through 160.5(e)3.

    1. Lighting control acceptance requirements. Before an occupancy permit is granted, indoor and outdoor lighting controls serving the building, area or site and installed to comply with Section 160.5(b)4D, 160.5(b)4C, 160.5(b)4E, 160.5(c)2 or 170.2(e)1Aiij shall be certified as meeting the Acceptance Requirements for Code Compliance as specified by Reference Nonresidential Appendix NA7.6 and NA7.8. A Certificate of Acceptance shall be submitted to the enforcement agency under Section 10-103(a) of Part 1 that the equipment and systems meet the acceptance requirements:

    A. Reserved;

    B. Reserved; C. Daylight responsive controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.1; D. Lighting shut-OFF controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.2; E. Demand responsive lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.3; and

    F. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and G. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4. H. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5. 2. Lighting control installation certificate requirements. To be recognized for compliance with Part 6, an Installation Certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable: A. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6, it complies with the applicable requirements of Section 110.9 and complies with Reference Nonresidential Appendix NA7.7.1.

    B. Certification that when an energy management control system is installed to function as a lighting control required by Part 6, it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 160, 170 and 180, and complies with Reference Nonresidential Appendix NA7.7.2. C. Certification that interlocked lighting systems used to serve an approved area comply with Section 170.2(e)2A and comply with Reference Nonresidential Appendix NA7.7.4. D. Certification that lighting controls installed to earn a lighting power adjustment factor (PAF) comply with Section 170.2(e)2B and comply with Reference Nonresidential Appendix NA7.7.5.

    E. Reserved.

  • § 140.3 High relevance — show source text

    A

    Above Grade Wall 140.3(a)9, 150.0(c), 160.1(b) Accent Luminaire 140.6(c)3G, 170.2(e)4 Accent, Display and Feature 140.6(b)4 Acceptance Requirements 10-103(a), 100.1(b), 110.6(a)6, 120.5(a), 120.6(a)7, 120.6(b)6, 120.6(c)8, 120.6(e)8, 120.6(f)5, 120.6(g)2, 120.6(i)4, 130.4(a), 140.9(b)3, 140.9(c)3-4, 160.3(d)1-2, 160.5(e)1 Acceptance Test Technician Certification Provider 10-103(a)4B, 10103.1(a), 10-109(i)B, 120.5(b), 130.4(c), 160.3(d)3, 160.5(e)3 Acceptance Testing 10-103(a)4, 10-103.1(a-b), 10-103.1(c)3, 10-103(e), 10-103.2(a-b), 120.5(b), 130.4(c), 141.0(b)2I, 141.0(b)2L, 160.3(d)3, 160.5(e)3, 180.2(4)B2 Actual Outdoor Lighting Power 140.7(a), 170.2(e)6 Addition Or Alteration 120.6(b)1–4, 140.9(b)1–2, 150.2(c), 180.4 Additional Credit 141.0(b)3C, 150.2(b)2, 180.2(c)2 Additional Fan Power Allowances 141.0(b)2C, Table 141.0-D Additional Multifamily Lighting Power Allowance for Specific Applications Table 170.2-S Additions 10-103(a)1C, 2A, 3D, 10-103(d)2, 10-106(a), 100.0(e)3, Table 100.0-A, Table 110.2-E, 120.0, Table 120.2-A, 120.6(c), 120.6(e), 130.0(a-b), 140.0, 140.6(a), 140.7(a), 141.0, 141.0(a), 141.1, 141.1(b–c), 150.0,150.1(a–b), 150.2, 150.2(a, c), 160.0, Table 160.3-C, 160.5(b), 170.0(a), 170.2(e)6A, 180.0, 180.1(a–b), 180.4 Adiabatic Gas Cooler 120.6(a)8, 120.6(b)5 Adjusted Indoor Lighting Power 140.6, 140.6(a)2 Adjustment Credits 180.2(b) Adjustment Factor 130.4(a, b, d), 140.6(a)2, 4, 140.6(c)3G, H, Table 140.6-A,

  • § 803.2 High relevance — show source text

    (1) Visual inspection of the equipment and installation.

    (2) Review of the certification requirements.

    (3) Functional tests of the systems and controls.

    E 803.2 Construction Documents. Details of commissioning acceptance requirements shall be incorporated into the construction documents, including information that describes the details of the functional tests to be performed. This information shall be permitted to be integrated into the specifications for testing and air balancing, energy management and control system, equipment startup procedures or commissioning. It is possible that the work will be performed by a combination of the test and balance (TAB) contractor,

    480 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    APPENDIX E

    mechanical/electrical contractor, and the energy management control system (EMCS) contractor, so applicable roles and responsibilities shall be clearly called out.

    E 803.2.1 Roles and Responsibilities. The roles and responsibilities of the persons involved in commissioning acceptance are included in Section E 803.2.1.1 through Section E 803.2.1.3.

    E 803.2.1.1 Field Technician. The field technician shall be responsible for performing and documenting the results of the acceptance procedures on the certificate of acceptance forms. The field technician shall sign the certificate of acceptance to certify that the information he provides on the certificate of acceptance is true and correct.

    E 803.2.1.2 Responsible Person. The responsible person shall be the contractor or registered design professional of record. A certificate of acceptance shall be signed by a responsible person to take responsibility for the scope of work specified by the certificate of acceptance document. The responsible person shall perform the field testing and verification work, and where this is the case, the responsible person shall complete and sign both the field technician’s signature block and the responsible person’s signature block on the certificate of acceptance form. The responsible person assumes responsibility for the acceptance testing work performed by the field technician agent or employee. E 803.2.1.3 Certificate of Acceptance. The certificate of acceptance shall be submitted to the Authority Having Jurisdiction in order to receive the final certificate of occupancy. The Authority Having Jurisdiction shall not release a final certificate of occupancy unless the submitted certificate of acceptance demonstrates that the specified systems and equipment have been shown to be performing in accordance with the applicable acceptance requirements. The Authority Having Jurisdiction has the authority to require the field technician and responsible person to demonstrate competence, to its satisfaction. Certificate of acceptance forms are located in Section E 806.0.

    E 804.0 Commissioning Tests. E 804.1 General. Functional tests shall be performed on new equipment and systems installed in either new construction or retrofit applications in accordance with this section. The appropriate certificate of acceptance form along with each specific test shall be completed and submitted to the Authority Having Jurisdiction before a final occupancy permit can be granted.

    E 804.2 Tests. Functional testing shall be performed on the devices and systems listed in this section. The functional test results are documented using the applicable certificate of acceptance forms shown in parenthesis and located in Section E 806.0. The functional tests shall be performed in accordance with Section E 805.0 using the following forms:

    (1) Minimum ventilation controls for constant and variable air volume systems (Form MECH-2A).

  • § 1.23 Medium relevance — show source text


    POUNDS
    PER CUBIC
    FOOT|MINIMUM REQUIRED EQUIVALENT
    THICKNESS FOR FIRE-RESISTANCE RATING
    OF CLAY MASONRY PROTECTION ASSEMBLY,
    _T_e (inches)|MINIMUM REQUIRED EQUIVALENT
    THICKNESS FOR FIRE-RESISTANCE RATING
    OF CLAY MASONRY PROTECTION ASSEMBLY,
    _T_e (inches)|MINIMUM REQUIRED EQUIVALENT
    THICKNESS FOR FIRE-RESISTANCE RATING
    OF CLAY MASONRY PROTECTION ASSEMBLY,
    _T_e (inches)|MINIMUM REQUIRED EQUIVALENT
    THICKNESS FOR FIRE-RESISTANCE RATING
    OF CLAY MASONRY PROTECTION ASSEMBLY,
    _T_e (inches)**| |COLUMN
    SIZE|CLAY
    MASONRY
    DENSITY,
    POUNDS
    PER CUBIC
    FOOT
    |1 hour|2 hours|3 hours|4 hours|4 hours|4 hours|1 hour|2 hours|3 hours|4 hours| |W14 × 82|120|1.23|2.42|3.41|4.29|W10 × 68|120|1.27|2.46|3.26|4.35| |W14 × 82|130|1.40|2.70|3.78|4.74|4.74|130|1.44|2.75|3.83|4.80| |W14 × 68|120|1.34|2.54|3.54|4.43|W10 × 54|120|1.40|2.61|3.62|4.51| |W14 × 68|130|1.51|2.82|3.91|4.87|4.87|130|1.58|2.89|3.98|4.95| |W14 × 53|120|1.43|2.65|3.65|4.54|W10 × 45|120|1.44|2.66|3.67|4.57| |W14 × 53|130|1.61|2.93|4.02|4.98|4.98|130|1.62|2.95|4.04|5.01| |W14 × 43|120|1.54|2.76|3.77|4.66|W10 × 33|120|1.59|2.82|3.84|4.73| |W14 × 43|130|1.72|3.04|4.13|5.09|5.09|130|1.77|3.10|4.20|5.13| |W12 × 72|120|1.32|2.52|3.51|4.40|W8 × 40|120|1.47|2.70|3.71|4.61| |W12 × 72|130|1.50|2.

  • § 160.2 Medium relevance — show source text

    E. Demand control ventilation systems required by Section 160.2(c)3 shall be tested in accordance with NA7.5.5. F. Supply fan variable flow controls shall be tested in accordance with NA7.5.6. G. Hydronic system variable flow controls shall be tested in accordance with NA7.5.7 and NA7.5.9. H. Boilers or chillers that require isolation controls as specified by Section 170.2(c)4Iii or 170.2(c)4Iiii shall be tested in accordance with NA7.5.7.

    I. Hydronic systems with supply water temperature reset controls shall be tested in accordance with NA7.5.8.

    J. Automatic demand shed controls shall be tested in accordance with NA7.5.10.

    K. Fault detection and diagnostics (FDD) for packaged direct expansion units shall be tested in accordance with NA7.5.11. L. Automatic fault detection and diagnostics (FDD) for air handling units and zone terminal units shall be tested in accordance with NA7.5.12.

    M. Distributed energy storage DX AC systems shall be tested in accordance with NA7.5.13. N. Thermal energy storage (TES) systems shall be tested in accordance with NA7.5.14. O. Supply air temperature reset controls shall be tested in accordance with NA7.5.15. P. Water-cooled chillers served by cooling towers with condenser water reset controls shall be tested in accordance with NA7.5.16.

    Q. When an energy management control system is installed, it shall functionally meet all of the applicable requirements of Part 6.

    R. Occupant sensing zone controls shall be tested in accordance with NA7.5.17. 2. Multifamily dwelling units. Before an occupancy permit is granted, the following systems and equipment serving multifamily dwelling units shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. These systems and equipment shall also comply with the applicable requirements of Section 160.3(d)3. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements: A. Multifamily building central ventilation ducts subject to Section 160.2(b)2C shall be leak tested in accordance with NA7.18.3.

    B. Multifamily building central ventilation system heat recovery or energy recovery systems in multifamily buildings with four or more habitable stories shall be tested in accordance with NA7.18.4.

    1. When certification is required by Title 24, Part 1, Section 10-103.2, the acceptance testing specified by Section 160.3(d)1 and 2 shall be performed by a Certified Mechanical Acceptance Test Technician (CMATT). If the CMATT is operating as an employee, the CMATT shall be employed by a Certified Mechanical Acceptance Test Employer. The CMATT shall disclose on the Certificate of Acceptance a valid CMATT certification identification number issued by an approved Acceptance Test Technician Certification Provider. The CMATT shall complete all Certificate of Acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.
    TABLE 160.3-A—RETURN DUCT SIZING FOR SINGLE RETURN DUCT SYSTEMS Col2 Col3
    Return duct length shall not exceed 30 feet and shall contain no more than 180 degrees of bend.
  • § 170.2 Medium relevance — show source text

    170.2(e)4B Lighting Controls 10-103.1, 110.9, 110.12(c), 110.12(e), 120.6(h)2, 6, 130.0(d), 130.0(e), 130.1, 130.2, 130.3, 130.4(a)5, 6, 130.4(b)6, 130.4(c), 140.6(a)2C, G, J, L, Table 140.6-A, 141.0(b)2I, 141.0(c)3, 150.0(k)2, 160.5(a)2, 3, 160.5(b)2, 3, 4, Table 160.5-B, 160.5(c)2, 160.5(d), 160.5(e), 170.2(e)2B, Table 170.2L, 180.2(b)4B Astronomical time-clock control Table 140.6-C, 150.0(k)3A, 160.5(a)3A, Table 170.2-M Automatic daylighting controls 110.9(b)2, 130.1(d), 130.1(f)3, 6, 140.6(a)2L, G, 160.5(b)4D, F, 170.2(e)2B, 180.3(b)4B Automatic lighting controls 140.6(a)2G, 170.2(e)2B Automatic scheduling controls 130.2(c)2, 160.5(c)2B Automatic time switch control 120.2(e)1, 120.6(b)3A, 130.1(f)5, 130.3(a)1, 130.3(a)2, 130.5(d)1, 150.0(k)3, 160.3(a)2D, 160.5(a)3A, 160.5(b)4F, 130.6(d)1 Certified Lighting Controls Acceptance Test Technician (CLCATT) 130.4(c), 160.5(e)3 Continuous dimming 140.6(a)2H, L, Table 140.6-A, 160.5(b)4D,Table 160.5-B, 170.2(e)2B, Table 170.2-L Control requirements for indoor lighting system alterations Table 141.0-F, Table 180.2-E

  • § 140.9 Medium relevance — show source text

    INDEX

    140.9(b)3, 140.9(c), 160.3(d)1, 160.3(d)2, 160.3(d)3, 160.5(e)1, 3 Compliance 10-103(a), 120.8(d), 150.1(b)3, 170.1(d) Installation 10-103(a)3, 150.1(b)3, 150.1(c)7, 150.2(b)1F Verification 10-103(a)5, 150.1(b)3 Certification 110.0(B), 110.2, 110.3(A), 110.4(a), 110.6(a), 110.8(a), 110.8(g), 110.9(c), 110,11, 120.5(b), 130.4(b), 130.4(c), 140.9(a)4, 150.0(n)3, 160.3(d)3, 160.4(c), 160.5(e) Certification Identification Number 10-103(C)3G, 120.5(B), 130.4(c), 160.3(d)3, 160.5(e) Certification Requirements 110.0(B), 110.6(a)1, 110.8(g)1 Certified 110.6(a)6, 110.8(i)1, 120.5(a) Equipment 110.4(a)1, 150.0(h), 150.0(p)1A Lighting Controls Acceptance Test Employer 130.4(c), 160.5(e) Mechanical Acceptance Test Employer 120.5(b), 160.3(d)3 Mechanical Acceptance Test Technician (CMATT) 120.5(b), 160.3(d)3 CFA and Dwelling Unit Adjustment Factors Table 150.1-C, Table 170.2-T CFM Per Square Foot 110.6(A)1, 120.1(D)3, 120.6(c)5, 140.3(a)9, 140.4(e)1, 141.0(b)2Q, 150.1(c)12A, Table 160.2-B, Table 160.2-C, 170.2(c)4N CFM Per Ton 150.0(M)13, 150.1(C)7, 150.2(B)1F, 160.3(b)5L, 170.2(c)3B, 180.2(b)2A Chalk Board 140.6(b)4 Chilled Water piping 120.3(b)2, 160.3(c)1C, 160.4(f)2B Water plant Table 120.2-A, 140.4(h)5, 140.4(j), Table 160.3-C, 170.2(c)4F Water system 120.6(h), 140.4(k)2, 140.4(m), 170.2(c)4C, I, K Water system cooling capacity Table 140.4-E, Table 170.2-E-2 Chiller 10-103(c)3B, 110.2(a), Table 120.2-A, 120.5(a)8, 16, 120.6(b)2A, Table 130.5-B, 140.

Frequently asked questions

Who must sign the Certificate of Acceptance?

The field technician who performs the acceptance testing signs the certificate; a responsible person (contractor or RDP) also reviews and signs per the Part‑1 certificate procedures.

Must a CLCATT always be used?

No — the CLCATT requirement applies when Part‑1 (Section 10‑103.1/10‑103.2) triggers certification for the acceptance testing. Acceptance testing itself is still required by Part 6; whether a CLCATT is required depends on the Part‑1 certification trigger.

What test procedures are required?

The code requires testing in accordance with the Reference Nonresidential Appendices: primarily NA7.6 for indoor/demand/daylight/demand‑response testing and NA7.8 for outdoor controls.

When is acceptance testing NOT required for an alteration?

Acceptance testing under § 160.5(e) is not required for alterations where lighting controls are added to control 20 or fewer luminaires (check alteration exceptions in the code).

What must a CLCATT put on the certificate?

The CLCATT must disclose a valid CLCATT certification identification number and complete the Certificate of Acceptance fields per the Part‑1 requirements.

More in California Energy Code

Ask about the California Energy Code

Get cited, plain-English answers on the California Energy Code for your project — any code section, any scenario.

Start Free Trial

Related in the California Energy Code