Title 24 · California Energy Code
Daylighting design, daylight-responsive controls and daylight-related PAFs
This hub explains where §130.1, §140.3 and the PAF tables (§140.6/Table 140.6‑A and §170.2/Table 170.2‑L) govern daylighting, required daylight‑responsive controls, and the documentation needed to claim daylight-related lighting power reductions.
Last reviewed: July 6, 2026
Overview
This area of the Code covers how buildings must use daylight (skylights, clerestories, sidelighting) together with automatic daylight-responsive lighting controls and how those strategies can reduce allowed lighting power through Power Adjustment Factors (PAFs). It ties mandatory control thresholds and sensor/zone rules in the lighting section to daylighting design criteria and PAFs in the lighting power sections, so daylighting both improves occupant comfort and reduces regulated lighting power when installed and documented correctly. See the daylight-control requirements in §130.1(d) for where daylight-responsive controls are required and how they must operate .
Key Code locations you’ll use for design and compliance are: the lighting controls and daylight-responsive control rules in §130.1 (daylight zones, sensor and dimming requirements) and acceptance-testing references; the daylighting design criteria in §140.3 (skylights, clerestories, slats, light shelves) that establish when a daylighting feature qualifies; and the PAF tables in §140.6/Table 140.6‑A and the multifamily Table 170.2‑L that list the available lighting-power reductions and eligibility conditions. Together these sections explain what to show on plans, required sensor behavior (e.g., >=90% reduction or OFF thresholds), and how to document/install to claim a PAF .
In this section
Code references
Grounded in the retrieved California Energy Code — click a citation to read the verbatim passage:
§ 160.5 High relevance — show source text
All daylight responsive controls shall meet the following requirements: vi. All skylit daylit zones, primary sidelit daylit zones, secondary sidelit daylit zones and the combined primary and secondary sidelit daylit zones in parking garages shall be shown on the plans; and NOTE: Parking areas on the roof of a parking structure are outdoor hardscape, not skylit daylit areas. vii. The daylight responsive controls shall provide separate control for general lighting in each type of daylit zone. The daylight responsive controls shall meet the following: a. General lighting in overlapping skylit daylit zone and sidelit daylit zone shall be controlled as part of the skylit daylit zone.
2025 CALIFORNIA ENERGY CODE 229
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
b. General lighting in overlapping primary and secondary sidelit daylit zone shall be controlled as part of the primary sidelit daylit zone. c. General lighting luminaires longer than 8 feet shall be controlled as segments of 8 feet or less according to the type of the daylit zone where the segment is primarily located; and Exception to Section 160.5(b)4Dviic: Where a luminaire contains a factory-assembled housing and light source as an integral unit in segments longer than 8 feet, the luminaire is allowed to be controlled according to the type of the daylit zone in which the segment is primarily located. viii. The daylight responsive controls shall meet the following: a. For spaces where the installation of multilevel lighting controls is required under Section 160.5(b)4B, allow the multilevel lighting controls to adjust the light level with continuous dimming; b. For each space, ensure the combined illuminance from the controlled lighting and daylight is not less than the illuminance from controlled lighting when no daylight is available; c. For areas other than parking garages, ensure that when the daylight illuminance is greater than 150 percent of the illuminance provided by the controlled lighting system when no daylight is available, the controlled lighting power in that daylight zone shall be reduced by a minimum of 90 percent; and d. For parking garages, ensure that when daylight illuminance levels measured at the farthest edge of the secondary sidelit zone away from the glazing or opening are greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in the combined primary and secondary sidelit daylight zones shall be reduced by 100 percent; and ix. Photosensors shall be located so that they are not readily accessible to unauthorized personnel; and x. The location where calibration adjustments are made to the daylight responsive controls shall be readily accessible to authorized personnel but may be inside a locked case or under a cover that requires a tool for access; and xi. Interaction with other lighting controls in a space where manual controls are required, the manual controls shall be capable of turning off or decreasing light levels below the light level set by the daylight responsive controls. Exception 1 to Section 160.5(b)4D: Areas under skylights where it is documented that existing adjacent structures or natural objects block direct sunlight for more than 1,500 daytime hours per year between 8 a.m. and 4
§ 130.1 High relevance — show source text
No more than 500 watts of rated lighting power shall be controlled together as a single zone; and iii. The occupant sensing controls shall be capable of automatically turning the lighting fully ON only in the separately controlled zone and shall be automatically activated from all designed paths of egress. Interior areas of parking garages are under the classification of indoor lighting and shall comply with Section 130.1(c)6E. Parking areas on the roof of a parking structure are under the classification of outdoor hardscape and shall comply with Section 130.2.
Reserved.
Hotel/motel guest rooms shall be controlled with one of the following controls such that, no longer than 20 minutes after the guest room has been vacated, lighting power is switched off: i. Captive card key controls; or ii. Occupant sensing controls; or
iii. Other automatic controls.
Exception to Section 130.1(c)8: A high-efficacy luminaire that meets the requirements in Section 150.0(k)1A and that is switched separately with the switch located within 6 feet of the entry door.
(d) Daylight responsive controls.
- Daylight responsive controls shall be installed in the following locations as applicable: A. In any enclosed space where the total installed wattage of general lighting luminaires completely or partially within skylit daylit zones is 75 watts or greater, the general lighting in the skylit daylit zones shall be controlled by daylight responsive controls. B. In any enclosed space where the total installed wattage of general lighting luminaires completely or partially within primary sidelit daylit zones is 75 watts or greater, the general lighting in the primary sidelit daylit zones shall be controlled by daylight responsive controls. C. In any enclosed space where the total wattage of general lighting luminaires in the secondary zones is 75 watts or greater, the general lighting in the secondary sidelit daylit zones shall be controlled by daylight responsive controls. General lighting in the secondary sidelit daylit zones shall be controlled independently of general lighting in the primary sidelit daylit zones.
98 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS
D. For skylights located in an atrium, the skylit daylit zone definition shall apply to the floor area directly under the atrium and the top floor area directly adjacent to the atrium. E. Parking garage areas where the total installed wattage of the general lighting in the primary and the secondary sidelit daylit zones is 60 watts or greater, the general lighting in the primary and secondary sidelit daylit zones shall be controlled by daylight responsive controls. 2. All daylight responsive controls shall meet the following requirements: A. All skylit daylit zones, primary sidelit daylit zones, secondary sidelit daylit zones, and the combined primary and secondary sidelit daylit zones in parking garages shall be shown on the plans; and Note: Parking areas on the roof of a parking structure are outdoor hardscape, not skylit daylit areas. B. The daylight responsive controls shall provide separate control for general lighting in each type of daylit zone. The daylight responsive controls shall meet the following: i. General lighting in overlapping skylit daylit zone and sidelit daylit zone shall be controlled as part of the skylit daylit zone. ii.
§ 160.5 High relevance — show source text
viii. The daylight responsive controls shall meet the following: a. For spaces where the installation of multilevel lighting controls is required under Section 160.5(b)4B, allow the multilevel lighting controls to adjust the light level with continuous dimming; b. For each space, ensure the combined illuminance from the controlled lighting and daylight is not less than the illuminance from controlled lighting when no daylight is available; c. For areas other than parking garages, ensure that when the daylight illuminance is greater than 150 percent of the illuminance provided by the controlled lighting system when no daylight is available, the controlled lighting power in that daylight zone shall be reduced by a minimum of 90 percent; and d. For parking garages, ensure that when daylight illuminance levels measured at the farthest edge of the secondary sidelit zone away from the glazing or opening are greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in the combined primary and secondary sidelit daylight zones shall be reduced by 100 percent; and ix. Photosensors shall be located so that they are not readily accessible to unauthorized personnel; and x. The location where calibration adjustments are made to the daylight responsive controls shall be readily accessible to authorized personnel but may be inside a locked case or under a cover that requires a tool for access; and xi. Interaction with other lighting controls in a space where manual controls are required, the manual controls shall be capable of turning off or decreasing light levels below the light level set by the daylight responsive controls. Exception 1 to Section 160.5(b)4D: Areas under skylights where it is documented that existing adjacent structures or natural objects block direct sunlight for more than 1,500 daytime hours per year between 8 a.m. and 4
p.m. Exception 2 to Section 160.5(b)4D: Areas adjacent to vertical glazing below an overhang, where the overhang covers the entire width of the vertical glazing, no vertical glazing is above the overhang, and the ratio of the overhang projection to the overhang rise is greater than 1.5 for south, east and west orientations or greater than 1 for north orientations.
Exception 3 to Section 160.5(b)4D: Where daylight responsive controls are not required for the primary sidelit daylit zones, and where the total wattage of general lighting luminaires in the secondary sidelit daylit zones is less than 85 watts, daylight responsive controls are not required for the secondary sidelit zone. Exception 4 to Section 160.5(b)4D: Reserved. Exception 5 to Section 160.5(b)4D: Rooms that have a total glazing area of less than 24 square feet, or parking garage areas with a combined total of less than 36 square feet of glazing or opening. Exception 6 to Section 160.5(b)4D: For parking garages, luminaires located in the daylight adaptation zone. Exception 7 to Section 160.5(b)4D: Luminaires in sidelit daylit zones in retail merchandise sales and wholesale showroom areas.
§ 130.1 High relevance — show source text
C. The daylight responsive controls shall meet the following: i. For spaces where the installation of multilevel lighting controls is required under Section 130.1(b), allow the multilevel lighting controls to adjust the light level with continuous dimming; ii. For each space, ensure the combined illuminance from the controlled lighting and daylight is not less than the illuminance from controlled lighting when no daylight is available; iii. For areas other than parking garages, ensure that, when the daylight illuminance is greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in that daylight zone shall be reduced by a minimum of 90 percent; and iv. For parking garages, ensure that when daylight illuminance levels measured at the farthest edge of the secondary sidelit zone away from the glazing or opening are greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in the combined primary and secondary sidelit daylit zones shall be reduced by 100 percent; and D. Photosensors shall be located so that they are not readily accessible to unauthorized personnel; and E. The location where calibration adjustments are made to the daylight responsive controls shall be readily accessible to authorized personnel but may be inside a locked case or under a cover which requires a tool for access; and F. The automatic daylighting control shall permit the multilevel lighting control to adjust the level of lighting.
Exception 1 to Section 130.1(d): Areas under skylights where it is documented that existing adjacent structures or natural objects block direct sunlight for more than 1,500 daytime hours per year between 8 a.m. and 4 p.m.
Exception 2 to Section 130.1(d): Areas adjacent to vertical glazing below an overhang, where the overhang covers the entire width of the vertical glazing, no vertical glazing is above the overhang, and the ratio of the overhang projection to the overhang rise is greater than 1.5 for south, east and west orientations or greater than 1 for north orientations.
Exception 3 to Section 130.1(d): Where daylight responsive controls are not required for the primary sidelit daylit zones, and where the total wattage of general lighting luminaires in the secondary sidelit daylit zones is less than 85 watts, daylight responsive controls are not required for the secondary sidelit zone.
Exception 4 to Section 130.1(d): Reserved.
Exception 5 to Section 130.1(d): Rooms that have a total glazing area of less than 24 square feet, or parking garage areas with a combined total of less than 36 square feet of glazing or opening.
Exception 6 to Section 130.1(d): For parking garages, luminaires located in the daylight adaptation zone.
Exception 7 to Section 130.1(d): Luminaires in sidelit daylit zones in retail merchandise sales and wholesale showroom areas.
(e) Demand responsive controls. See Section 110.12 for requirements for demand responsive lighting controls.
(f) Occupancy sensing controls interactions with space-conditioning systems. For space-conditioning system zones serving only spaces that are required to have occupant sensing controls as specified in Sections 130.1(c)5 and 6, and where Table 120.1-A allows the ventilation air to be reduced to zero when the space is in occupied-standby mode, the space-conditioning system shall be permitted to be controlled by occupancy sensing controls as specified in Section 120.2(e)3.
§ 170.2 High relevance — show source text
xi. To qualify for the PAF for a demand responsive control in Table 170.2-L, the general lighting wattage receiving the PAF shall not be within the scope of Section 110.12(c) and a demand responsive control shall meet all of the following requirements: a. The controlled lighting shall be capable of being automatically reduced in response to a demand response signal; and b. General lighting shall be reduced in a manner consistent with the illuminance uniformity requirements of Section 160.5(b)4B. xii. To qualify for the PAFs for clerestory fenestration, horizontal slats or light shelves in Table 170.2-L, the daylighting design shall meet the requirements in Section 170.2(b). The PAFs shall only apply to lighting in a primary or secondary sidelit daylit zone where continuous dimming daylighting controls meeting the requirements of Section 160.5(b)4D are installed.
TABLE 170.2-L—LIGHTING POWER ADJUSTMENT FACTORS (PAF) Col2 Col3 TYPE OF CONTROL TYPE OF AREA FACTOR 1. Daylight Continuous
Dimming Plus OFF ControlLuminaires in skylit daylit zone or primary sidelit daylit zone 0.10 2. Occupant Sensing Controls
in Office Spaces Larger Than
250 Square FeetIn open plan offices > 250 square feet: One sensor controlling an area that is:
No larger than 125 square feet0.30 2. Occupant Sensing Controls
in Office Spaces Larger Than
250 Square FeetIn open plan offices > 250 square feet: One sensor controlling an area that is:
From 126 to 250 square feet0.20 3. Institutional Tuning Luminaires in nondaylit areas.
Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.0.10 3. Institutional Tuning Luminaires in daylit areas.
Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.0.05 4. Demand Responsive
ControlGeneral lighting luminaires not in the scope of Section 110.12(c). Luminaires that qualify for other
PAFs in this table may also qualify for this demand responsive control PAF.0.05 5. Clerestory Fenestration Luminaires in daylit areas adjacent to the clerestory. Luminaires that qualify for daylight dimming
plus OFF control may also qualify for this PAF.0.05 6. Horizontal Slats Luminaires in daylit areas adjacent to vertical fenestration with interior or exterior horizontal slats.
Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.0.05 7. Light Shelves Luminaires in daylit areas adjacent to clerestory fenestration with interior or exterior light shelves.
This PAF may be combined with the PAF for clerestory fenestration. Luminaires that qualify for
daylight dimming plus OFF control may also qualify for this PAF.0.10 a. To qualify for any of the power adjustment factors in this table, the installation shall comply with the applicable requirements in Section 170.2(e)1Aii.
b. Only one PAF may be used for each qualifying luminaire unless combined.
c.§ 130.1 High relevance — show source text
General lighting in the secondary sidelit daylit zones shall be controlled independently of general lighting in the primary sidelit daylit zones.
98 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS
D. For skylights located in an atrium, the skylit daylit zone definition shall apply to the floor area directly under the atrium and the top floor area directly adjacent to the atrium. E. Parking garage areas where the total installed wattage of the general lighting in the primary and the secondary sidelit daylit zones is 60 watts or greater, the general lighting in the primary and secondary sidelit daylit zones shall be controlled by daylight responsive controls. 2. All daylight responsive controls shall meet the following requirements: A. All skylit daylit zones, primary sidelit daylit zones, secondary sidelit daylit zones, and the combined primary and secondary sidelit daylit zones in parking garages shall be shown on the plans; and Note: Parking areas on the roof of a parking structure are outdoor hardscape, not skylit daylit areas. B. The daylight responsive controls shall provide separate control for general lighting in each type of daylit zone. The daylight responsive controls shall meet the following: i. General lighting in overlapping skylit daylit zone and sidelit daylit zone shall be controlled as part of the skylit daylit zone. ii. General lighting in overlapping primary and secondary sidelit daylit zones shall be controlled as part of the primary sidelit daylit zone. iii. General lighting luminaires longer than 8 feet shall be controlled as segments of 8 feet or less according to the type of the daylit zone in which the segment is primarily located; and Exception to Section 130.1(d)2Biii: Where a luminaire contains a factory assembled housing and light source as an integral unit in segments longer than 8 feet, the luminaire segment is allowed to be controlled according to the type of the daylit zone in which the segment is primarily located. C. The daylight responsive controls shall meet the following: i. For spaces where the installation of multilevel lighting controls is required under Section 130.1(b), allow the multilevel lighting controls to adjust the light level with continuous dimming; ii. For each space, ensure the combined illuminance from the controlled lighting and daylight is not less than the illuminance from controlled lighting when no daylight is available; iii. For areas other than parking garages, ensure that, when the daylight illuminance is greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in that daylight zone shall be reduced by a minimum of 90 percent; and iv. For parking garages, ensure that when daylight illuminance levels measured at the farthest edge of the secondary sidelit zone away from the glazing or opening are greater than 150 percent of the illuminance provided by the controlled lighting when no daylight is available, the controlled lighting power in the combined primary and secondary sidelit daylit zones shall be reduced by 100 percent; and D. Photosensors shall be located so that they are not readily accessible to unauthorized personnel; and E. The location where calibration adjustments are made to the daylight responsive controls shall be readily accessible to authorized personnel but may be inside a locked case or under a cover which requires a tool for access; and F.
§ 130.4 High relevance — show source text
The setting of the limit is verified by the acceptance test required by Section 130.4(a)7; and iv. The construction documents specify which lighting systems shall have their maximum light output or maximum power draw set to no greater than 85 percent of full light output or full power draw. K. To qualify for the PAF for a demand responsive control in Table 140.6-A, the general lighting wattage receiving the PAF shall not be within the scope of Section 110.12(c) and a demand responsive control shall meet all of the following requirements: i. The controlled lighting shall be capable of being automatically reduced in response to a demand response signal; and ii. General lighting shall be reduced in a manner consistent with the requirements of Section 130.1(b). L. To qualify for the PAFs for clerestory fenestration, horizontal slats, or light shelves in Table 140.6-A, the daylighting design shall meet the requirements in Section 140.3(d). The PAFs shall only apply to lighting in a primary or secondary sidelit daylit zone where continuous dimming daylighting controls meeting the requirements of Section 130.1(d) are installed.
TABLE 140.6-A—LIGHTING POWER ADJUSTMENT FACTORS (PAF) Col2 Col3 TYPE OF CONTROL TYPE OF AREA FACTOR 1. Daylight continuous dimming plus
OFF controlLuminaires in skylit daylit zone or primary sidelit daylit zone or secondary sidelit daylit zone 0.10 2. Occupant sensing controls in offices
larger than 250 square feetOne sensor controlling an area that is no larger than 125 square feet 0.30 3. Occupant sensing controls in offices
larger than 250 square feetOne sensor controlling an area that is 126-250 square feet 0.20 4. Institutional tuning Luminaires in non-daylit areas:
Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.0.10 4. Institutional tuning Luminaires in daylit areas:
Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF.0.05 5. Demand responsive control General lighting luminaires not in the scope of Section 110.12(c).
If DR controls are required of Section 110.12(c), this PAF is not available for any lighting in the
project. Luminaires that qualify for other PAFs in this table may also qualify for this demand
responsive control PAF.0.05 6. Clerestory fenestration Luminaires in daylit areas adjacent to the clerestory.
Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.0.05 7. Horizontal slats Luminaires in daylit areas adjacent to vertical fenestration with interior or exterior horizontal slats.
Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.0.05 8. Light shelves Luminaires in daylit areas adjacent to clerestory fenestration with interior or exterior light
shelves. This PAF may be combined with the PAF for clerestory fenestration.
Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF.0.10 a. § 140.6 High relevance — show source text
F. Only lighting wattage directly controlled in accordance with Section 140.6(a)2 shall be used to reduce the installed watts as allowed by Section 140.6(a)2 for calculating the Adjusted Indoor Lighting Power. If only a portion of the wattage in a luminaire is controlled in accordance with Section 140.6(a)2, then only that portion of controlled wattage may be reduced in calculating adjusted indoor lighting power. G. Lighting controls used to qualify for a PAF shall be designed and installed in addition to manual, multilevel, and automatic lighting controls required in Section 130.1, and in addition to any other lighting controls required by any provision of Part 6. PAFs shall not be available for lighting controls required by Part 6. H. To qualify for the PAF for daylight continuous dimming plus OFF control, the daylight control and controlled luminaires shall comply with Section 130.1(d), 130.4(a)3 and 130.4(a)7, and the daylight control shall be continuous dimming and shall additionally turn lights completely OFF when the daylight available in the daylit zone is greater than 150 percent of the illuminance received from the general lighting system at full power. The PAF shall apply to the luminaires in the primary sidelit daylit zone, secondary sidelit daylit zone and skylit daylit zone.
130 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE
COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY
I. To qualify for the PAF for an occupant sensing control controlling the general lighting in large office areas above workstations, in accordance with Table 140.6-A, the following requirements shall be met: i. The office area shall be greater than 250 square feet; and ii. This PAF shall be available only in office areas which contain workstations; and iii. Controlled luminaires shall only be those that provide general lighting directly above the controlled area, or furniture mounted luminaires that comply with Section 140.6(a)2 and provide general lighting directly above the controlled area; and
iv. Qualifying luminaires shall be controlled by occupant sensing controls that meet all of the following requirements, as applicable: a. Infrared sensors shall be equipped by the manufacturer, of fitted in the field by the installer, with lenses or shrouds to prevent them from being triggered by movement outside of the controlled area. b. Ultrasonic sensors shall be tuned to reduce their sensitivity to prevent them from being triggered by movements outside of the controlled area.
c. All other sensors shall be installed and adjusted as necessary to prevent them from being triggered by movements outside of the controlled area.
v. Occupant sensing control zones, in offices greater than 250 square feet, shall be shown on the plans. J. To qualify for the PAF for an Institutional Tuning in Table 140.6-A, the tuned lighting system shall comply with all of the following requirements: i. The lighting controls shall limit the maximum output or maximum power draw of the controlled lighting to 85 percent or less of full light output or full power draw; and ii. The means of setting the limit is accessible only to authorized personnel; and iii. The setting of the limit is verified by the acceptance test required by Section 130.4(a)7; and iv.
§ 140.6 High relevance — show source text
I. To qualify for the PAF for an occupant sensing control controlling the general lighting in large office areas above workstations, in accordance with Table 140.6-A, the following requirements shall be met: i. The office area shall be greater than 250 square feet; and ii. This PAF shall be available only in office areas which contain workstations; and iii. Controlled luminaires shall only be those that provide general lighting directly above the controlled area, or furniture mounted luminaires that comply with Section 140.6(a)2 and provide general lighting directly above the controlled area; and
iv. Qualifying luminaires shall be controlled by occupant sensing controls that meet all of the following requirements, as applicable: a. Infrared sensors shall be equipped by the manufacturer, of fitted in the field by the installer, with lenses or shrouds to prevent them from being triggered by movement outside of the controlled area. b. Ultrasonic sensors shall be tuned to reduce their sensitivity to prevent them from being triggered by movements outside of the controlled area.
c. All other sensors shall be installed and adjusted as necessary to prevent them from being triggered by movements outside of the controlled area.
v. Occupant sensing control zones, in offices greater than 250 square feet, shall be shown on the plans. J. To qualify for the PAF for an Institutional Tuning in Table 140.6-A, the tuned lighting system shall comply with all of the following requirements: i. The lighting controls shall limit the maximum output or maximum power draw of the controlled lighting to 85 percent or less of full light output or full power draw; and ii. The means of setting the limit is accessible only to authorized personnel; and iii. The setting of the limit is verified by the acceptance test required by Section 130.4(a)7; and iv. The construction documents specify which lighting systems shall have their maximum light output or maximum power draw set to no greater than 85 percent of full light output or full power draw. K. To qualify for the PAF for a demand responsive control in Table 140.6-A, the general lighting wattage receiving the PAF shall not be within the scope of Section 110.12(c) and a demand responsive control shall meet all of the following requirements: i. The controlled lighting shall be capable of being automatically reduced in response to a demand response signal; and ii. General lighting shall be reduced in a manner consistent with the requirements of Section 130.1(b). L. To qualify for the PAFs for clerestory fenestration, horizontal slats, or light shelves in Table 140.6-A, the daylighting design shall meet the requirements in Section 140.3(d). The PAFs shall only apply to lighting in a primary or secondary sidelit daylit zone where continuous dimming daylighting controls meeting the requirements of Section 130.1(d) are installed.
TABLE 140.6-A—LIGHTING POWER ADJUSTMENT FACTORS (PAF) Col2 Col3 TYPE OF CONTROL TYPE OF AREA FACTOR 1. Daylight continuous dimming plus
OFF controlLuminaires in skylit daylit zone or primary sidelit daylit zone or secondary sidelit daylit zone 0.10 2. Occupant sensing controls in offices
larger than 250 square feetOne sensor controlling an area that is no larger than 125 square feet 0.30 3. § 130.1 High relevance — show source text
- All skylit daylit zones and primary sidelit daylit zones shall be shown on building plans.
- General lighting in daylit zones shall be controlled in accordance with Section 130.1(d).
- The total skylight area is at least 3 percent of the total floor area in the space within a horizontal distance of 0.7 times the average ceiling height from the edge of rough opening of skylights; or the product of the total skylight area and the average skylight visible transmittance is no less than 1.5 percent of the total floor area in the space within a horizontal distance of 0.7 times the average ceiling height from the edge of rough opening of skylights.
112 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE
COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY
- All skylights shall have a glazing material or diffuser that has a measured haze value greater than 90 percent, tested according to ASTM D1003 (notwithstanding its scope) or other test method approved by the Commission.
- Skylights for conditioned and unconditioned spaces shall have an area-weighted average visible transmittance (VT) no less than the applicable value required by Section 140.3(a)6D.
Exception 1 to Section 140.3(c): Auditoriums, churches, movie theaters, museums and refrigerated warehouses.
Exception 2 to Section 140.3(c): In buildings with unfinished interiors, future enclosed spaces for which there are plans to have: A. A floor area of less than or equal to 5,000 square feet, or B. Ceiling heights of less than or equal to 15 feet.
This exception shall not be used for S-1 or S-2 (storage), or for F-1 or F-2 (factory) occupancies.
Exception 3 to Section 140.3(c): Enclosed spaces having a designed general lighting system with a lighting power density less than 0.5 watts per square foot.
Exception 4 to Section 140.3(c): Enclosed spaces where it is documented that permanent architectural features of the building, existing structures or natural objects block direct beam sunlight on at least half of the roof over the enclosed space for more than 1500 daytime hours per year between 8 a.m. and 4 p.m.
(d) Daylighting Design Power Adjustment Factors (PAFs). To qualify for a Power Adjustment Factor (PAF) as specified in Section 140.6(a)2L, daylighting devices shall meet the following requirements:
- Clerestory fenestration. To qualify for a PAF, clerestory fenestration shall meet the following requirements: A. Shall be installed on east-, west-, or south-facing facades. B. Shall have a head height that is at least 10 feet above the finished floor. C. Shall have a glazing height that is greater than or equal to 10 percent of the head height. D. If operable shading is installed on the clerestory fenestration, then the clerestory fenestration shading shall be controlled separately from shading serving other vertical fenestration.
- **Interior and exterior horizontal slats.
§ 140.6 High relevance — show source text
It can be a line voltage switch or a low voltage switch selecting between two relays. It cannot be overridden or changed in any manner that would permit both loads to operate simultaneously. 2. Reduction of wattage through controls. In calculating adjusted indoor lighting power, the installed watts of a luminaire providing general lighting in an area listed in Table 140.6-A may be reduced by the product of (i) the number of watts controlled as described in Table 140.6-A, times (ii) the applicable power adjustment factor (PAF), if all of the following conditions are met: A. An installation certificate is submitted in accordance with Section 130.4(b), and B. Luminaires and controls meet the applicable requirements of Section 110.9, and Sections 130.0 through 130.5; and C. The controlled lighting is permanently installed general lighting systems and the controls are permanently installed nonresidential-rated lighting controls. When used for determining PAFs for general lighting in offices, furniture mounted luminaires that comply with all of the following conditions shall qualify as permanently installed general lighting systems: i. The furniture mounted luminaires shall be permanently installed no later than the time of building permit inspection; and ii. The furniture mounted luminaires shall be permanently hardwired; and iii. The furniture mounted lighting system shall be designed to provide indirect general lighting; and iv. Before multiplying the installed watts of the furniture mounted luminaire by the applicable PAF, 0.2 watts per square foot of the area illuminated by the furniture mounted luminaires shall be subtracted from installed watts of the furniture mounted luminaires; and
v. The lighting control for the furniture mounted luminaire complies with all other applicable requirements in Section 140.6(a)2.
D. At least 50 percent of the light output of the controlled luminaire is within the applicable area listed in Table 140.6-A. Luminaires on lighting tracks shall be within the applicable area in order to qualify for a PAF. E. Only one PAF from Table 140.6-A may be used for each qualifying luminaire. PAFs shall not be added together unless allowed in Table 140.6-A.
F. Only lighting wattage directly controlled in accordance with Section 140.6(a)2 shall be used to reduce the installed watts as allowed by Section 140.6(a)2 for calculating the Adjusted Indoor Lighting Power. If only a portion of the wattage in a luminaire is controlled in accordance with Section 140.6(a)2, then only that portion of controlled wattage may be reduced in calculating adjusted indoor lighting power. G. Lighting controls used to qualify for a PAF shall be designed and installed in addition to manual, multilevel, and automatic lighting controls required in Section 130.1, and in addition to any other lighting controls required by any provision of Part 6. PAFs shall not be available for lighting controls required by Part 6. H. To qualify for the PAF for daylight continuous dimming plus OFF control, the daylight control and controlled luminaires shall comply with Section 130.1(d), 130.4(a)3 and 130.4(a)7, and the daylight control shall be continuous dimming and shall additionally turn lights completely OFF when the daylight available in the daylit zone is greater than 150 percent of the illuminance received from the general lighting system at full power. The PAF shall apply to the luminaires in the primary sidelit daylit zone, secondary sidelit daylit zone and skylit daylit zone.
130 2025 CALIFORNIA ENERGY CODE
Frequently asked questions
When are daylight-responsive controls required?
Daylight-responsive controls are required where general lighting wattage in skylit, primary sidelit, or secondary sidelit daylit zones reaches the threshold (typically 75 W for skylit/primary/secondary daylit zones; parking garage sidelit zones use 60 W), and those daylit zones must be shown on the plans; the specific thresholds and zone rules are in §130.1(d) .
What PAFs are available for daylighting and how do you qualify?
PAFs (percent reductions of installed watts) are listed in Table 140.6‑A (and Table 170.2‑L for multifamily). A common PAF for continuous daylight dimming plus OFF control reduces qualifying luminaires by 0.10 (10%) when controls meet §130.1(d) and the installation and documentation requirements in §140.6(a) (including acceptance testing and installation certificates) are satisfied; additional PAFs exist for clerestories, slats, light shelves, occupant sensing, institutional tuning and demand response with specific eligibility rules in the tables and §140.6(a) .
More in California Energy Code
- Compliance paths, energy budgets, performance modeling and forms/software requirements
- Controls, commissioning, demand-response, sensors, and field verification/diagnostic testing
- Domestic hot water systems, efficiency, controls and installation requirements
- Electrical infrastructure, EV charging readiness, load management and demand controls
- Envelope construction, insulation, fenestration and thermal performance
- HVAC systems, ventilation rates, ducting, controls and testing
- Interior and exterior lighting power, controls and daylighting requirements
- Mandatory measures, appliance efficiency and certification requirements
- Photovoltaic requirements, BESS (battery energy storage) sizing and SARA procedures
- Reference appendices, test procedures, product certification and labeling requirements
- Scope, applicability, definitions and administrative requirements
Ask about the California Energy Code
Get cited, plain-English answers on the California Energy Code for your project — any code section, any scenario.
Start Free Trial