Title 24 · California Energy Code
Outdoor lighting power, hardscape allowances and outdoor controls
This hub explains how Title 24 computes allowed outdoor lighting power, how hardscape allowances and specific-application allowances work, and the required outdoor lighting controls and exceptions.
Last reviewed: July 6, 2026
Overview
This area of the California Energy Code (Title 24, Part 6) sets how much outdoor lighting power is allowed on a site, how hardscape (parking, sidewalks, plazas, canopies, etc.) is accounted for, and what automatic controls are required to limit hours and levels of illumination. The primary prescriptive rules live in §140.7 (Prescriptive Requirements for Outdoor Lighting) and the mandatory control and equipment provisions are in §130.2 (Outdoor Lighting Controls and Equipment) and related Sections in Chapter 1 and Chapter 16 of Part 6.
Allowed outdoor lighting power is computed as the sum of a general hardscape lighting allowance plus any additional allowances for specific applications (per §140.7(d)), using area-wattage and initial-wattage allowances keyed to Lighting Zone (see Table 140.7-A / 140.7‑B and the hardscape definitions). The Code defines the illuminated hardscape area (a square about each pole equal to 10× the mounting height) and limits trading of allowances (general hardscape allowance can be traded to some specific applications, but many trades are restricted).
Controls are essential: scheduling/astronomical timers, photocells for signs, and motion-sensing/dimming requirements for many hardscape luminaires (including requirements for dim levels, timeouts and maximum load per sensor), plus special controls and exceptions for signs, façades and some safety lighting. See §130.2 for outdoor control requirements and the motion-sensor/dimming requirements referenced throughout the outdoor lighting sections.
In this section
Code references
Grounded in the retrieved California Energy Code — click a citation to read the verbatim passage:
§ 140.7. High relevance — show source text
138 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE
COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY
- Outdoor lighting systems for qualified historic buildings, as defined in the California Historic Building Code (Title 24, Part 8), if they consist solely of historic lighting components or replicas of historic lighting components. If lighting systems for qualified historic buildings contain some historic lighting components or replicas of historic components, combined with other lighting components, only those historic or historic replica components are exempt. All other outdoor lighting systems for qualified historic buildings shall comply with Section 140.7.
(b) Outdoor lighting power trade-offs. Outdoor lighting power trade-offs shall be determined as follows:
- Allowed lighting power determined according to Section 140.7(d)1 for general hardscape lighting allowance may be traded to specific applications in Section 140.7(d)2, provided the hardscape area from which the lighting power is traded continues to be illuminated in accordance with Section 140.7(d)1A.
- Allowed lighting power determined according to Section 140.7(d)2 for additional lighting power allowances for specific applications shall not be traded between specific applications, or to hardscape lighting in Section 140.7(d)1.
- Trading of lighting power allowances between outdoor and indoor areas shall not be permitted.
(c) Calculation of actual lighting power. The wattage of outdoor luminaires shall be determined in accordance with Section 130.0(c).
(d) Calculation of allowed lighting power. The allowed lighting power shall be the combined total of the sum of the general hardscape lighting allowance determined in accordance with Section 140.7(d)1, and the sum of the additional lighting power allowance for specific applications determined in accordance with Section 140.7(d)2.
- General hardscape lighting allowance. Determine the general hardscape lighting power allowances as follows: A. The general hardscape area of a site shall include parking lot(s), roadway(s), driveway(s), sidewalk(s), walkway(s), bikeway(s), plaza(s), bridge(s), tunnel(s), and other improved area(s) that are illuminated. In plan view of the site, determine the illuminated hardscape area, which is defined as any hardscape area that is within a square pattern around each luminaire or pole that is ten times the luminaire mounting height with the luminaire in the middle of the pattern, less any areas that are within a building, beyond the hardscape area, beyond property lines or obstructed by a structure. The illuminated hardscape area shall include portions of planters and landscaped areas that are within the lighting application and are less than or equal to 10 feet wide in the short dimensions and are enclosed by hardscape or other improvement on at least three sides. Multiply the illuminated hardscape area by the area wattage allowance (AWA) from Table 140.7-A for the appropriate lighting zone.
§ 140.7 High relevance — show source text
SECTION 140.7—PRESCRIPTIVE REQUIREMENTS FOR OUTDOOR LIGHTING
(a) An outdoor lighting installation complies with this section if it meets the requirements in Subsections (b) and (c), and the actual outdoor lighting power installed is no greater than the allowed outdoor lighting power calculated under Subsection (d). The allowed outdoor lighting shall be calculated according to outdoor lighting zone in Title 24, Part 1, Section 10-114.
Exceptions to Section 140.7(a): When more than 50 percent of the light from a luminaire falls within one or more of the following applications, the lighting power for that luminaire shall not be required to comply with Section 140.7:
- Temporary outdoor lighting.
- Lighting required and regulated by the Federal Aviation Administration, and the Coast Guard.
- Lighting for public streets, roadways, highways, and traffic signage lighting, including lighting for driveway entrances occurring in the public right-of-way.
- Lighting for sports and athletic fields, and children’s playgrounds.
- Lighting for industrial sites, including but not limited to, rail yards, maritime shipyards and docks, piers and marinas, chemical and petroleum processing plants, and aviation facilities.
- Lighting of public monuments.
- Lighting of signs complying with the requirements of Sections 130.3 and 140.8.
- Lighting of tunnels, bridges, stairs, wheelchair elevator lifts for American with Disabilities Act (ADA) compliance, and ramps that are other than parking garage ramps.
- Landscape lighting.
- In theme parks: outdoor lighting only for themes and special effects.
- Lighting for outdoor theatrical and other outdoor live performances, provided that these lighting systems are additions to area lighting systems and are controlled by a multiscene or theatrical cross-fade control station accessible only to authorized operators.
138 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE
COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY
- Outdoor lighting systems for qualified historic buildings, as defined in the California Historic Building Code (Title 24, Part 8), if they consist solely of historic lighting components or replicas of historic lighting components. If lighting systems for qualified historic buildings contain some historic lighting components or replicas of historic components, combined with other lighting components, only those historic or historic replica components are exempt. All other outdoor lighting systems for qualified historic buildings shall comply with Section 140.7.
(b) Outdoor lighting power trade-offs. Outdoor lighting power trade-offs shall be determined as follows:
- Allowed lighting power determined according to Section 140.7(d)1 for general hardscape lighting allowance may be traded to specific applications in Section 140.7(d)2, provided the hardscape area from which the lighting power is traded continues to be illuminated in accordance with Section 140.7(d)1A.
- Allowed lighting power determined according to Section 140.7(d)2 for additional lighting power allowances for specific applications shall not be traded between specific applications, or to hardscape lighting in Section 140.7(d)1.
- Trading of lighting power allowances between outdoor and indoor areas shall not be permitted.
(c) Calculation of actual lighting power. The wattage of outdoor luminaires shall be determined in accordance with Section 130.0(c).
(d) **Calculation of allowed lighting power.
§ 170.2 High relevance — show source text
Reserved.
Outdoor lighting. A. A multifamily or mixed occupancy outdoor lighting installation complies with this section if it meets the requirements in Subsections 170.2(e)6B and C, and the actual outdoor lighting power installed is no greater than the allowed outdoor lighting power calculated under Subsection 170.2(e)6D. The allowed outdoor lighting shall be calculated according to outdoor lighting zone in Title 24, Part 1, Section 10-114. Exceptions to Section 170.2(e)6A: When more than 50 percent of the light from a luminaire falls within one or more of the following applications, the lighting power for that luminaire shall not be required to comply with Section 170.2(e)6:
i. Temporary outdoor lighting. ii. Lighting required and regulated by the Federal Aviation Administration and the Coast Guard.
2025 CALIFORNIA ENERGY CODE 263
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES
iii. Lighting for public streets, roadways, highways and traffic signage lighting, including lighting for driveway entrances occurring in the public right-of-way owned or maintained by a local municipality or utility. iv. Lighting for sports and athletic fields, and children’s playgrounds.
v. Reserved.
vi. Lighting of public monuments. vii. Lighting of signs complying with the requirements of Sections 160.5(d) and 170.2(e)7. viii. Lighting of stairs, wheelchair elevator lifts for American with Disabilities Act (ADA) compliance, and ramps that are other than parking garage ramps. ix. Landscape lighting.
x. Reserved.
xi. Lighting for outdoor theatrical and other outdoor live performances, provided that these lighting systems are additions to area lighting systems and are controlled by a multiscene or theatrical cross-fade control station accessible only to authorized operators. xii. Outdoor lighting systems for qualified historic buildings, as defined in the California Historic Building Code (Title 24, Part 8), if they consist solely of historic lighintg components or replicas of historic lighting components. If lighting systems for qualified historic buildings contain some historic lighting components or replicas of historic components, combined with other lighting components, only those historic or historic replica components are exempt. All other outdoor lighting systems for qualified historic buildings shall comply with Section 170.2(e)6. B. Outdoor lighting power trade-offs. Outdoor lighting power trade-offs shall be determined as follows: i. Allowed lighting power determined according to Section 170.2(e)6Di for general hardscape lighting allowance may be traded to specific applications in Section 170.2(e)6Dii, provided the hardscape area from which the lighting power is traded continues to be illuminated in accordance with Section 170.2(e)6Dia. ii. Allowed lighting power determined according to Section 170.2(e)2Dii for additional lighting power allowances for specific applications shall not be traded between specific applications, or to hardscape lighting in Section 170.2(e)6Di. iii. Trading off lighting power allowances between outdoor and indoor areas shall not be permitted. C. Calculation of actual lighting power. The wattage of outdoor luminaires shall be determined in accordance with Section 160.5(b)1. D. **Calculation of allowed lighting power.
§ 203.1 High relevance — show source text
ENERGY BUDGET.
GEOTHERMAL.
LONG-TERM SYSTEM COST (LSC).
PROCESS.
RECOVERED ENERGY, ON-SITE.
SOLAR ACCESS.
SOLAR POOL HEATING SYSTEM.
SECTION A5.203—PERFORMANCE APPROACH
A5.203.1 Energy efficiency. Nonresidential, high-rise residential and hotel/motel buildings that include lighting and/or mechanical systems shall comply with Sections A5.203.1.1 and A5.203.1.2. Newly constructed buildings and additions are included in the scope of these sections. Buildings permitted without lighting or mechanical systems shall comply with Section A5.203.1.1 but are not required to comply with Section A5.203.1.2.
A5.203.1.1 Tier 1 and Tier 2 prerequisites. To comply with Tier 1, ONE of the following efficiency measures is required for all applicable components of the building project. To comply with Tier 2, TWO of the following efficiency measures are required.
A5.203.1.1.1 Outdoor lighting. Outdoor lighting requirements are described below.
A5.203.1.1.1.1 Newly installed outdoor lighting power shall be no greater than 90 percent of the Allowed Outdoor Lighting Power, and general hardscape lighting within the scope of Title 24, Part 6, Section 140.7(b)1 shall have a color temperature no higher than 3000K. The Allowed Outdoor Lighting Power calculation is specified in Title 24, Part 6, Section 140.7, Requirements for Outdoor Lighting.
Exception to Section A5.203.1.1.1.1:
- The color temperature requirement is not applicable to the applications identified in the exceptions to Section 140.7(a) of Title 24, Part 6, nor to the applications identified as “specific applications” in Section 140.7(b)2 and Table 140.7-B of Title 24, Part 6.
A5.203.1.1.1.2 Outdoor pole-mounted and arm-mounted luminaires shall be installed with tilting not greater than 10 degrees, or the outdoor luminaires shall be installed with arm-mount or tenon-mount capable of tilting less than or within 10 degrees.
Exceptions to Section A5.203.1.1.1.2:
- Lighting for building facades, public monuments, public art, statues and vertical surfaces of bridges.
- Lighting not permitted by a health or life safety statute, ordinance or regulation to be a cutoff luminaire.
- Temporary outdoor lighting.
- Lighting required and regulated by the Federal Aviation Administration or the Coast Guard.
- Lighting for public streets, roadways, highways, and traffic signage lighting, including lighting for driveway entrances occurring in the public right-of-way. Luminaires that illuminate the public right of way including publicly-maintained or utility-maintained sidewalks and bikeways.
- Lighting for sports and athletic fields and children’s playgrounds.
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-13
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A5 — NONRESIDENTIAL VOLUNTARY MEASURES
- Lighting for industrial sites, including but not limited to, rail yards, maritime shipyards and docks, piers and marinas, chemical and petroleum processing plants, and aviation facilities.
§ 170.2 High relevance — show source text
x. Reserved.
xi. Lighting for outdoor theatrical and other outdoor live performances, provided that these lighting systems are additions to area lighting systems and are controlled by a multiscene or theatrical cross-fade control station accessible only to authorized operators. xii. Outdoor lighting systems for qualified historic buildings, as defined in the California Historic Building Code (Title 24, Part 8), if they consist solely of historic lighintg components or replicas of historic lighting components. If lighting systems for qualified historic buildings contain some historic lighting components or replicas of historic components, combined with other lighting components, only those historic or historic replica components are exempt. All other outdoor lighting systems for qualified historic buildings shall comply with Section 170.2(e)6. B. Outdoor lighting power trade-offs. Outdoor lighting power trade-offs shall be determined as follows: i. Allowed lighting power determined according to Section 170.2(e)6Di for general hardscape lighting allowance may be traded to specific applications in Section 170.2(e)6Dii, provided the hardscape area from which the lighting power is traded continues to be illuminated in accordance with Section 170.2(e)6Dia. ii. Allowed lighting power determined according to Section 170.2(e)2Dii for additional lighting power allowances for specific applications shall not be traded between specific applications, or to hardscape lighting in Section 170.2(e)6Di. iii. Trading off lighting power allowances between outdoor and indoor areas shall not be permitted. C. Calculation of actual lighting power. The wattage of outdoor luminaires shall be determined in accordance with Section 160.5(b)1. D. Calculation of allowed lighting power. The allowed lighting power shall be the combined total of the sum of the general hardscape lighting allowance determined in accordance with Section 170.2(e)2Di, and the sum of the additional lighting power allowance for specific applications determined in accordance with Section 170.2(e)6Dii. i. General hardscape lighting allowance . Determine the general hardscape lighting power allowances as follows:
a. The general hardscape area of a site shall include parking lot(s), roadway(s), driveway(s), sidewalk(s), walkway(s), bikeway(s), plaza(s), bridge(s), tunnel(s) and other improved area(s) that are illuminated. Public roadway(s) that are illuminated by a lighting system owned or maintained by the local municipality or utility shall not be included in the area calculations. In plan view of the site, determine the illuminated hardscape area, which is defined as any hardscape area that is within a square pattern around each luminaire or pole that is ten times the luminaire mounting height with the luminaire in the middle of the pattern, less any areas that are within a building, beyond the hardscape area, beyond property lines or obstructed by a structure. The illuminated hardscape area shall include portions of planters and landscaped areas that are within the lighting application and are less than or equal to 10 feet wide in the short dimensions and are enclosed by hardscape or other improvement on at least three sides. Multiply the illuminated hardscape area by the Area Wattage Allowance (AWA) from Table 170.2-R for the appropriate lighting zone. b. Determine the Initial Wattage Allowance (IWA) for general hardscape lighting from Table 170.2-R for the appropriate lighting zone. The hardscape area shall be permitted one IWA per site.
§ 170.2 High relevance — show source text
** The allowed lighting power shall be the combined total of the sum of the general hardscape lighting allowance determined in accordance with Section 170.2(e)2Di, and the sum of the additional lighting power allowance for specific applications determined in accordance with Section 170.2(e)6Dii. i. General hardscape lighting allowance . Determine the general hardscape lighting power allowances as follows:
a. The general hardscape area of a site shall include parking lot(s), roadway(s), driveway(s), sidewalk(s), walkway(s), bikeway(s), plaza(s), bridge(s), tunnel(s) and other improved area(s) that are illuminated. Public roadway(s) that are illuminated by a lighting system owned or maintained by the local municipality or utility shall not be included in the area calculations. In plan view of the site, determine the illuminated hardscape area, which is defined as any hardscape area that is within a square pattern around each luminaire or pole that is ten times the luminaire mounting height with the luminaire in the middle of the pattern, less any areas that are within a building, beyond the hardscape area, beyond property lines or obstructed by a structure. The illuminated hardscape area shall include portions of planters and landscaped areas that are within the lighting application and are less than or equal to 10 feet wide in the short dimensions and are enclosed by hardscape or other improvement on at least three sides. Multiply the illuminated hardscape area by the Area Wattage Allowance (AWA) from Table 170.2-R for the appropriate lighting zone. b. Determine the Initial Wattage Allowance (IWA) for general hardscape lighting from Table 170.2-R for the appropriate lighting zone. The hardscape area shall be permitted one IWA per site. c. The general hardscape lighting allowance shall be the sum of the allowed watts determined from a and b above.
TABLE 170.2-R—GENERAL HARDSCAPE MULTIFAMILY LIGHTING POWER ALLOWANCE Col2 Col3 Col4 Col5 Col6 TYPE OF POWER ALLOWANCE LIGHTING ZONE
**02 **LIGHTING ZONE
**12 **LIGHTING ZONE
**22 **LIGHTING ZONE
**32 **LIGHTING ZONE
**42 **Area Wattage Allowance (AWA) No allowance1 0.026 W/ft2 0.030 W/ft2 0.038 W/ft2 0.055 W/ft2 Initial Wattage Allowance (IWA) No allowance1 300 W 350 W 400 W 450 W 1. Continuous lighting is explicitly prohibited in Lighting Zone 0. A single luminaire of 15 watts or less may be installed at an entrance to a parking area, trail head, fee payment
kiosk, outhouse or toilet facility, as required to provide safe navigation of the site infrastructure. Luminaires installed shall meet the maximum zonal lumen limits as specified
in Section 160.5(c)1.
2. Narrow band spectrum light sources with a dominant peak wavelength greater than 580 nm—as mandated by local, state or federal agencies to minimize the impact on local,
active professional astronomy or nocturnal habitat of specific local fauna—shall be allowed a 2.0 lighting power allowance multiplier.1. Continuous lighting is explicitly prohibited in Lighting Zone 0. § 209.4.4.2 High relevance — show source text
Allowed lighting power determined according to Section A6.209.4.4.2 for additional lighting power allowances for specific applications shall not be traded between specific applications or to hardscape lighting in Section A6.209.4.4.1.
Allowed lighting power determined according to Section A6.209.4.4.3 for additional lighting power allowances for local ordinance shall not be traded to specific applications in Section A6.209.4.4.2 or to hardscape areas not covered by the local ordinance.
Trading off lighting power allowances between outdoor and indoor areas shall not be permitted.
A6.209.4.2 Outdoor lighting power. An outdoor lighting installation complies with this section if the actual outdoor lighting power installed is no greater than the allowed outdoor lighting power calculated under Section A6.209.4.4 The allowed outdoor lighting shall be calculated by Lighting Zone as defined in Section 10-114 of Title 24, Part 1. Local governments may amend lighting zones in compliance with Section 10-114 of Title 24, Part 1.
A6.209.4.3 Calculation of actual lighting power. The wattage of outdoor luminaires shall be determined in accordance with Section 130(d) of Title 24, Part 6.
APPENDIX A6.1-28 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A6.1 — VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]
A6.209.4.4 Calculation of allowed lighting power. The allowed lighting power shall be the combined total of the sum of the general hardscape lighting allowance determined in accordance with Section A6.209.4.4.1, the sum of the additional lighting power allowance for specific applications determined in accordance with Section A6.209.4.4.2 and the sum of the additional lighting power allowances for local ordinance determined in accordance with Section A6.209.4.4.3.
A6.209.4.4.1 General hardscape lighting allowance. Determine the general hardscape lighting power allowances as follows:
A6.209.4.4.1.1 The general hardscape area of a site shall include parking lot(s), roadway(s), driveway(s), sidewalk(s), walkway(s), bikeway(s), plaza(s) and other improved area(s) that are illuminated. In plan view of the site, determine the illuminated hardscape area, which is defined as any hardscape area that is within a square pattern around each luminaire or pole that is ten times the luminaire mounting height with the luminaire in the middle of the pattern, less any areas that are within a building, beyond the hardscape area, beyond property lines or obstructed by a structure. The illuminated hardscape area shall include portions of planters and landscaped areas that are within the lighting application and are less than or equal to 10 feet wide in the short dimensions and are enclosed by hardscape or other improvement on at least three sides. Multiply the illuminated hardscape area by the Area Wattage Allowance (AWA) from Table A6.209.4-A for the appropriate Lighting Zone.
§ 209.2.3.1.3 High relevance — show source text
**
A6.209.2.3.1.3 Daylight area, secondary sidelit.
A6.209.2.3.1.4 Daylight area, skylit.
A6.209.2.3.2 Controls for luminaires providing general lighting that are in or are
partially in the skylit daylight area and or the primary sidelit daylight area.
A6.209.2.4 Shut-off controls.||
|
|| |A6.209.3 Outdoor lighting controls and equipment.
A6.209.3.1 Outdoor lighting.
A6.209.3.2 Luminaire cutoff requirements.
A6.209.3.3 Controls for outdoor lighting.||
|
||APPENDIX A6.1-38 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A6.1 — VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]
NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4] — continued
FEATURE OR MEASURE COMPLIANCE LEVELS Col3 Col4 NOTES FEATURE OR MEASURE Mandatory
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenVOLUNTARY
CALGreenFEATURE OR MEASURE Mandatory
CALGreenTier 1 Tier 2 Tier 2 A6.209.4 Outdoor lighting.
A6.209.4.1 Outdoor lighting power trade-offs.
A6.209.4.2 Outdoor lighting power.
A6.209.4.3 Calculation of actual lighting power.
A6.209.4.4 Calculation of allowed lighting power.
A6.209.4.4.1 General hardscape lighting allowance.
A6.209.4.4.2 Additional lighting power allowance for specific applications.
**A6.209.4.4.3 Additional lighting power allowance for local ordinance requirements.§ 22.5 High relevance — show source text
May be used for one or two frontage side(s) per site.**|WATTAGE ALLOWANCE PER UNIT LENGTH (W/linear ft). May be used for one or two frontage side(s) per site.|WATTAGE ALLOWANCE PER UNIT LENGTH (W/linear ft). May be used for one or two frontage side(s) per site.|WATTAGE ALLOWANCE PER UNIT LENGTH (W/linear ft). May be used for one or two frontage side(s) per site.| ||**Outdoor sales frontage.**Allowance for frontage immediately adjacent to the principal viewing
location(s) and unobstructed for its viewing length. A corner sales lot may include two adjacent
sides provided that a different principal viewing location exists for each side. Luminaires qualifying
for this allowance shall be located between the principal viewing location and the frontage outdoor
sales area.|No
allowance|22.5
w/linear ft|36
w/linear ft|45
w/linear ft| |WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft2). May be used for any illuminated hardscape area on the site.|WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft2). May be used for any illuminated hardscape area on the site.|WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft2). May be used for any illuminated hardscape area on the site.|WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft2). May be used for any illuminated hardscape area on the site.|WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft2). May be used for any illuminated hardscape area on the site.|WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft2). May be used for any illuminated hardscape area on the site.| ||**Hardscape ornamental lighting.**Allowance for the total site illuminated hardscape area. Lumi-
naires qualifying for this allowance shall be rated for 100 watts or less as determined in
accordance with Section 130(d) and shall be post-top luminaires, lanterns, pendant luminaires or
chandeliers.|No
allowance|0.02
w/ft2|0.04
w/ft2|0.06
w/ft2| |WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft2). Use as appropriate provided that none of the following specific applications shall be
used for the same area.|WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft2). Use as appropriate provided that none of the following specific applications shall be
used for the same area.|WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft2). Use as appropriate provided that none of the following specific applications shall be
used for the same area.|WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft2). Use as appropriate provided that none of the following specific applications shall be
used for the same area.|WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft2). Use as appropriate provided that none of the following specific applications shall be
used for the same area.|**WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft2).§ 160.5 High relevance — show source text
In parking lots and outdoor sales lots where the bottom of the luminaire is mounted 24 feet or less above the ground, the replacement luminaires shall comply with Section 160.5(c)2A and Section 160.5(c)2C; II. For parking lots and outdoor sales lots where the bottom of the luminaire is mounted greater than 24 feet above the ground and for all other lighting applications, the replacement luminaires shall comply with Section 160.5(c)2A and either comply with Section 160.5(c)2B or be controlled by lighting control systems, including motion sensors, that automatically reduce lighting power by at least 40 percent in response to the area being vacated of occupants; and Exception to Section 180.2(b)4Bvb: Alterations where fewer than five existing luminaires are replaced. c. In alterations that do not increase the connected lighting load, where 50 percent or more of the existing luminaires are replaced in general hardscape or a specific application, the replacement luminaires shall meet the requirements of Subsection b above and the requirements of Section 170.2(e)6 for general hardscape lighting or specific lighting applications containing the alterations. Exception 1 to Section 180.2(b)4Bvc: Alterations where the replacement luminaires have at least 40 percent lower power consumption compared to the original luminaires are not required to comply with the lighting power allowances of Section 170.2(e)6. Exception 2 to Section 180.2(b)4Bvc: Alterations where fewer than five existing luminaires are replaced. Exception 3 to Section 180.2(b)4Bv: Acceptance testing requirements of Section 160.5(e) are not required for alterations where controls are added to 20 or fewer luminaires.
vi. Alterations to existing internally and externally illuminated signs that increase the connected lighting load, replace and rewire more than 50 percent of the ballasts, or relocate the sign to a different location on the same site or on a different site shall meet the requirements of Section 170.2(e)7. Exception to Section 180.2(b)4Bvi: Replacement of parts of an existing sign, including replacing lamps, the sign face or ballasts, that do not require rewiring or that are done at a time other than when the sign is relocated, is not an alteration subject to the requirements of Section 180.2(b)4Bvi. vii. Alterations to existing electrical power distribution systems shall meet the applicable requirements of the following sections: a. Service electrical metering. New or replacement electrical service equipment shall meet the requirements of Section 160.6(a) applicable to the electrical power distribution system altered; and b. Separation of electrical circuits for electrical energy monitoring. For entirely new or complete replacement of electrical power distribution systems, the entire system shall meet the applicable requirements of Section 160.6(b); and c. Voltage drop. For alterations of feeders and branch circuits where the alteration includes addition, modification or replacement of both feeders and branch circuits, the altered circuits shall meet the requirements of Section 160.6(c); and Exception to Section 180.2(b)4Bviic: Voltage drop permitted by California Electrical Code Sections 647.4, 695.6 and 695.7.
d. Circuit controls for 120-volt receptacles and controlled receptacles. For entirely new or complete replacement of electrical power distribution systems, the entire system shall meet the applicable requirements of Section 160.6(d).
2025 CALIFORNIA ENERGY CODE 281
§ 160.5 High relevance — show source text
iii. Automatic scheduling controls shall allow scheduling of a minimum of two nighttime periods with independent lighting levels, and may include an override function that turns lighting ON during its scheduled dim or OFF state for no more than 2 hours when an override is initiated.
C. Motion sensing controls . i. Motion sensing controls shall be installed for outdoor luminaires providing lighting for general hardscape, parking lots, and outdoor canopies, where the bottom of the luminaire is mounted 24 feet above grade or lower. ii. Motion sensing controls shall be capable of reducing the outdoor lighting power of each controlled luminaire by 50 to 90 percent, and separately capable of turning the luminaire OFF, during unoccupied periods. iii. Motion sensing controls shall be capable of reducing the lighting to its dim or OFF state no longer than 15 minutes after the area has been vacated, and of returning the lighting to its ON state when the area becomes occupied. iv. No more than 1,500 watts of lighting power shall be controlled by a single sensor or as a single zone. Exception 1 to Section 160.5(c)2C: Luminaires with a maximum rated wattage of 40 watts each are not required to have motion sensing controls. Exception 2 to Section 160.5(c)2C: Applications listed as exceptions to Section 170.2(e)2A and luminaires providing lighting for building façade, ornamental hardscape or outdoor dining are not required to have motion sensing controls. Exception 3 to Section 160.5(c)2C: Lighting subject to a health or life safety statute, ordinance or regulation may have a minimum time-out period longer than 15 minutes or a minimum dimming level above 50 percent when necessary to comply with the applicable law.
(d) Sign lighting controls. All sign lighting shall meet the requirements below as applicable:
Indoor signs. All indoor sign lighting other than exit sign lighting shall be controlled with an automatic time-switch control or astronomical time-switch control.
Outdoor signs. Outdoor sign lighting shall meet the following requirements as applicable: A. All outdoor sign lighting shall be controlled with a photocontrol in addition to an automatic time-switch control, or an astronomical time-switch control.
Exception to Section 160.5(d)2A: Outdoor signs in tunnels, and signs in large permanently covered outdoor areas that are intended to be continuously lit, 24 hours per day and 365 days per year. B. All outdoor sign lighting that is ON both day and night shall be controlled with a dimmer that provides the ability to automatically reduce sign lighting power by a minimum of 65 percent during nighttime hours. Signs that are illuminated at night and for more than 1 hour during daylight hours shall be considered ON both day and night.
2025 CALIFORNIA ENERGY CODE 231
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
Exception to Section 160.5(d)2B: Outdoor signs in tunnels and large covered areas that are intended to be illuminated both day and night. 3. Demand responsive electronic message center (EMC) control. See Section 110.12 for requirements for demand responsive EMC controls.
§ 180.2 High relevance — show source text
Exception 4 to Section 180.2(b)4Biv: Acceptance testing requirements of Section 160.5(e) are not required for alterations where lighting controls are added to control 20 or fewer luminaires. Exception 5 to Section 180.2(b)4Biv: Any alteration limited to adding lighting controls or replacing lamps, ballasts or drivers.
280 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING MULTIFAMILY BUILDINGS
Exception 6 to Section 180.2(b)4Biv: One-for-one luminaire alteration of up to 50 luminaires either per complete floor of the building or per complete tenant space, per annum. v. Alterations to existing outdoor lighting systems in a lighting application listed in Table 170.2-R or 170.2-S shall meet the applicable requirements of Sections 160.5(b)1, 160.5(b)2, 160.5(b)3, 160.5(c)1 and 160.5(e), and: a. In alterations that increase the connected lighting load, the added or altered luminaires shall meet the applicable requirements of Section 160.5(c)2 and the requirements of Section 170.2(e)6 for general hardscape lighting or for the specific lighting applications containing the alterations; and b. In alterations that do not increase the connected lighting load, where 10 percent or more of the existing luminaires are replaced in a general hardscape or a specific lighting application, the alterations shall meet the following requirements: I. In parking lots and outdoor sales lots where the bottom of the luminaire is mounted 24 feet or less above the ground, the replacement luminaires shall comply with Section 160.5(c)2A and Section 160.5(c)2C; II. For parking lots and outdoor sales lots where the bottom of the luminaire is mounted greater than 24 feet above the ground and for all other lighting applications, the replacement luminaires shall comply with Section 160.5(c)2A and either comply with Section 160.5(c)2B or be controlled by lighting control systems, including motion sensors, that automatically reduce lighting power by at least 40 percent in response to the area being vacated of occupants; and Exception to Section 180.2(b)4Bvb: Alterations where fewer than five existing luminaires are replaced. c. In alterations that do not increase the connected lighting load, where 50 percent or more of the existing luminaires are replaced in general hardscape or a specific application, the replacement luminaires shall meet the requirements of Subsection b above and the requirements of Section 170.2(e)6 for general hardscape lighting or specific lighting applications containing the alterations. Exception 1 to Section 180.2(b)4Bvc: Alterations where the replacement luminaires have at least 40 percent lower power consumption compared to the original luminaires are not required to comply with the lighting power allowances of Section 170.2(e)6. Exception 2 to Section 180.2(b)4Bvc: Alterations where fewer than five existing luminaires are replaced. Exception 3 to Section 180.2(b)4Bv: Acceptance testing requirements of Section 160.5(e) are not required for alterations where controls are added to 20 or fewer luminaires.
vi.
Frequently asked questions
What is the "general hardscape lighting allowance" and how is it calculated?
The general hardscape allowance covers illuminated parking, roadways, sidewalks, plazas, canopies and similar improved areas; you determine the illuminated hardscape area (the 10× mounting-height square pattern around each luminaire), multiply that area by the Area Wattage Allowance (AWA) for the project's Lighting Zone, and add any permitted Initial Wattage Allowance (IWA) per site to get the general hardscape allowance under §140.7(d).
When are motion sensors or dimming controls required for outdoor luminaires?
Motion-sensing controls are required for many general hardscape applications (parking lots, outdoor canopies, sales and non-sales areas) where the bottom of the luminaire is mounted 24 feet or lower; sensors must be capable of reducing power by 50–90% (and turn luminaires off) with a timeout no longer than 15 minutes, and they must not control more than 1,500 W per sensor/zone, per the control rules in §130.2 and related subsections.
Can outdoor lighting allowances be transferred between areas or indoors?
Some trading is allowed: the general hardscape allowance may be traded to certain specific applications if the source hardscape remains illuminated per the rule, but additional allowances for specific applications generally cannot be traded among themselves or to hardscape, and trading between outdoor and indoor allowances is not permitted. See the outdoor lighting power trade-off rules in §140.7.
More in California Energy Code
- Compliance paths, energy budgets, performance modeling and forms/software requirements
- Controls, commissioning, demand-response, sensors, and field verification/diagnostic testing
- Domestic hot water systems, efficiency, controls and installation requirements
- Electrical infrastructure, EV charging readiness, load management and demand controls
- Envelope construction, insulation, fenestration and thermal performance
- HVAC systems, ventilation rates, ducting, controls and testing
- Interior and exterior lighting power, controls and daylighting requirements
- Mandatory measures, appliance efficiency and certification requirements
- Photovoltaic requirements, BESS (battery energy storage) sizing and SARA procedures
- Reference appendices, test procedures, product certification and labeling requirements
- Scope, applicability, definitions and administrative requirements