Editor's note— Ord. No. 65.155, § 3, adopted September 2, 2025, amended the Code by repealing former Ch. 300, §§ V-300-1 and V-300-2, and adding a new Ch. 300. Former Ch. 300 pertained to similar subject matter, and derived from Ord. No. 113.26, § 3, adopted December 6, 2022.

Section 1 — Adoption of the California Fire Code, 2025 Edition

Section 5809.3.4 is hereby amended to the California Fire Code, 2025 Edition, to read as follows:

5809.3.3 Site plan. For other than emergency roadside service, a site plan shall be developed for each location at which mobile gaseous hydrogen fueling occurs. The site plan shall be in sufficient detail to indicate:

  1. All buildings and structures.

  2. Lot lines and property lines.

  3. Solar photovoltaic parking lot canopies.

  4. Appurtenances on site and their use and function.

  5. All uses adjacent to the lot lines of the site.

  6. Hydrogen fueling locations.

  7. The scale of the site plan.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-1.01 - Adoption of the California Fire Code, 2025 Edition

An Ordinance of the City of Milpitas adopting the 2025 edition of the California Fire Code, regulating and governing the safeguarding of life and property from fire and explosion hazards arising from the storage, handling and use of hazardous substances, materials and devices, and from conditions hazardous to life or property in the occupancy of buildings and premises in the City of Milpitas providing for the issuance of permits and collection of fees. That a certain document, except as herein amended, one (1) copy of which is on file in the office of the City Clerk, known as the California Fire Code, including Chapter 1, Chapter 4, and Appendices B, BB, C, CC, D, H and K as published by the International Code Council, based on the International Fire Code, 2024 Edition, is hereby adopted by reference as the Fire Code for the City of Milpitas in the State of California regulating and governing the safeguarding of life and property from fire and explosion hazards arising from the storage, handling and use of hazardous substances, materials and devices, and from conditions hazardous to life or property in the occupancy of buildings and premises as herein provided; providing for the issuance of permits and collection of fees therefore; and each and all of the regulations, provisions penalties, conditions and terms of said Fire Code on file in the office of the City Clerk are hereby referred to, adopted, and made a part hereof, as if fully set out in this Ordinance, with the additions, insertions, deletions and changes, if any, prescribed in Section 2 of this Ordinance.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.01 - Amendments to the 2025 California Fire Code

Chapter 1, Scope and Administration, of the California Fire Code, 2025 Edition, is hereby adopted and amended as follows:

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.02

Section 101.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

101.1 Title. These regulations shall be known as the Fire Code of the City of Milpitas, herein referred to as 'this Code.'

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.03

Section 102.3 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

102.3 Changes in use or occupancy. No change shall be made in the use or occupancy of any structure that would place the structure in a different division of the same group or occupancy or in a different group of occupancies, unless such structure is made to comply with the requirements of this Code and the City of Milpitas Building Codes adopted under Title II of the Milpitas Municipal Code. Subject to the approval of the fire code official, the use or occupancy of an existing structure shall be allowed to be changed and the structure is allowed to be occupied for purposes in other groups without conforming to all of the requirements of this Code and the City of Milpitas Building Codes for those groups, provided the new or proposed use is less hazardous, based on life and fire risk, than the existing use.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.04

Section 102.4 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

102.4 Application of Building Code. The design and construction of new structures shall comply with the City of Milpitas Building Codes adopted under Title II of the Milpitas Municipal Code, and any alterations, additions, changes in use or changes in structures required by this Code, which are within the scope of the City of Milpitas Building Codes, shall be made in accordance therewith.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.05

Section 102.5 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

102.5 Application of Residential Code. Where structures are designed and constructed in accordance with the City of Milpitas Building Codes adopted under Title II of the Milpitas Municipal Code, the provisions of this Code shall apply as follows:

  1. Construction and design provisions: Provisions of this Code pertaining to the exterior of the structure shall apply, including, but not limited to premises identification, fire apparatus access and water supplies. Where interior or exterior systems or devise are installed, construction permits required by Section 105.7 of this Code shall also apply.

  2. Administrative, operational and maintenance provisions: All such provision of this Code shall apply.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.06

Section 103.2 of the California Fire Code, 2025 Edition, is deleted in its entirety.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.07

Section 104.10 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

104.10 Fire Investigations. The fire code official, the fire department or other responsible authority shall have the authority to investigate the cause, origin and circumstances of any fire, explosion or other hazardous condition. Information that could be related to trade secrets or processes shall not be made part of the public record except as directed by a court of law.

The fire code official and authorized members of the fire department shall have the powers of a peace officer pursuant to Penal Code Section 830.37. Other members of the fire department, as designated by the Fire Chief, may issue citations for violations of fire-related laws and ordinances pursuant to Penal Code Section 836.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.08

Section 105.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

105.1 General. Permits shall be in accordance with Sections 105.1.1 through 105.7.26.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.09

Section 105.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

105.2 Application. Applications for a permit required by this Code shall be made to the fire code official in such form and detail as prescribed by the fire code official. Applications for permits shall be accompanied by such plans as prescribed by the fire code official. Said application shall be accompanied by a fee in the amount set by Section 106.2 of this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.10

Section 105.5 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

105.5 Required operational permits. The fire code official is authorized to issue operational permits for the operations set forth in Sections 105.5.1 through 105.5.63.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.11

Table 105.5.9 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

TABLE 105.5.9 PERMIT AMOUNTS FOR COMPRESSED GASES 1

TYPE OF GAS AMOUNT (cubic feet) 2
TYPE OF GAS × 0.0283 for m 3
Carbon dioxide used in carbon dioxide enrichment systems 875 (100lb)
Carbon dioxide used in insulated liquid carbon dioxide beverage dispensing applications 875 (100lb)
Corrosive 200
Flammable (except cryogenic and liquefied petroleum gases) 200
Highly toxic Any amount
Inert and simple asphyxiant 200
Irritant 200
Moderately toxic 20
Other health hazards 200
Oxidizing (including oxygen) 200
Pyrophoric Any amount
Radioactive Any amount
Sensitizer 200
Toxic Any Amount
Unstable (reactive) Any amount

For SI: 1 cubic foot = 0.02832 m 3 .

1 Refer to Chapters 27, 30, 32, 35, 37, 40 and 41 for additional requirements and exceptions.

2 Cubic feet measured at normal temperature and pressure.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.12

Table 105.5.11 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

TABLE 105.5.11 PERMIT AMOUNTS FOR CRYOGENIC FLUIDS

TYPE OF CRYOGENIC FLUID INSIDE BUILDING (gallons) OUTSIDE BUILDING (gallons)
Flammable More than 1 55
Inert 55 55
Oxidizing (includes oxygen) 10 50
Physical or health hazard not indicated above Any Amount Any Amount

For SI: 1 gallon = 3.785 L

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.13

Section 105.5.18, subsections (3.), (10.) and (11.) of the California Fire Code, 2025 Edition, are amended to read as follows:

  1. To store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 55 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment.

  2. To engage in the dispensing of liquid fuels into the fuel tanks of motor vehicles at commercial, industrial, governmental or manufacturing establishments in accordance with Section 5706.5.4 or to engage in on-demand mobile fueling operations in accordance with Section 5707.

  3. To utilize a site for the dispensing of liquid fuels from tank vehicle into the fuel tanks of motor vehicles, marine craft and other special equipment at commercial, industrial, governmental or manufacturing establishments in accordance with Section 5706.5.4 or to utilize a site for on-demand mobile fueling operations in accordance with Section 5707.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.14

Table 105.5.22 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

TABLE 105.5.22 PERMIT AMOUNTS FOR HAZARDOUS MATERIALS

TYPE OF MATERIAL AMOUNT
Carcinogens 10 pounds
Class II and IIIA Combustible liquids
Inside 25 gallons
Outside 55 gallons
Class IIIB Combustible Liquids 55 gallons
Corrosive materials:
Gases See Table 105.5.9
Liquids 55 gallons
Solids 500 pounds
Cryogens See Table 105.5.11
Explosive materials Any Amount
Flammable materials:
Gases See Table 105.5.9
Liquids See Section 105.5.18
Solids 10 pounds
Highly toxic materials:
Gases Any amount
Liquids Any amount
Solids Any amount
Moderately toxic gas 20 cubic feet
Organic peroxides:
Liquids: Class I—II Any Amount
Liquids: Class III 1 gallon
Liquids: Class IV 2 gallons
Liquids: Class V No Permit Required
Solids: Class I—II Any Amount
Solids: Class III 10 pounds
Solids: Class IV 20 pounds
Solids: Class V No Permit Required
Oxidizing materials:
Gases See Table 105.5.9
Liquids: Class 4 Any amount
Liquids: Class 3 1 gallon
Liquids: Class 2 10 gallons
Liquids: Class 1 55 gallons
Solids: Class 4 Any amount
Solids: Class 3 10 pounds
Solids: Class 2 100 pounds
Solids: Class 1 500 pounds
Other health hazards:
Liquids 55 gallons
Solids 500 pounds
Pyrophoric materials:
Gases Any amount
Liquids Any amount
Solids Any amount
Radioactive materials:
Gases Any amount
Liquids See Section 105.5.61
Solids See Section 105.5.61
Toxic materials:
Gases Any amount
Liquids 10 gallons
Solids 100 pounds
Unstable (reactive) materials:
Liquids
Class 4 & 3 Any Amount
Class 2 5 gallons
Class 1 10 gallons
Solids
Class 4 & 3 Any Amount
Class 2 50 pounds
Class 1 100 pounds
Water-reactive materials:
Liquids
Class 3 Any Amount
Class 2 5 gallons
Class 1 55 gallons
Solids
Class 3 Any Amount
Class 2 50 pounds
Class 1 500 pounds

For SI: 1 gallon = 3.785 L, 1 pound = 0.454kg.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.15

Section 105.5.51 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

105.5.51 Temporary membrane structures, tents and canopies. An operational permit is required to operate an air-supported temporary membrane structure or a tent having an area in excess of 200 square feet (19 m 2 ), or a canopy in excess of 400 square feet (37 m 2 ). Smaller tents or canopies set side by side are considered as one, unless separated from each other by 10 feet on all sides.

Exceptions:

  1. Tents used exclusively for recreational camping purposes.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.16

Section 105.5.60 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.60 B Occupancy restaurants. An operational permit is required to operate a B Occupancy restaurant.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.17

Section 105.5.61 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.61 Day care facility. An operational permit is required to operate a large family day care home facility, a Group E day care facility or a Group I-4 day care facility.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.18

Section 105.5.62 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.62 Emergency responders radio coverage system. An operational permit is required to operate an emergency responders radio coverage system in accordance with Section 510.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.19

Section 105.5.63 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.63 On-demand mobile fueling operations. An operational permit is required to conduct on-demand mobile fueling operations. An independent permit is required for the site and the vendor/mobile fuel operator.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.20

Section 105.5.64 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.64 Private School. An operational permit is required to operate a private school Occupancy Group E or a heritage school (CA Education Code Section 33195.4).

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.21

Section 105.5.65 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.65 Radioactive materials. To store or handle at any installation more than one microcurie (37,000 becquerel) of radioactive material not contained in a sealed source or more than 1 millicurie (37,000,000 becquerel) of radioactive material in a sealed source or sources, or any amount of radioactive material for which a specific license(s) from the Nuclear Regulatory Commission is required.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.22

Section 105.5.66 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.66 Water base fire protection systems. An operational permit is required to conduct inspections, testing and maintenance of a water base fire protection system in conformance with the CA Code of Regulations, Title 19, Division 1, Chapter 5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.23

Section 105.5.67 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.5.67 Woodworking. An operational permit is required to conduct woodworking operations involving mass production or involving more than one of each type of machine, or where machines are used continuously (as opposed to intermittently) or substantial products of sawdust may be a problem.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.24

Section 105.6 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

105.6 Required construction permits. The fire code official is authorized to issue construction permits for work as set forth in Sections 105.6.1 through 105.6.25.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.25

Section 105.6.4 of the California Fire Code, 2025 Edition, is amended to read as follows:

105.6.4 Cryogenic fluids. A construction permit is required for the installation of or alteration to stationary cryogenic fluid storage systems where the system capacity exceeds the amounts listed in Table 105.5.11. Maintenance performed in accordance with this Code is not considered to be an alteration and does not require a construction permit.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.26

Section 105.6.26 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

105.6.26 Other building permits. The Building Department shall transmit to the Fire Department a copy of each plan submitted for construction, alteration, or change of use or occupancy for all occupancy classifications for review and approval for conformance to the fire code of the City of Milpitas. The fee for each permit shall be as set by Section 108.2 of this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.27

Section 106.1.1 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

106.1.1 Electronic documents. The fire code official may require electronic base documents for all construction documents, operational permits, and/or modified drawings for the need of Fire Department inspections and/or operations. The fire code official shall designate the software base format for the electronic documents.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.28

Section 108.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

108.2 Schedule of permit fees. The fee for each permit shall be as set forth by resolution of the City of Milpitas City Council. The City Council may establish fees sufficient to recover its costs in administering this Code and no permit shall be issued until such fees have been paid. For work not disclosed in the fee schedule set by Council, the fire code official has the right to assess the necessary fees to recover the Fire Department's cost.

Operational Permits. All fees for annual operational fire permits under the provision of Section 105.5 of this Chapter shall be due and payable at the time of commencement of occupancy and said permit shall expire by December 31 of the same year. Fees for the renewal of such permit(s) shall be due and payable upon the expiration of the prior permit. No permit fee hereunder shall be refundable by reason of the cessation of occupancy during the permit period. Every annual permit fee that is not paid within a period of thirty (30) days from the time the same become due is hereby declared to be delinquent, and a penalty of 100% shall be added to say fee.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.29

Section 109.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

109.1 Inspection authority. The fire code official is authorized to inspect, as often as necessary, buildings and premises, including such other hazards or appliances designated by the fire code official for the purposes of ascertaining and causing to be corrected any conditions which would reasonably tend to cause fire or contribute to its spread, result in an unauthorized discharge of hazardous materials, or any violation of this Code or any other law or standard affecting fire and life safety. The fee for each inspection shall be as set forth by resolution of the City Council. The City may establish fees sufficient to recover its costs in administering this Chapter.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.30

Section 109.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

109.5 Documents. Any person or party who prevents or attempts to prevent any fire code official from examining any relevant books or records in the conduct of his or her official duties under this Code shall be in violation of this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.31

Section 109.6 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

109.6 Evidence. Any person or party who prevents or interferes with the preservation of evidence of any violation of any of the provisions of this Code or of the rules and regulations promulgated pursuant to this Code or any other Federal, State, or local law, rule, or regulation shall be in violation of this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.32

Section 109.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

109.7 Interference. Any person or party who willfully prevents, interferes with, or attempts to hinder in any way the work of the fire code official in the lawful enforcement of any provision of this Code, or fails to promptly permit entry for the purpose of inspection and examination pursuant to this Code shall be in violation of this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.33

Section 112.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

112.1 Appeals. Whenever the Fire Chief or his or her designee disapproves an application or refuses to grant a permit applied for, or when it is claimed that the provisions of this Code do not apply or that the true intent and meaning of this Code have been misconstrued or wrongly interpreted, the applicant may appeal from the decision of the Fire Chief to the City Council or designee within ten (10) calendar days from the date of the decision appealed. Appeals shall be carried out pursuant to the provisions of Section 5 Appeals to Council of Chapter 20 Standard Procedures of Title I of the Milpitas Municipal Code. An appeal shall stay all proceedings in furtherance of the act or decision appealed unless the Fire Chief or his or her designee whose act is appealed shall certify in writing that a stay would, in his or her opinion, cause peril to life or property. Said certificate shall contain a detailed statement of the facts of which said peril arises and of the reasons for said opinion. The decision of the City Council or designee shall be final.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.34

Section 112.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

112.2 Limitations on authority. An application for appeal shall be based on a claim that the intent of this Code or the rules legally adopted hereunder have been incorrectly interpreted, the provisions of this Code do not fully apply, or an equivalent method of protection or safety is proposed.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.35

Section 112.3 of the California Fire Code, 2025 Edition, is deleted in its entirety.

112.3 Qualifications. This section is deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.36

Section 113.1.1 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.1 Abatement of fire and life safety hazards by fire code official. If any person fails to comply with the orders of the fire code official, or if the fire code official is unable to locate the owner, operator, occupant or other person responsible within a reasonable time, the fire code official or any authorized representative may take such steps as are necessary to abate the hazard for the protection of the public safety. In no event is notice necessary before abatement, when the hazard is a clear and present danger to the public welfare. All costs related to such abatement shall become a lien or special assessment on the subject property.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.37

Section 113.1.2 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.2 Criminal or civil penalty for violation; payment of funds to account. Pursuant to the City's prosecutorial discretion, the City may enforce violations of the provisions of this Code in any manner authorized by this section or by any other law, including but not limited to issuance of criminal citations, referral to the District Attorney, referral to the City Attorney, referral to other appropriate agencies, administrative actions and civil actions.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.38

Section 113.1.3 hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.3 Misdemeanors - continuing violations. Any person who violates any of the provisions of this Code, any of the provisions of any written authority of the City Manager or his or her duly authorized agents and representatives or any provision of any permit issued pursuant to this Code shall be guilty of an infraction/misdemeanor. Each and every day, or any part thereof, during which any such violation is committed, continued or allowed shall be a separate offense. Penalties for violations shall be as set forth by resolution of the City Council.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.39

Section 113.1.4 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.4 Prosecution. Every violation of this Code shall be a misdemeanor; provided, however, that where the City Attorney or his or her duly authorized agents has determined that such action would be in the best interest of justice, the City Attorney may specify in the accusatory pleading, citation or amendment thereto that the violation shall be prosecuted as an infraction.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.40

Section 113.1.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.5 Penalty for infraction. Each and every violation of this Code, which is deemed an infraction, is punishable by:

(1) A fine not exceeding one hundred dollars ($100.00) for the first violation;

(2) A fine not exceeding two hundred dollars ($200.00) for the second violation of the same provision within one-year period; or,

(3) A fine not exceeding five hundred dollars ($500.00) for each additional violation, after the second, of the same provision of this Chapter within a one-year period of the first violation.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.41

Section 113.1.6 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.6 Penalty for misdemeanor. Each and every violation of this Code, which is deemed a misdemeanor, is punishable by a penalty of not more than one thousand dollars ($1,000.00) or by imprisonment in the City or County jail for a period not exceeding six (6) months, or, by both penalty and imprisonment.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.42

Section 113.1.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.7 Enforcement authority. The following designated employee positions may enforce the provisions of this Code by issuance of citations. Peace officers and persons employed in such positions are authorized to exercise the authority provided in Penal Code Section 836.5 and are authorized to issue citations for violations of this Code. The designated employee positions are: the City Manager or his or her duly authorized agents and representatives.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.43

Section 113.1.8 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

113.1.8 Civil penalties. Any person who intentionally, accidentally or negligently violates any provision of this Code, any written authority of the City Manager or his or her duly authorized agents and representatives, or any provision of any permit issued pursuant to this Code may be civilly liable to the City in the sum of not less than one hundred dollars ($100.00) but not to exceed one thousand dollars ($1,000.00) per day for each day in which such violation occurs or continues. The City may petition the municipal or superior court to impose, assess, and recover such sums. The civil penalty provided in this Section excludes inspection costs and abatement costs, is cumulative and not exclusive, and shall be in addition to all other remedies available to the City under state and federal law and local ordinances. Funds collected pursuant to this Section shall be paid to the City's Fire Prevention account, which shall be a holding account to be used solely for Fire Code enforcement, fire prevention and hazardous materials training, and for the purchase of equipment as needed for the performance of the fire code official duties.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.44

Section 202 of the California Fire Code, 2025 Edition, is amended by adding the following definitions:

CARCINOGEN is a substance that causes the development of cancerous growths in living tissue. A chemical is considered a carcinogen if:

  1. It has been evaluated by the International Agency for Research on Cancer and found to be a carcinogen or potential carcinogen,

  2. It is listed as a carcinogen or potential carcinogen in the latest edition of the Annual Report on Carcinogens published by the National Toxicology program, or

  3. It is regulated by OSHA as a carcinogen.

CORROSIVE LIQUID. Corrosive liquid is:

  1. any liquid which, when in contact with living tissue, will cause destruction or irreversible alteration of such tissue by chemical action; or

  2. any liquid having a pH of 2 or less or 12.5 or more; or

  3. any liquid classified as corrosive by the U.S. Department of Transportation; or

  4. any material exhibiting the characteristics of corrosivity in accordance with Title 22, California Code of Regulations § 66261.22.

DEVICE is an appliance or piece of equipment that plays an active part in the proper functioning of the regulated systems. Examples include, but are not limited to the following: smoke detectors, heat detectors, flame detectors, manual pull stations, horns, alarms, bells, warning lights, hydrants, risers, FDCs, standpipes, strobes, control panels, transponders, and other such equipment used to detect, transmit, initiate, annunciate, alarm, or respond according to the system design criteria.

LARGE-SCALE FIRE TESTING. Testing a representative energy storage system that induces a significant fire into the device under test and evaluates whether the fire will spread to adjacent energy storage system units, surrounding equipment, or through an adjacent fire-resistance-rated barrier.

MAXIMUM THRESHOLD QUANTITY (MAX TQ). Maximum Threshold Quantity (Max TQ) is the maximum quantity of a moderately toxic or toxic gas, which may be stored in a single vessel before a more stringent category of regulation is applied.

MINIMUM THRESHOLD QUANTITY. Minimum threshold quantity is the aggregate quantity of highly toxic, toxic or moderately toxic gas in a control area which, due to the minimum aggregate quantities, need only comply with the requirements set forth in Section 6004.1.

MODERATELY TOXIC GAS. A chemical or substance that has a median lethal concentration (LC50) in air more than 2000 parts per million but not more than 5000 parts per million by volume of gas or vapor, when administered by continuous inhalation for an hour, or less if death occurs within one hour, to albino rats weighing between 200 and 300 grams each.

OTHER HEALTH HAZARD MATERIAL is a material which is an irritant, sensitizer, or carcinogen or a material which affects target organs of the body, including but not limited to, those materials which produce liver damage, kidney damage, damage to the nervous system, act on the blood to decrease hemoglobin function, deprive the body tissue of oxygen or affect reproductive capabilities, including mutations (chromosomal damage) or teratogens (effect on fetuses).

SECONDARY CONTAINMENT. Secondary containment is that level of containment that is external to and separate from primary containment and is capable of safely and securely containing the material, without discharge, for a period of time reasonably necessary to ensure detection and remedy of the primary containment failure.

SENSITIZER is a chemical that causes a substantial proportion of exposed people or animals to develop an allergic reaction in normal tissue after repeated exposure to the chemical.

SPILL CONTROL. That level of containment that is external to and separate from the primary containment and is capable of safely and securely containing the contents of the largest container and prevents the materials from spreading to other parts of the room.

TEMPORARY shall not exceed one year.

WORKSTATION is a defined space or independent principal piece of equipment using hazardous materials with a hazard rating of 3 or 4 in accordance with NFPA 704 where a specific function, laboratory procedure or research activity occurs. Approved or listed hazardous materials storage cabinets, flammable liquid storage cabinets or gas cabinets serving a workstation are included as part of the workstation. A workstation is allowed to contain ventilation equipment, fire protection devices, electrical devices, and other processing and scientific equipment.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.45

Section 316.7 is hereby added to the California Fire Code, 2025 Edition, as follows:

316.7 Roof guardrails at interior courts. Roof openings into interior courts that are bounded on all sides by building walls shall be protected with guardrails. The top of the guardrail shall not be less than 42 inches in height above the adjacent roof surface that can be walked on. Intermediate rails shall be designed and spaced such that a 12-inch diameter sphere cannot pass through.

Exception: Where the roof opening is greater than 600 square feet in area.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.46

Section 503 of the California Fire Code, 2025 Edition is adopted and Section 503.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

503.1 Where required. Fire apparatus access roads shall be provided and maintained in accordance with Sections 503.1.1 through 503.7, Appendix D of this Code, and or as directed by the fire code official.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.47

Section 503.2.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm) or as required by Appendix D, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of 13 feet 6 inches (4115 mm).

Exception: When there are not more than two Group R, Division 3 or Group U occupancies less than 3 stories, the access road width may be modified by the fire code official.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.48

Section 503.2.4 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

503.2.4 Turning radius. The required turning radius of a fire apparatus access road shall be a minimum of 28 feet (8534.4 mm) inside, and a minimum of 48 feet 6 inches (14782.8 mm) outside.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.49

Section 503.6 the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

503.6 Security gates. The installation of security gates across a fire apparatus access road shall be approved by the fire code official. Where security gates are installed, they shall have an approved means of emergency operation. The security gates and the emergency operation shall be maintained operational at all times. Electric gate operators, where provided, shall be listed in accordance with UL 325. Gates intended for automatic operation shall be designed, constructed and installed to comply with the requirements of ASTM F2200. The minimum width for commercial applications is 20 feet (6096 mm), and 14 feet (4268 mm) for single-family dwellings.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.50

Section 503.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

503.7 Adjacent access. No source of access from lands adjoining a property to be developed shall be considered fire apparatus access roads, unless there is obtained the irrevocable and unobstructed rights and recorded as an ingress/egress access easement with the County of Santa Clara.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.51

Section 504.2 of the California Fire Code, 2025 Edition, is hereby adopted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.52

Section 504.3.1 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

504.3.1 Number of stairways. The fire code official shall determine the required number and location of stairway(s) to the roof.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.53

Section 504.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

504.5 Enclosed courts. Buildings with enclosed courts shall be provided with readily accessible access for fire department personnel to bring in a 36 feet long ground ladder into the court. The access height and width shall be large enough to accommodate the ladder and the personnel carrying the ladder.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.54

Section 504.6 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

504.6 Access Control Devices. When access control devices including bars, grates, gates, electric or magnetic locks or similar devices, which would inhibit rapid fire department emergency access to the building, are installed, such devices shall be approved by the fire code official. All access control devices shall be provided with an approved means for deactivation or unlocking by the fire department. Access control devices shall also comply with Chapter 10 Egress.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.55

Section 505.3 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

505.3 Address illumination. All required address numbers shall be provided with illumination.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.56

Section 507.5.1.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

507.5.1.1 Hydrant for automatic fire sprinkler and or standpipe systems. Buildings equipped with an automatic fire sprinkler system and or a standpipe system installed in accordance with Sections 903 and or 905 shall have a fire hydrant within 50 feet of the fire department connections.

Exception: The distance shall be permitted to exceed 50 feet (30 m) where approved by the fire code official.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.57

Section 507.5.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

507.5.7 Private hydrants. Private hydrants shall have the bottom 6 inches of the hydrant painted, with a weather resistive paint, white in color.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.58

Section 508.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

508.1 General. Where required by other sections of this Code and in all R-1 buildings with more than 200 rooms, R-2 buildings with more than 100 dwellings, and buildings classified as high-rise buildings by the California Building Code and Group I-2 occupancies having occupied floors located more than 75 feet above the lowest level of fire department vehicle access, a fire command center for fire department operations shal1 be provided and shall comply with Sections 508.1.1 through 508.1.7.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.59

Section 508.1.6 of the California Fire Code, 2025 Edition, is amended by adding the following:

  1. A locking key box, approved by the fire code official, large enough for ten (10) sets of master keys.

  2. Ten (10) sets of master keys for the building.

  3. A complete set of architectural, electrical, mechanical and plumbing plans for the building.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.60

Section 510.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

510.1 Emergency responder communications enhancement systems in new buildings. Approved radio coverage for emergency responders shall be provided within all buildings meeting any one of the following conditions:

  1. There are more than 3 stories above grade plane (as defined by the Building Code Section 202);

  2. The total building area is 30,000 square feet or more;

  3. The total basement area is 5,000 square feet or more;

  4. Where required by the fire code official and radio coverage signal strength levels are not consistent with the minimum levels set forth in Section 510.4.1

Exceptions:

  1. Where approved by the fire code official, a wired communication system in accordance with Section 907.2.12.2 shall be permitted to be installed or maintained in lieu of an approved radio coverage system.

  2. Where it is determined by the fire code official that the radio coverage system is not needed.

  3. In facilities where emergency responder radio coverage is required and such systems, components or equipment required could have a negative impact on the normal operations of that facility, the fire code official shall have the authority to accept an automatically activated emergency responder radio coverage system.

  4. Buildings and areas of buildings that have minimum radio coverage signal strength levels of the Silicon Valley Regional Interoperability Authority (SVRIA) P25 Phase 2 700 MHz Digital Trunked Radio System within the building in accordance with Section 510.4.1 without the use of an indoor radio coverage system.

The radio coverage system shall be installed and maintained in accordance with Sections 510.4 through 510.6.4 of this Code and with the applicable provisions of NFPA 1221, Standard for the Installation, Maintenance and Use of Emergency Services Communications Systems.

The coverage shall be based upon the existing coverage levels of the public safety communication systems of the jurisdiction at the exterior of the building. This section shall not require improvement of the existing public safety communication systems.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.61

Section 510.4 of the California Fire Code, 2025 Edition, is amended to read as follows:

510.4 Technical requirements. Systems, components, and equipment required to provide emergency responder radio coverage systems shall comply with the current Emergency Responders Radio Coverage Systems Standard Details and Specifications enforced by the Milpitas Fire Department.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.62

Section 510.5 of the California Fire Code, 2025 Edition, is amended to read as follows:

510.5 Installation requirements. The installation of the emergency responder radio coverage system shall be in accordance with NFPA 1221 and the current Emergency Responder Radio Coverage Systems Standard Details and Specification enforced by the Milpitas Fire Department.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.63

Section 510.5.3 first paragraph of the California Fire Code, 2025 Edition, is amended to read as follows:

510.5.3 Acceptance test procedure and system certification. Where an emergency responder radio coverage system is required, and upon completion of installation, the building owner shall have the radio system tested to verify that two-way coverage on each floor of the building is not less than 95 percent. Final system acceptance will require ERRCS power level and DAQ testing with agency FCC license holder, systems administrators, or designee. The test procedure shall be conducted in accordance with NFPA 1221 and the current Emergency Responder Radio Coverage System Standard Details and Specification enforced by the Milpitas Fire Department.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.64

Section 604.1.1 hereby added to the California Fire Code, 2025 Edition, to read as follows:

604.1.1 New elevators. All new passenger service elevators shall meet the medical service elevator requirements in the California Building Code, 2025 Edition, Chapter 30.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.65

Section 608.9 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

608.9 Refrigerant detection. Machinery rooms, cold storage rooms, and refrigerator boxes having the circuit capacity of section 608.7 shall be provided with a refrigerant detector with an audible and visible alarm. Where ammonia is used as the refrigerant, detection shall comply with IIAR 2. For refrigerants other than ammonia, refrigerant detection shall comply with Section 608.9.1.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.66

Section 901.6.3 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

901.6.3 Records. Records of all system inspections, tests, and maintenance required by the referenced standard shall be maintained on the premises for a minimum of five years and shall be electronically submitted to the fire code official by the company that performed the inspection, testing or maintenance in a manner prescribed by the fire code official.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.67

Section 903.1.2 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.1.2 Fire Walls and Fire Barriers. Fire walls and fire barriers shall not be considered to create separate buildings for the purpose of automatic fire sprinkler requirements as set forth in Chapter 9 of this Code.

Exception: Buildings separated by continuous fire wall of 4-hour fire resistive construction without openings or penetrations. Buildings required to have automatic fire sprinkler protection as set forth in Section 13113 of Health and Safety Code are prohibited from using fire walls in lieu of automatic fire sprinkler protection.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.68

Section 903.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

903.2 Where Required. Approved automatic fire sprinkler in new and existing buildings and structures shall be provided in the locations described in this Section or per the requirements set forth in Sections 903.2.1 through 903.2.20, whichever is the more restrictive:

  1. In other than residential buildings which require the installation of fire sprinkler for all new buildings according to the California Residential Code, an automatic fire sprinkler shall be provided throughout all new buildings and structures greater than 1,000 square feet of building area.

Exception: Group S-2 or U occupancies used exclusively for vehicle parking and which meet all of the following:

a. Noncombustible construction.

b. Maximum building area not to exceed 5,000 square feet. Structures with less than 10' horizontal separation are considered as one.

c. Structure is open on three (3) or more side.

d. Minimum of 10 feet separation from existing buildings unless area is separated by fire walls complying with California Building Code.

  1. An automatic fire sprinkler shall be provided throughout existing Group A, B, E, F, L, M, S and U buildings and structures, when additions are made that increase the building area to more than 3,600 square feet or that create conditions described in Sections 903.2.1 through 903.2.21.

  2. An automatic fire sprinkler shall be provided throughout existing Group R occupancies when additions are made that increase the building area to more than 3,600 square feet, or when the Building Department determines that the home needs to comply with the current CA Building Codes due to extensive remodel/renovation.

  3. Any change in the character of occupancy or in use of any building with a building area equal to or greater than 3,600 square feet which, in the opinion of the fire code official or building official, would place the building into a more hazardous division of the same occupancy group or into a different group of occupancies and constitutes a greater degree of life safety 1 or increased fire risk 2 , shall require the installation of an approved fire automatic fire sprinkler system.

  4. Life Safety - Increased occupant load, public assembly areas, public meeting areas, churches, indoor amusement attractions, buildings with complex exiting systems due to increased occupant loads, large schools/day-care facilities, large residential care facilities with non-ambulatory.

  5. Fire Risks - High-piled combustible storage, woodworking operations, hazardous operations using hazardous materials, increased fuel loads (storage of moderate to highly combustible materials), increased sources of ignition (welding, automotive repair with the use of flammable liquids and open flames).

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.69

Section 903.2.11.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.2.11.7 Chemical Fume Hood Fire Protection. NFPA 45, section 7.10.1 approved automatic fire extinguishing systems shall be provided in chemical fume hoods in the following cases:

  1. Existing hoods having interiors with a flame spread index greater than 25 in which flammable liquids are handled

  2. If a hazard assessment determines that an automatic extinguishing system is required for the chemical fume hood, then the applicable automatic fire protection system standard shall be followed.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.70

Section 903.3.1.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

903.3.1.1 NFPA 13 sprinkler systems. Where the provisions of this Code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 as amended in Chapter 80 except as provided in Section 903.3.1.1.1 and 903.3.1.1.3.

For a new building having no designated use or tenant, the minimum sprinkler design density shall be Ordinary Hazard Group 2. Where future use or tenant is determined to require a higher density, the sprinkler system shall be augmented to meet the higher density.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.71

Section 903.3.1.4 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.3.1.4 One sprinkler design. One sprinkler head design shall not be permitted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.72

Section 903.3.5.3 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.3.5.3. Riser location. The fire sprinkler system riser shall not be located within electrical rooms or storage closets and shall be provided with clear access and working clearance. The fire sprinkler system riser location shall be approved by the fire code official.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.73

Section 903.3.5.4 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.3.5.4 Number of water supplies. For buildings and or structures over 200,000 square feet, the fire code official may require more than one source of water supply.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.74

Section 903.3.5.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.3.5.5 Automatic fire sprinkler riser system. The automatic fire sprinkler riser system shall be a manifold type system and shall meet the design requirements of the NFPA 13 Standards.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.75

Section 903.3.5.6 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.3.5.6 Water supply safety margin. Hydraulic design for the automatic fire sprinkler system shall provide a minimum 10% safety margin.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.76

Section 903.3.5.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

903.3.5.7 Automatic fire sprinkler pipe velocity. The automatic fire sprinkler system shall be designed to a maximum 20 feet per second water flow.

Exception: The fire code official may grant higher water velocity for existing buildings when supported by mechanical engineering design done by a California registered engineer.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.77

Section 907.2.9.1 of the California Fire Code, 2025 Edition, is amended to delete the following:

907.2.9.1 Manual fire alarm system. Exception 3. is deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.78

Section 913.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

913.7 Fire Pump standby power. Power supply from local utility provider is not considered a reliable source of power. Standby power is required for electrical or natural gas fire pumps.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.79

Section 914.2.1 of the California Fire Code, 2025 Edition, is amended to delete the exception:

914.2.1 Automatic fire sprinkler system exception is deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.80

Section 914.3.1 of the California Fire Code, 2025 Edition, is amended to delete the exception:

914.3.1 Automatic fire sprinkler system exception is deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.81

Section 914.3.9 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

914.3.9 Anchor devices. Anchor repelling devices meeting the Fire department requirements shall be placed on the roof for Fire department use.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.82

Section 914.3.10 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

914.3.10 Helicopter pad. High-rise buildings greater than 150' in height (above the lowest level of Fire department access) may be required to provide a helicopter pad, which meets the requirements of the Fire department.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.83

Section 914.4.1 of the California Fire Code, 2025 Edition, is amended to delete the exceptions:

914.4.1 Automatic sprinkler systems exceptions 1 and 2 are deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.84

Section 914.6.1 of the California Fire Code, 2025 Edition, is amended to delete the exceptions:

914.6.1 Automatic Sprinkler Systems exceptions 1 and 2 are deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.85

Section 916.8 of the California Fire Code, 2025 Edition, is amended to read as follows:

916.8 System activation. A gas detection alarm shall be initiated where any sensor detects a concentration of gas exceeding the following thresholds:

  1. For flammable gases, a gas concentration exceeding 25 percent of the lower flammability limit (LFL).

  2. For nonflammable gases, a gas concentration exceeding one-half of the 1DLH, unless a different threshold is specified by the section of this code requiring a gas detection system.

Upon activation of a gas detection alarm, alarm signals or other required responses shall be as specified by the section of this code requiring a gas detection system. Audible and visible alarm signals associated with a gas detection alarm shall be distinct from fire alarm and carbon monoxide alarm signals.

The audible alarm signals shall be in accordance with 907.5.2.1.1 and 907.5.2.1.2. The visual alarm notification appliances shall be in accordance with 907.5.2.3.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.86

Section 1103.2 of the California Fire Code, 2025 Edition, is hereby adopted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.87

Section 1207.6.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

1207.6.1 Exhaust ventilation. Where required by Table 1207.6 or elsewhere in this code, exhaust ventilation of rooms, areas and walk-in units containing electrochemical ESS shall be provided in accordance with the California Mechanical Code, Sections 1207.6.1.1 or 1207.6.1.2, and 1207.6.1.3.

1207.6.1.1 Ventilation based on LFL. The exhaust ventilation system shall be designed to limit the maximum concentration or flammable gas to 25 percent of the lower flammable limit (LFL) of the total volume of the room, area, or walk-in unit during the worst-case event of simultaneous charging of batteries at the maximum charge rate, in accordance with nationally recognized standards.

1207.6.1.2 Ventilation based on exhaust rate. Continuous ventilation shall be provided at a rate of not less than 1 cubic foot per minute (cfm) per square foot [0.00508 m 3 /(s · m 2 )] of the floor area, but not less than 150 cfm (4 m 3 /min). The exhaust system shall be designed to provide air movement across all parts of the floor for gases having a vapor density greater than air and across all parts of the vault ceiling for gases having a vapor density less than air.

1207.6.1.3 Exhaust ventilation failure. Failure of exhaust ventilation system shall automatically disengage the charging system.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.88

Section 1207.6.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

1207.6.2 Spill control and neutralization. Where required by Table 1207.6 or elsewhere in this code, areas containing free-flowing liquid electrolyte or hazardous materials, shall be provided with spill control and neutralization in accordance with this section.

  1. 1207.6.2.1 Spill Control. Spill control shall be provided to prevent the flow of liquid electrolyte or hazardous materials to adjoining rooms or areas. The method shall be capable of containing a spill for the single largest battery or vessel.

1207.6.2.1.1 Spill control design. The spill control shall be designed and constructed in accordance with 5004.2.1.

1207.6.2.1.2 Spill control monitoring. Spill control systems shall be monitored in accordance with 5004.2.2.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.89

Section 2807.6 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

2807.6 Fire protection water supply system. An approved fire protection water supply and hydrant system suitable for the fire hazard involved shall be provided for open storage yards and processing areas. Hydrant systems shall be installed in accordance with NFPA 24 adopted by this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.90

Section 2808.11 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

2808.11 Fire protection water supply system. An approved fire protection water supply and hydrant system suitable for the fire hazard involved shall be provided for open storage yards and processing areas. Hydrant systems shall be installed in accordance with NFPA 24 adopted by this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.91

Section 3307.1.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

3307.1.2 Stairways required. Each level above the first story in new multi-story buildings that requires two (2) exit stairways shall be provided with at least two (2) usable exit stairways after the floor decking is installed. The stairways shall be continuous and discharge to grade level. Stairways serving more than two (2) floor levels shall be enclosed (with openings adequately protected) after the exterior walls/windows are in place. Exit stairs in new and in existing, occupied buildings shall be lighted and maintained clear of debris and construction materials at all times.

Exception: For new multi-story buildings, one of the required exit stairs may be obstructed on not more than two (2) contiguous floor levels for the purposes of stairway construction (i.e., installation of gypsum board, painting, flooring, etc.).

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.92

Section 3307.1.3.1 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

3307.1.3.1 Required means of egress. All new buildings under construction shall have a least one unobstructed means of egress. All means of egress shall be identified in the prefire plan per Section 3308.2.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.93

Section 3306.5 of the California Fire Code, 2025 Edition, is amended to read as follows:

3306.5 Completion before occupancy. In buildings where an automatic sprinkler system is required by this code or the California Building Code, it shall be unlawful to occupy any portion of a building or structure until the automatic sprinkler system installation has been tested and approved, except as provided in Section 105.3.4.

In new buildings of combustible construction where, automatic fire sprinkler systems are required to be installed, the system shall be placed in service as soon as possible. Immediately upon the completion of sprinkler pipe installation on each complete wood framed floor level, the piping shall be hydrostatically tested and inspected. After inspection approval from the Fire department, each floor level of sprinkler piping shall be connected to the system supply riser and placed into service with all sprinkler heads uncovered. Protective caps may be installed on the active sprinklers during the installation of drywall, texturing and painting, but shall be removed immediately after this work is completed. For system activation notification, an exterior audible waterflow alarm shall bell can be installed and connected to the sprinkler waterflow device prior to installation of the monitoring system. For the purpose of this requirement, complete wood frame means the installation of a sub-floor, roof sheeting or any other horizontal material that covers the top of the subject floor level.

For buildings equipped with fire sprinkler systems that are undergoing alterations, the sprinkler system(s) shall remain in service at all times except when system modifications are necessary. Fire sprinkler systems undergoing modifications shall be returned to service at the end of each workday unless otherwise approved by the fire department. The General contractor or his/her designee shall check the sprinkler control valve(s) at the end of each workday to confirm that the system has been restored to service.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.94

Section 4103.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

4103.1 Portable unvented heaters. Portable unvented fuel-fired heating equipment shall be prohibited in occupancies in Groups A, B, E, I, R-1, R-2, R2.1, R2.2, R-3, R3.1 and R-4 and ambulatory care facilities.

Exceptions:

  1. Portable unvented fuel-fired heaters listed in accordance with UL 647 are permitted to be used in one and two- family dwellings, where operated and maintained in accordance with the manufacturer's instructions.

  2. Portable outdoor gas-fired heating appliances in accordance with Section 605.5.2.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.95

Section 4103.1.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

4103.1.2.1.1 Prohibited locations. The storage or use of portable outdoor gas-fired heating appliances is prohibited in any of the following locations:

  1. Inside of any occupancy where connected to the fuel gas container.

  2. Inside of tents, canopies and membrane structures.

  3. On exterior balconies, and rooftops.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.96

Section 5001.2.2.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

5001.2.2.2 Health hazards. The material categories listed in this section are classified as health hazards. A material with a primary classification as a health hazard can also pose a physical hazard.

  1. Highly toxic and toxic materials.

  2. Corrosive materials.

  3. Moderately toxic gas.

  4. Other health hazards.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.97

Section 5001.5.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

5001.5.1 Hazardous materials management plan (HMMP). Where required by the fire code official, an application for a hazardous materials permit in accordance with Section 105.6 of this code shall include a Hazardous Materials Management Plan (HMMP).

The HMMP shall include the following:

a. Information consistent with that outlined in Sections H1, H2 and H3 of Appendix H of this code.

b. A facility site plan designating the following:

  1. Access to each storage and use area.

  2. Location of emergency equipment.

  3. Location where liaison will meet emergency responders.

  4. Facility evacuation meeting point locations.

  5. The general purpose of other areas within the building.

  6. Location of all above-ground and underground tanks and their appurtenances including, but not limited to, sumps, vaults, below-grade treatment systems and piping.

  7. The hazard classes in each area.

  8. Locations of all control areas and Group H occupancies.

  9. Emergency exits.

The HMMP shall be readily available onsite.

[For SFM] The HMMP shall comply with Health and Safety Code, Chapter 6.95, Sections 25500 through 25545, and Title 19, Division 2, Chapter 4.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.98

Section 5001.5.1.1 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5001.5.1.1 Submittal frequency. Facilities required to maintain a hazardous materials permit shall submit an updated or recertified HMMP within 12 months of the previous submittal, or within 30 days of a change, whichever occurs first.

Exceptions: The following facilities may submit an updated HMMP within 36 months of the previous submittal if no reportable changes have occurred:

  1. Cell tower sites with no hazardous materials related permits other than a permit for a battery system.

  2. Facilities with no hazardous materials related permits other than a permit for carbon dioxide used in an insulated liquid carbon dioxide beverage dispensing system.

  3. Facilities with no other hazardous materials related permits other than a permit for a fixed medical gas system.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.99

Section 5003.1.3.1 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5003.1.3.1 Highly toxic, toxic, moderately toxic gases and similarly used or handled materials. The storage, use and handling of highly toxic, toxic and moderately toxic gases in amounts exceeding Table 6004.1 shall be in accordance with this Chapter and Chapter 60. Any highly toxic, toxic or moderately toxic material that is used or handled as a gas or vapor shall be in accordance with the requirements for highly toxic, toxic or moderately toxic gases.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.100

Section 5003.1.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5003.1.5 Other health hazards. The storage, use and handling of materials classified as other health hazards in amounts exceeding 200 cubic feet for gases, 55 gallons for liquids and 500 pounds for solids shall be in accordance with Section 5003.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.101

Section 5003.1.6 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5003.1.6 Additional spill control and secondary containment requirements. In addition to the requirements set forth in Section 5004.2, an approved spill control and containment system is required for any quantity of hazardous materials that are liquids or solids at normal temperature and pressure (NTP), where a spill is determined to be a plausible event and where such an event would endanger people, property or the environment. The approved containment system may be required to include a combination of spill control and secondary containment meeting the design and construction requirements set forth in Section 5004.2.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.102

Section 5003.2.2.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

5003.2.2.1 Design and construction. Piping, tubing, valves, fittings and related components used for hazardous materials shall be in accordance with the following:

  1. Piping, tubing, valves, fittings and related components shall be designed and fabricated from materials compatible with the material to be contained and shall be of adequate strength and durability to withstand the pressure, structural and seismic stress, and exposure to which they are subject.

  2. Piping and tubing shall be identified in accordance with ASME A13.1 and Santa Clara County Fire Chiefs Marking Requirements and Guidelines for Hazardous Materials and the Hazardous Waste to indicate the material conveyed.

  3. Manual valves or automatic remotely activated fail-safe emergency shutoff valves shall be installed on supply piping and tubing, and provided with ready access at the following locations:

3.1.1.

The point of use.

3.1.2.

The tank, cylinder or bulk source.

  1. Manual emergency shutoff valves and controls for remotely activated emergency shutoff valves shall be identified and the location shall have access clearly visible and indicated by means of a sign.

  2. Backflow prevention or check valves shall be provided when the backflow of hazardous materials could create a hazardous condition or cause the unauthorized discharge of hazardous materials.

  3. Where gases or liquids having a hazard ranking of:

Health hazard Class 3 or 4

Flammability Class 4

Reactivity Class 4

in accordance with NFPA 704 are carried in pressurized piping above 15 pounds per square inch gauge (psig) (103 Kpa), an approved means of leak detection, emergency shutoff or excess flow control shall be provided. Where the piping originates from within a hazardous material storage room or area, the excess flow control shall be located within the storage room or area. Where the piping originates from a bulk source, the excess flow control shall be located as close to the bulk source as practical.

Exceptions:

1

Piping for inlet connections designed to prevent backflow.

  1. Piping for pressure relief devices.

  2. Secondary containment or equivalent protection from spills or leaks shall be provided for piping for liquid hazardous materials and for highly toxic and toxic corrosive gases above threshold quantities listed in Table 6004.1. Secondary containment includes, but is not limited to double walled piping.

Exceptions:

  1. Secondary containment is not required for toxic corrosive gases if the piping is constructed of inert materials.

  2. Piping under sub-atmospheric conditions if the piping is equipped with an alarm and fail-safe-to-close valve activated by a loss of vacuum.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.103

Section 5003.2.2.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

5003.2.2.2 Additional regulation for supply piping for health hazard materials. Supply piping and tubing for gases and liquids having a health hazard ranking of 3 or 4 in accordance with NFPA 704 shall be in accordance with ASME B31.3 and the following:

  1. Piping and tubing utilized for the transmission of highly toxic, toxic or highly volatile corrosive liquids and gases shall have welded or brazed connections throughout except for connections within an exhausted enclosure if the material is a gas, or an approved method of drainage or containment is provided for connections if the material is a liquid.

  2. Piping and tubing shall not be located within corridors, within any portion of a means of egress required to be enclosed in fire-resistance-rated construction or in concealed spaces in areas not classified as Group H Occupancies.

  3. All primary piping for highly toxic, toxic and moderately toxic gases shall pass a helium leak test of 1x10-9 cubic centimeters/second where practical, or shall pass testing in accordance with an approved, nationally recognized standard. Tests shall be conducted by a qualified "third party" not involved with the construction of the piping and control systems.

Exception: Piping and tubing within the space defined by the walls of corridors and the floor or roof above or in concealed space above other occupancies when installed in accordance with Section 415.11.7.4 of the California Building Code as required for Group H, Division 5 Occupancies.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.104

Section 5003.2.9.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

5003.2.9.1 Equipment, devices and systems requiring testing. The following equipment, systems and devices shall be tested in accordance with Sections 5003.2.9 and 5003.2.9.2.

  1. Gas detection systems, alarms and automatic emergency shutoff valves required by Section 6004.2.2.10 for highly toxic, toxic and moderately toxic gases.

  2. Limited control systems from liquid level, temperature and pressure required by Section 5003.2.7, 5003.4.8 and 5005.1.4.

  3. Emergency alarm systems and supervision required by Section 5004.9 and 5005.4.4.

  4. Monitoring and supervisory systems required by Section 5004.10 and 5005.1.6.

  5. Manually activated shutdown controls required by Section 6403.1.1.1 for compressed gas systems conveying pyrophoric gases.

  6. Leak detection sensors required by sections 5003.1.6 (MMC V-300-2.101) and 5004.2.2.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.105

Section 5003.3.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

5003.3.1 Unauthorized discharges. In the event hazardous materials are released in quantities reportable under state, federal or local regulations or when there is a release or a threatened release that presents a threat to health, property or the environment, the fire code official shall be notified immediately in an approved manner and the following procedures required in accordance with Sections 5003.3.1.1 through 5003.3.1.4.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.106

Section 5003.5.2 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5003.5.2 Ventilation ducting. Ducts for venting hazardous materials operations shall be labeled with the hazard class of the material being vented and the direction of flow.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.107

Section 5003.5.3 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5003.5.3 "H" Occupancies. In "H" occupancies, all piping and tubing may be required to be identified when there is any possibility of confusion with hazardous materials transport tubing or piping. Flow direction indicators are required.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.108

Section 5003.9.8 of the California Fire Code, 2022 Edition, is amended to read as follows:

5003.9.8 Separation of incompatible materials. Incompatible materials in storage and storage of materials that are incompatible with materials in use shall be separated. When the stored materials are in containers having a capacity of more than 5 pounds (2 kg), 0.5 gallon (2 L), or any amount of compressed gases, separation shall be accomplished by:

  1. Segregating incompatible materials in storage by a distance of not less than 20 feet (6096 mm) and in an independent containment system.

  2. Isolating incompatible materials in storage by a noncombustible partition extending not less than 18 inches (457 mm) above and to the sides of the stored material.

  3. Storing liquid and solid materials in hazardous material storage cabinets.

  4. Storing compressed gases in gas cabinets or exhausted enclosures in accordance with Sections 5003.8.5 and 5003.8.6. Materials that are incompatible shall not be stored within the same cabinet or exhausted enclosure.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.109

Section 5003.9.11 is hereby added to the California Fire Code, 2025 Edition to read as follows:

5003.9.11 Fire extinguishing systems for workstations dispensing, handling or using hazardous materials. Combustible and non-combustible workstations, which dispense, handle or use hazardous materials, shall be protected by an approved automatic fire extinguishing system in accordance with Section 2703.10.

Exception: Internal fire protection is not required for Biological Safety Cabinets that carry NSF/ANSI certification where quantities of flammable liquids in use or storage within the cabinet do not exceed 500 ml.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.110

Section 5003.9.12 hereby added to the California Fire Code, 2025 Edition, to read as follows:

5003.9.12 Immersion heaters. All electrical immersion heaters used in dip tanks, sinks, vats and similar operations shall be provided with approved over-temperature controls and low liquid level electrical disconnects. Manual reset of required protection devices shall be provided.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.111

Section 5003.10.4.3 of the California Fire Code, 2025 Edition, is amended to read as follows:

5003.10.4.3 Highly toxic, toxic and moderately toxic, gases shall be limited to a container of a maximum water capacity of 1 lb.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.112

Section 5004.2.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

5004.2.1 Spill control for hazardous material liquids. Rooms, buildings or areas used for storage of hazardous material liquids, shall be provided with spill control to prevent the flow of liquids to adjoining areas. Floors in indoor locations and similar surfaces in outdoor locations shall be constructed to contain a spill from the largest single vessel by one of the following methods:

  1. Liquid-tight sloped or recessed floors in indoor locations or similar areas in outdoor locations.

  2. Liquid-tight floors in indoor and/or outdoor locations or similar areas provided with liquid-tight raised or recessed sills or dikes.

  3. Sumps and collection systems, including containment pallets in accordance with Section 5004.2.3.

  4. Other approved engineered systems.

Except for surfacing, the floors, sills, dikes, sumps and collection systems shall be constructed of noncombustible material, and the liquid-tight seal shall be compatible with the material stored. When liquid-tight sills or dikes are provided, they are not required at perimeter openings having an open-grate trench across the opening that connects to an approved collection system.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.113

Section 5004.2.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

5004.2.2 Secondary containment for hazardous material liquids and solids. Buildings, rooms or areas used for the storage of hazardous materials liquids or solids shall be provided with secondary containment in accordance with this section.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.114

Table 5004.2.2 of the California Fire Code, 2025 Edition is hereby deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.115

Section 5004.2.2.2 is hereby amended to the California Fire Code, 2025 Edition, to read as follows:

5004.2.2.2 Incompatible materials. Incompatible materials shall be separated from each other in independent secondary containment systems.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.116

Section 5004.2.2.5 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

5004.2.2.5 Monitoring. An approved monitoring method shall be provided to detect hazardous materials in the spill control and secondary containment systems and to verify that the provisions of this Code for the storage and handling of hazardous materials are addressed. Monitoring shall be recorded at least once per week. The monitoring method is allowed to be visual inspection of the primary or secondary containment, or other approved means. Where secondary containment is subject to the instruction of water, a monitoring method for detecting water shall be provided. Where monitoring devices are provide, they shall be connected to approved visual or audible alarms.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.117

Section 5004.2.3 of the California Fire Code, 2025 Edition, is amended to read as follows:

5004.2.3 Containment pallets. Combustible containment pallets shall not be used inside buildings to comply with Section 5004.2 where the individual container capacity exceeds 55 gallons (208 L) or an aggregate capacity of multiple containers exceeds 1,000 gallons (3785 L) for liquids or where the individual container capacity exceeds 550 pounds (250 kg) or an aggregate of multiple containers exceeds 10,000 pounds (4540 kg) for solids.

Where used as an alternative to spill control and secondary containment for outdoor storage in accordance, with the exception in Section 5004.2, containment pallets shall comply with all of the following:

  1. A liquid-tight sump accessible for visual inspection shall be provided;

  2. The sump shall be designed to contain not less than 66 gallons (250L);

  3. Exposed surfaces shall be compatible with material stored;

  4. Containment pallets shall be protected to prevent collection of rainwater within the sump of the containment pallet.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.118

Section 5005.4.4 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

5005.4.4 Dispensing, use and handling. When hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704, or toxic or moderately toxic gases exceeding 405 cu. ft. and any amount of highly toxic compressed gases are transported through corridors or exit enclosures, there shall be an emergency telephone system, a local manual alarm station or an approved alarm-initiating device at not more than 150-foot (45,720 mm) intervals and at each exit and exit- access doorway throughout the transport route. The signal shall be relayed to an approved central, proprietary or remote station service or constantly attended on-site location and shall also initiate a local audible alarm.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.119

Section 5303.5.3, method 1. of the California Fire Code, 2025 Edition, is amended to read as follows:

  1. Securing containers, cylinders and tanks to a fixed object with one or more noncombustible restraints.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.120

Section 5307.3.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

5307.3.2 Gas detection system. Where ventilation is not provided in accordance with Section 5307.3.1, a gas detection system complying with Section 916 shall be provided in rooms or indoor areas and in below-grade outdoor locations with insulated carbon dioxide systems, and where the carbon dioxide tubing connects to the beverage dispensing system. Carbon dioxide sensors shall be provided within 12 inches (305 mm) of the floor in an area where the gas is expected to accumulate or other approved locations. The system shall be designed as follows:

  1. Activates an audible and visible supervisory alarm at a normally attended location upon detection of a carbon dioxide concentration of 5,000 ppm (9000 mg/m 3 ).

  2. Activates an audible and visible alarm within the room or immediate area where the system is installed upon detection of carbon dioxide concentration of 30,000 ppm (54000 mg/m 3 ).

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.121

Section 5601.1.3 of the California Fire Code 2025 Edition, is amended to read in its entirety as follows:

5601.1.3 Fireworks. The possession, manufacture, storage, sale, handling, and use of fireworks, including those fireworks classified as Safe and Sane by the California State Fire Marshal, are prohibited.

Exception: The use of fireworks for fireworks displays as allowed in Section 5608.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.122

Section 5704.2.7.5.8 of the California Fire Code, 2025 Edition, is amended to read as follows:

5704.2.7.5.8 Overfill prevention. An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent the overfill of all Class I, II and IIIA liquid storage tanks. Storage tanks in refineries, bulk plants or terminals regulated by Sections 5706.4 or 5706.7 shall have overfill protection in accordance with API 2350.

Exception: Outside aboveground tanks with a capacity of 1320 gallons (5000 L) or less need only comply with Section 5704.2.9.7.5, item 1, sub-item (1.1)

An approved means or method in accordance with Section 5704.2.9.7.5 shall be provided to prevent the overfilling of Class IIIB liquid storage tanks connected to fuel-burning equipment inside buildings.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.123

Section 5704.2.7.5.9 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5704.2.7.5.9 Automatic filling of tanks. Systems that automatically fill flammable or combustible liquid tanks shall be equipped with overfill protection, approved by the fire code official that sends an alarm signal to a constantly attended location and immediately stops the filling of the tank. The alarm signal and automatic shutoff shall be tested on an annual basis and records of such testing shall be maintained on-site for a period of five (5) years.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.124

Section 5707 of the California Fire Code, 2025 Edition, is hereby adopted and amended as follows:

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.125

Section 5707.3.3 of the California Fire Code, 2025 Edition, is amended as follows:

5707.3.3 Site plan. A site plan shall be developed for each location or area at which mobile fueling occurs. The site plan shall be in sufficient detail to indicate the following:

  1. All buildings and structures.

  2. Lot lines or property lines.

  3. Electric car chargers.

  4. Solar photovoltaic parking lot canopies.

  5. Appurtenances on-site and their use or function.

  6. All uses adjacent to the lot lines of the site.

  7. Fueling locations.

  8. Locations of all storm drain openings and adjacent waterways or wetlands.

  9. Information regarding slope, natural drainage, curbing and impounding.

  10. How a spill will be kept on the site property.

  11. Scale of the site plan.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-12.126

Section 5707.4 of the California Fire Code, 2025 Edition, is amended to read as follows:

5707.4 Mobile fueling areas. Mobile fueling shall not occur on public streets, public ways, any residential street, or inside buildings. Fueling on the roof level of parking structures or other buildings is prohibited.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.127

Sections 5707.6.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

5707.6.7 Bonding. A means for bonding the mobile fueling vehicle to the motor vehicle shall be provided. Such bonding means shall be employed during fueling operations.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.129

Chapter 60 of the California Fire Code, 2025 Edition, is amended to read as follows:

HIGHLY TOXIC, TOXIC AND MODERATELY TOXIC GASES

6001.1 Scope. The storage and use of highly toxic, toxic and moderately toxic materials shall comply with this chapter. Compressed gases shall also comply with Chapter 53.

Exceptions:

  1. Display and storage in Group M and storage in Group S occupancies complying with Section 5003.11.

  2. Conditions involving pesticides or agricultural products as follows:

2.1

Application and release of pesticide, agricultural products and materials intended for use in weed abatement, erosion control, soil amendment or similar applications when applied in accordance with the manufacturer's instruction and label directions.

2.2

Transportation of pesticides in compliance with the Federal Hazardous Materials Transportation Act and regulations thereunder.

2.3

Storage in dwellings or private garages of pesticides registered by the US Environmental Protection Agency to be utilized in and around the home, garden, pool, spa and patio.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.130

Section 6004.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.1 General. Materials stored or used as a gas whether or not the material meets the definition of a compressed gas, and meets the definition of a highly toxic, toxic and moderately toxic gas shall comply with Section 6004.

The minimum threshold quantity for highly toxic, toxic and moderately toxic gases, vapors and mists for indoor and exterior storage and use are set forth in Table 6004.1.

Table 6004.1 Minimum Threshold Quantities for Highly Toxic, Toxic and Moderately Toxic Gases

Highly Toxic 20
Toxic 405 cubic feet
Moderately Toxic 405 cubic feet

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.131

Section 6004.1.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.1.1 Special limitations for indoor storage and use by occupancy. The indoor storage and use of highly toxic, toxic and moderately toxic gases in certain occupancies shall be subject to the limitations contained in Sections 6004.1.1.1 through 6004.1.1.3.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.132

Section 6004.1.1.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.1.1.1 Group A, E, I or U occupancies. Highly toxic, toxic and moderately toxic gases shall not be stored or used within Group A, E, I or U occupancies.

Exception: Cylinders not exceeding 20 cubic feet (0.556 m 3 ) at normal temperature and pressure (NTP) are allowed within gas cabinets or fume hoods.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.133

Section 6004.1.1.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.1.1.2 Group R occupancies. Highly toxic, toxic and moderately toxic gases shall not be stored or used in Group R occupancies.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.134

Section 6004.1.1.3 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.1.1.3 Offices, retail sales and classrooms. Highly toxic, toxic and moderately toxic gases shall not be stored or used in offices, retail sales or classroom portions of Group B, F, M or S occupancies.

Exception: In classrooms of Group B occupancies, cylinders with a capacity not exceeding 20 cubic feet (0.566 m 3 ) at NTP are allowed in gas cabinets or fume hoods.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.135

Section 6004.1.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.1.2 Gas cabinets. Gas cabinets containing highly toxic, toxic and moderately toxic gases shall comply with Section 5003.8.6 and the following requirements:

  1. The average ventilation velocity at the face of gas cabinet access ports or windows shall not be less than 200 cubic feet per minute (1.02 m/s) with a minimum of 150 feet per minute (0.76 m/s) at any point of the access port or window.

  2. Gas cabinets shall be connected to an exhaust system.

  3. Gas cabinets shall not be used as the sole means of exhaust for any room or area.

  4. The maximum number of cylinders located in a single gas cabinet shall not exceed three, except that cabinets containing cylinders not exceeding 1 pound (0.454 kg) net contents are allowed to contain up to 100 cylinders.

  5. Gas cabinets required by Section 6004.2 or 6004.3 shall be equipped with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Alternative fire-extinguishing systems shall not be used.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.136

Section 6004.1.3 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.1.3 Exhausted enclosures. Exhausted enclosures containing highly toxic, toxic or moderately toxic gases shall comply with Section 5003.8.6 and the following requirements:

  1. The average ventilation velocity at the face of the enclosure shall not be less than 200 feet per minute (1.02 m/s) with a minimum of 150 feet per minute (0.76 m/s).

  2. Exhausted enclosures shall be connected to an exhaust system.

  3. Exhausted enclosures shall not be used as the sole means of exhaust for any room or area.

Exhausted enclosures required by Section 6004.2 or 6004.3 shall be equipped with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Alternative fire-extinguishing system shall not be used.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.137

Section 6004.1.4 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.4 Automatic shut-off valve. If gas monitoring is not provided, an automatic shut-off valve, which is of a fail-safe to close design, shall be provided to shutoff the supply of toxic and moderately toxic gases upon failure of the required gas cabinet or exhausted enclosure ventilation.

An automatic shut-off valve, which is of a fail-safe to close design, shall be provided to shut off the supply of highly toxic gases for any of the following:

  1. Activation of a manual fire alarm system.

  2. Activation of the gas detection system.

  3. Failure of emergency power.

  4. Failure of primary containment.

  5. Seismic activity.

  6. Failure of required ventilation.

  7. Manual activation at an approved remote location.

An automatic shutoff valve is not required if a manual shutoff valve at the source is readily accessible and the process is continuously attended and supervised by a qualified individual.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.128

Section 6004.1.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.5 Emergency control station. Signals from emergency equipment used for highly toxic gases shall be transmitted to an approved location.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.139

Section 6004.1.6 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.6 Maximum threshold quantity. Toxic gases stored or used in quantities exceeding the maximum threshold quantity in a single vessel per control area or outdoor control area shall comply with the additional requirements for highly toxic gases of Section 6004 of this Code.

Moderately toxic gases stored or used in quantities exceeding the maximum threshold quantity. in a single vessel per control area or outdoor control area shall comply with the additional requirements for toxic gases of Section 6004 of this Code.

The following formula shall be used to calculate the maximum threshold quantity:

Max TQ (pounds) = LC 50 (ppm) × 2 lb.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.140

Section 6004.1.7 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.7 Reduced flow valve. All containers of highly toxic and toxic materials other than lecture bottles containing highly toxic material and having a vapor pressure exceeding 29 psia shall be equipped with a reduced flow valve when available. If a reduced flow valve is not available, the container shall be used with a flow-limiting device. All flow limiting devices shall be part of the valve assembly and visible to the eye when possible; otherwise, they shall be installed as close as possible to the cylinder source.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.141

Section 6004.1.8 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.8 Fire extinguishing systems. Buildings and areas for the storage and use of materials regulated by this Chapter shall be protected by an automatic fire sprinkler system in accordance with NFPA 13. The design of the sprinkler system for any room or area where highly toxic, toxic and moderately toxic gases are stored, handled or used shall be in accordance with Section 5004.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.142

Section 6004.1.9 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.9 Local gas shut off. Manual activation controls shall be provided for highly toxic and toxic gases at locations near the point of use and near the source, as approved by the fire code official. The fire code official may require additional controls at other places, including, but not limited to, the entry to the building, storage or use areas, and emergency control stations. Manual activated shut-off valves shall be of a fail-safe-to-close design.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.143

Section 6004.1.10 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.10 Exhaust ventilation monitoring. For highly toxic and toxic gases exceeding threshold quantities, a continuous monitoring system shall be provided to assure that the required exhaust ventilation rate is maintained. The monitoring system shall initiate a local alarm. The alarm shall be both visual and audible and shall be designed to provide warning both inside and outside of the interior storage, use, or handling area.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.144

Section 6004.1.11 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.11 Emergency response plan. If the preparation of an emergency response plan for the facility is not required by any other law, responsible persons shall prepare, or cause to be prepared, and filed with the fire code official, a written emergency response plan. If the preparation of an emergency response plan is required by other law, a responsible person shall file a copy of the plan with the fire code official.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.145

Section 6004.1.12 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.12 Cylinder leak testing. Cylinders shall be tested for leaks immediately upon delivery and again immediately prior to departure. Testing shall be approved by the fire code official in accordance with appropriate nationally recognized industry standards and practices, if any. Appropriate remedial action shall be immediately undertaken when leaks are detected.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.146

Section 6004.1.13 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.13 Inert gas purge system. Gas systems shall be provided with dedicated inert gas purge systems. A dedicated inert gas purge system may be used to purge more than one gas, provided the gases are compatible. Purge gas systems shall be located in an approved gas cabinet unless the system operates by vacuum demand.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.147

Section 6004.1.14 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.1.14 Seismic shutoff valve. An automatic seismic shut-off valve, which is of a fail-safe to close design, shall be provided to shutoff the supply of highly toxic, toxic and moderately toxic gases with an LC 50 less than or equal to 3000 parts per million upon a seismic event within 5 seconds of a horizontal sinusoidal oscillation having a peak acceleration of 0.3G (1.47 m/sec 2 ) and a period of 0.4 seconds.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.148

Section 6004.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2 Indoor storage and use. The indoor storage or use of highly toxic, toxic and moderately toxic compressed gases shall be in accordance with Sections 6004.2.1 through 6004.2.2.10.4.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.149

Section 6004.2.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2.1 Applicability. The applicability of regulations governing the indoor storage and use of highly toxic, toxic, and moderately toxic gases shall be as set forth in Sections 6004.2.1.1 through 6004.2.1.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.150

Section 6004.2.1.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2.1.1 Quantities not exceeding the maximum allowable quantity per control area. The indoor storage or use of highly toxic, toxic and moderately toxic gases in amounts exceeding the maximum allowable quantity per control area set forth in Table 5003.1.1(2) shall be in accordance with Sections 5001, 5003, 6001, 6004.2.1.4 and 6004.2.1.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.151

Section 6004.2.1.4 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.2.1.4 Quantities not exceeding minimum threshold quantity per control area. The indoor storage or use of highly toxic, toxic and moderately toxic gases in amounts not exceeding the minimum threshold quantity per control area set forth in Table 6004.1 shall be in accordance with Sections 6001, 6004.1 and Chapter 50.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.152

Section 6004.2.1.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.2.1.5 Quantity exceeding the minimum threshold quantity per control area. The indoor storage or use of highly toxic, toxic and moderately gases in amounts exceeding the minimum threshold quantity per control area set forth in Table 6004.1 shall be in accordance with Sections 6001, 6004.1, 6004.2 and Chapter 50.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.153

Section 6004.2.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2.2 General indoor requirements. The general requirements applicable to the indoor storage and use of highly toxic and toxic compressed gases shall be in accordance with Sections 6004.2.2.1 through 6004.2.2.10.4.

Moderately toxic gases with an LC 50 less than or equal to 3000 parts per million shall comply with the requirements for toxic gases in Sections 6004.2.2.1 through 6004.2.2.10.3.

Moderately toxic gases with an LC 50 more than 3000 parts per million but not greater than 5000 parts per million and exceeding the maximum threshold quantity, as determined by 6004.1.6, shall comply with the requirements for toxic gases in Sections 6004.2.2.1 through 6004.2.2.7.

Moderately toxic gases shall not be considered as toxic gases for maximum allowable quantities determinations under Table 5003.1.1(2).

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.154

Section 6004.2.2.7 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2.2.7 Treatment systems. The exhaust ventilation from gas cabinets, exhausted enclosures, gas rooms and local exhaust systems required in Section 6004.2.2.4 and 6004.2.2.5 shall be directed to a treatment system. The treatment system shall be utilized to handle the accidental release of gas and to process exhaust ventilation. The treatment system shall be designed in accordance with Sections 6004.2.2.7.1 through 6004.2.2.7.5 and Section 509 of the California Mechanical Code.

Exceptions:

  1. Highly toxic, toxic and moderately toxic gases storage. A treatment system is not required for cylinders, containers and tanks in storage when all of the following are provided:

1.1.

Valve outlets are equipped with gas-tight outlet plug or caps.

1.2.

Hand wheel-operated valves have handles secured to prevent movement.

1.3.

Approved containment vessels or containment systems are provided in accordance with Section 6004.2.2.3.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.155

Section 6004.2.2.8 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2.2.8 Emergency power. For highly toxic and toxic gas systems, emergency power, in accordance with Section 1203, shall be provided for the following:

  1. Exhaust ventilation system.

  2. Treatment system.

  3. Gas detection system.

  4. Smoke detection system.

  5. Temperature control system.

  6. Fire alarm system.

  7. Emergency alarm system.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.156

Section 6004.2.2.10 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2.2.10 Gas detection system. A gas detection system complying with Section 916 shall be provided to detect the presence of a highly toxic or toxic gas at or below the PEL or ceiling limit of the gas for which detection is provided. In occupied areas where gas cabinets or exhausted enclosures are not provided, the fire code official may require a cyclical basis at intervals not to exceed 5 minutes.

The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit and shall initiate a response in accordance with Sections 6004.2.2.10.1 through 6004.2.2.10.3 if the gas detection system is activated.

Exception: A gas detection system is not required for toxic gases when the physiological warning threshold level for the gas is at a level below the accepted PEL for the gas.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.157

Section 6004.2.2.10.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.2.2.10.1 Alarms. The gas detection system shall initiate a local alarm and transmit a signal to an approved location when a short-term hazard condition is detected. The alarm shall be both visual and audible and shall provide warning both inside and outside the area where the gas is detected. The audible alarm shall be distinct from all other alarms.

Exception: Signal transmission to a constantly attended control station is not required where not more than one cylinder of highly toxic, toxic or moderately toxic gas is stored.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.158

Section 6004.2.2.10.2 of the California Fire Code, 2025 Edition is amended to read as follows:

6004.2.2.10.2 Shut off of gas supply. The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected.

Exception: An automatic shutdown is not required for reactors utilized for the production of highly toxic, toxic or moderately toxic compressed gases where such reactors are:

  1. Operated at pressures less than 15 pounds per square inch gauge (psig) (103.4kPa).

  2. Constantly attended.

  3. Provided with emergency shutoff valves that have ready access.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.159

Section 6004.2.2.10.4 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.2.2.10.4 Emergency alarm. The indoor storage or use of highly toxic or toxic gases in amounts exceeding the minimum threshold quantity per control area set forth in Table 6004.1 shall also comply with Sections 5004.9 and 5005.4.4.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.160

Section 6004.3 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.3 Outdoor storage and use. The outdoor storage or use of highly toxic, toxic and moderately toxic compressed gases shall be in accordance with Sections 6004.3.1 through 6004.3.4.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.161

Section 6004.3.1 of the California Fire Code, 2016 Edition, is amended to read as follows:

6004.3.1 Applicability. The applicability of regulations governing the outdoor storage and use of highly toxic, toxic, and moderately toxic gases shall be as set forth in Sections 6004.3.1.1 through 6004.3.1.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.162

Section 6004.3.1.1 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.3.1.1 Quantities not exceeding the maximum allowable quantity per control area. The outdoor storage or use of highly toxic and toxic gases in amounts exceeding the threshold quantity per control area set forth in Table 5003.1.1(4) shall be in accordance with Sections 5001, 5003, 6001, 6004.1, and 6004.3.1.4 and 6004.3.1.5.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.163

Section 6004.3.1.4 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.3.1.4 Quantities not exceeding minimum threshold quantity per control area. The outdoor storage or use of highly toxic, toxic and moderately toxic gases in amounts not exceeding the minimum threshold quantity per control area set for in Table 6004.1 shall be in accordance with Sections 6001, 6004.1 and Chapter 50.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.164

Section 6004.3.1.5 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6004.3.1.5 Quantity exceeding the minimum threshold quantity per control area. The outdoor storage or use of highly toxic, toxic and moderately gases in amounts exceeding the minimum threshold quantity per control area set forth in Table 6004.1 shall be in accordance with Sections 6001, 6004.1, 6004.3 and Chapter 50.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.165

Section 6004.3.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.3.2 General outdoor requirements. The general requirements applicable to the outdoor storage and use of highly toxic, toxic and moderately toxic gases shall be in accordance with Sections 6004.3.2.1 through 6004.3.2.4.

Moderately toxic gases with an LC 50 equal to or less than 3000 parts per million shall comply with the requirements for toxic gases in Sections 5001, 5003, 6001, 6004.1 and 6004.3.

Moderately toxic gases with an LC 50 more than 3000 parts per million but not greater than 5000 parts per million and exceeding the maximum threshold quantity, as determined by 6004.1.6, shall comply with the requirements for toxic gases in Sections 5001, 5003, 6001, 6004.1 and 6004.3.2.1 through 6004.3.2.4.

Moderately toxic gases shall not be considered as toxic gases for maximum allowable quantities determinations under Table 5003.1.1(4).

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.166

Section 6004.3.3 of the California Fire Code, 2025 Edition, is amended to read as follows:

6004.3.3 Outdoor storage weather protection for portable tanks and cylinders. Weather protection in accordance with Section 5004.13 and this section shall be provided for portable tanks and cylinders located outdoors and not within gas cabinets or exhausted enclosures. The storage area shall be equipped with an approved automatic sprinkler system in accordance with Section 903.3.1.1.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.167

Section 6405.3.1 is hereby added to the California Fire Code, 2025 Edition, to read as follows:

6405.3.1 Silane distribution systems automatic shutdown. Silane distribution systems shall automatically shut down at the source upon activation of the gas detection system at levels above the alarm level and/or failure of the ventilation system for the silane distribution system.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.168

Appendix B105.2 of the California Fire Code, 2025 Edition, is amended to read as follows:

B105.2 Buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses. The minimum fire-flow and flow duration for buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Tables B105.1(2) and B105.2.

Exceptions: [SFM] Group B, S-2 and U occupancies having a floor area not exceeding 1,000 square feet, primarily constructed of noncombustible exterior walls with wood or steel roof framing, having a Class A roof assembly, with uses limited to the following or similar uses:

  1. California State Parks buildings of an accessory nature (restrooms).

  2. Safety roadside rest areas (SRRA), public restrooms.

  3. Truck inspection facilities (TIF), CHP office space and vehicle inspection bays.

  4. Sand/salt storage buildings, storage of sand and salt.

The maximum fire flow reduction for all commercial buildings greater than 30,000 square feet and residential podium buildings shall not exceed 25 percent of the fire flow specified in Table B105.1(2). The maximum fire flow reduction for all other buildings shall not exceed 50 percent of the fire flow specified in Table B105.1(2).

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.169

Section D101.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

D101.1 Scope. Fire apparatus access roads shall be in accordance with this appendix and all other applicable requirements of this Code.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.170

Section D103.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm). See Figure D103.1. Only conditions with 26 feet roads are applicable.

Exception: The fire code official may approve other condition that provides equivalent access.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.171

Section D103.2 through D103.5 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

D103.2 Grade. The maximum grade of a fire department apparatus access road shall not exceed 15-percent, unless approved by the fire code official.

D103.3 Turning radius. The required turning radius of a fire apparatus access roads shall be a minimum of 30 inside, and a minimum of 50 outside.

D103.4 Dead ends. Dead-end fire apparatus access roads in excess of 150 feet (45 720 mm) shall be provided with width and turnaround provisions in accordance with Table D103.4, as approved by the fire code official.

TABLE D103.4 REQUIREMENTS FOR DEAD-END FIRE APPARATUS ACCESS ROADS

Length (Feet) Width (feet) Turnarounds Required
0—150 26 Not required, unless determined necessary by the fire code official
151—500 26 120-foot Hammerhead, 60-foot "Y" or 96-foot-diameter cul-de-sac in accordance with Figure D103.1
500—750 26 120-foot Hammerhead, 60-foot "Y" or 96-foot-diameter cul-de-sac in accordance with Figure D103.1
Over 750 Special approval required.

D103.5 Fire apparatus access road gates. Gates securing the fire apparatus access roads shall comply with all of the following criteria: the fire apparatus access roads shall comply with all of the following criteria:

  1. Where a single gate is provided, the gate width shall be not less than 20 feet (6096 mm). Where a fire apparatus road consists of a divided roadway, the gate width shall be not less than 20 feet (6096 mm).

  2. Gates shall be of the horizontal swing, horizontal slide, vertical lift or vertical pivot type.

  3. Construction of gates shall be of materials that allow manual operation by one person.

  4. Gate components shall be maintained in an operative condition at all times and replaced or repaired when defective.

  5. Electric gates shall be equipped with a means of opening the gate by fire department personnel for emergency access. Emergency opening devices shall be approved by the fire code official.

  6. Methods of locking shall be submitted for approval by the fire code official.

  7. Electric gate operators, where provided, shall be listed in accordance with UL 325.

  8. Gates intended for automatic operation shall be designed, constructed and installed to comply with the requirements of ASTM F2200.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.172

Section D104.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

D104.1 Buildings with two or more fire apparatus access roads. Buildings or facilities exceeding 30 feet (9144 mm), or three stories in height, or 50,000 square feet (5760m 2 ) shall be provided with at least two means of fire apparatus access for each structure.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.173

Section D104.2 of the California Fire Code, 2025 Edition, is deleted in its entirety.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.174

Section D105.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

D105.2 Width. Fire apparatus access roads shall have a minimum unobstructed width of 26 feet (7925 mm) in the immediate vicinity of any building or portion of building more than 30 feet (9144) in height.

Exception: The Fire Code Official may approve the use of other usable space/area that provides equivalent required width.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.175

Section D106.1 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

D106.1 Projects having more than 50 dwelling units. Multiple-family residential projects having more than 50 dwelling units shall be equipped throughout with two separate and approved fire apparatus access roads.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.176

Section D106.2 of the California Fire Code, 2025 Edition, is amended to read in its entirety as follows:

D106.2 Projects having more than 200 dwelling units. For Multiple-family residential projects having more than 200 units, the fire code official may require more than two fire apparatus access roads.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →

V-300-2.177

Section D107.1 of the California Fire Code, 2025 Edition, exceptions No. 1 and No. 2 are deleted.

(Ord. No. 113.27, § 3, 9/2/25)

Exceptions & meaning →