Title 15 — BUILDINGS AND CONSTRUCTION›Division 1 — Fremont Building Standards Code›Chapter 15.35 — FREMONT FIRE CODE
Fremont Municipal Code § 907.6 Fremont Fire Code
Fremont Municipal Code · 2026-10 edition · updated 2026-10-05 · Fremont
Cite as: Fremont Municipal Code § 907.6 · Text as of 2026-10-05
907.6.4.1 – 907.6.4.1.1 {CFC text not modified}¶
907.6.4.2 High-rise buildings. In high-rise buildings, and Group I-2 occupancies having occupied floors located more than 75 feet (22860mm) above the lowest level of fire department vehicle access, a separate zone by floor shall be provided for all the following types of alarm-initiating devices where provided:
Smoke detectors.
Sprinkler water-flow devices.
Manual fire alarm boxes.
Other approved types of automatic fire detection devices or suppression systems in accordance with Fire Department Standard 25A.
907.6.4.3 {CFC text not modified}
Fire alarm initiating devices with individual annunciation in accordance with the Fire Department Standard 25A.
{CFC text not modified}
Fire alarm system troubles in accordance with the Fire Department Standard 25A.
{CFC text not modified}
{CFC text not modified}
907.6.4.4 – 907.6.5 {CFC text not modified}¶
907.6.6 Monitoring. Fire alarm system shall transmit distinctly and descriptively different alarm, supervisory and trouble signals to an approved supervising station in accordance with NFPA 72 and Fire Department Standard 25A or when approved by the Fire Code Official, shall sound an audible signal at a constantly attended location.
907.6.6.1 – 907.10.1 {CFC text not modified}¶