Title 15 — BUILDINGS AND CONSTRUCTION›Division 1 — Fremont Building Standards Code›Chapter 15.35 — FREMONT FIRE CODE

Fremont Municipal Code § 907.1 907.1.2 {CFC text not modified}

Fremont Municipal Code · 2026-10 edition · updated 2026-10-05 · Fremont

Cite as: Fremont Municipal Code § 907.1 · Text as of 2026-10-05

907.1.3 Equipment. Systems and their components shall be California State Fire Marshal listed and approved for the purpose for which they are installed. The building owner shall provide a serially numbered certificate from an approved nationally recognized testing laboratory for all fire alarm systems indicating that the system has been installed in accordance with the approved plans and specifications and meets minimum NFPA Standards. A copy shall be provided to the fire marshal’s office at no cost to the city. Certification shall be required for all new systems installed after January 1, 1996. Existing systems that can no longer be serviced or maintained or those that are deemed problematic shall also be required to obtain this certification within 12 months of notification.

907.1.3.1 Remote Annunciator Location. All new or existing systems that require a new Fire Alarm Control Panel shall have a remote annunciator at the main entrance. It shall be visible to approaching emergency personnel.

907.1.4 – 907.1.5 {CFC text not modified}

907.2 {CFC text not modified}

Exceptions:

  1. deleted

  2. – 3. {CFC text not modified}