Skip to content

Earlier editions: 2026-09

Title 15 — BUILDINGS AND CONSTRUCTION›Division 1 — Fremont Building Standards Code›Chapter 15.35 — FREMONT FIRE CODE

Fremont Municipal Code § 5005.2 Fremont Fire Code

Fremont Municipal Code · 2026-10 edition · updated 2026-10-05 · Fremont

Cite as: Fremont Municipal Code § 5005.2 · Text as of 2026-10-05

5005.2.2 – 5005.2.2.2 {CFC text not modified}

5005.2.2.3 Spill control for hazardous materials liquids. Buildings, rooms or areas where hazardous materials liquids are used shall be provided with spill control in accordance with Section 5004.2.1.

5005.2.2.4 Secondary containment for hazardous materials liquids. Buildings, rooms or areas where hazardous materials liquids are used in vessels or systems shall be provided with secondary containment in accordance with Section 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following:

  1. Individual Vessel or System: Greater than 55 gallons (208.2 L)

  2. Multiple Vessels or Systems: Greater than 1,000 gallons (3785 L)

Exceptions & meaning →

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — Fremont Municipal Code

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.