Title 15 — BUILDINGS AND CONSTRUCTION›Division 1 — Fremont Building Standards Code›Chapter 15.35 — FREMONT FIRE CODE
Fremont Municipal Code § 5005.3 5005.3.3 {CFC text not modified}
Fremont Municipal Code · 2026-10 edition · updated 2026-10-05 · Fremont
Cite as: Fremont Municipal Code § 5005.3 · Text as of 2026-10-05
5005.3.4 Spill control for hazardous materials liquids in open systems. Outdoor areas where hazardous materials liquids are dispensed or used in open systems shall be provided with spill control in accordance with Section 5004.2.1.
5005.3.5 Secondary containment for hazardous materials liquids in open systems. Buildings, rooms or areas where hazardous materials liquids are dispensed or used in open systems shall be provided with secondary containment in accordance with Section 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following:
Individual Vessel or System: Greater than 1.3 gallons (5 L)
Multiple Vessels or Systems: Greater than 5.3 gallons (20 L)
5005.3.6 Spill control for hazardous materials liquids in closed systems. Outdoor areas where hazardous materials liquids are used in closed systems shall be provided with spill control in accordance with Section 5004.2.1.
5005.3.7 Secondary containment for hazardous materials liquids in closed systems. Outdoor areas where hazardous materials liquids are dispensed or used in closed systems shall be provided with secondary containment in accordance with Section 5004.2.2 when the capacity of an individual vessel or system or the capacity of multiple vessels or systems exceeds the following:
Individual Vessel or System: Greater than 55 gallons (208.2 L)
Multiple Vessels or Systems: Greater than 1,000 gallons (3785 L)
5005.3.8 – 5005.4.4 {CFC text not modified}¶