Title 15 — BUILDINGS AND CONSTRUCTION›Division 1 — Fremont Building Standards Code›Chapter 15.35 — FREMONT FIRE CODE
Fremont Municipal Code § 6.3 Fremont Fire Code
Fremont Municipal Code · 2026-10 edition · updated 2026-10-05 · Fremont
Cite as: Fremont Municipal Code § 6.3 · Text as of 2026-10-05
6.3.7.1 System Water Supply valves, isolation control valves and other valves in fire…¶
- Where a building has a fire alarm system or a sprinkler monitoring system installed, the valve shall be supervised by:
a. A central station, proprietary or remote supervising station.
b. Deleted
- When a building does not have a fire alarm system or a sprinkler monitoring system installed, the valve shall be supervised by (a & b):
a. Locking the valves in the open position or
b. Sealing valves in an approved weekly recorded inspection where valves are located within fenced enclosures under the control of the owner.
(d) NFPA 15-22 through 22-23 {CFC text not modified}
(e) NFPA 24-25 is amended to read: