Skip to content

Earlier editions: 20222019

Chapter 3 — BUILDING PLANNING

R325 Light, Ventilation and Heating — 2025 California Residential Code

California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-09-26 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Residential Code (Title 24, Part 2.5) § R325 · Effective January 1, 2026 · Official source: Building Standards Commission

R325.1 Habitable rooms.

Habitable space shall be provided natural light and natural ventilation in accordance with Sections R325.1.1 through R325.1.3.

R325.1.1 Natural light. Habitable rooms shall have an aggregate area of glazed openings not less than 8 percent of the floor area of such rooms. Required glazed openings shall face directly onto a street, alley or public way, or a yard or court located on the same lot as the building.

Exceptions:

  1. Required glazed openings shall be permitted to face into a roofed porch, deck or patio adjacent to a street, alley, public way, yard or court, where there the longer side of the roofed area is not less than 65 percent unobstructed and the ceiling height is not less than 7 feet (2134 mm).

  2. Required glazed openings shall be permitted to face into a sunroom adjacent to a street, alley, public way, yard or court.

  3. Glazed openings are not required where artificial light is provided that is capable of producing an average illumination of 6 footcandles (65 lux) over the area of the room at a height of 30 inches (762 mm) above the floor level.

  4. Eave projections shall not be considered as obstructing the clear open space of a yard or court. 5. Glazed openings may open into a passive solar energy collector provided the area of exterior glazed opening(s) into the passive solar energy collector is increased to compensate for the area required by the interior space.

R325.1.2 Natural ventilation. Habitable rooms shall have an aggregate area openable to the outdoors not less than 4 percent of the floor area of such rooms. Openings shall be through windows, skylights, doors, louvers or other approved openings to the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants.

Exceptions:

  1. Natural ventilation shall not be required in habitable rooms other than kitchens where a whole-house mechanical ventilation system or a mechanical ventilation system capable of producing 0.35 air changes per hour in the habitable rooms is installed in accordance with the California Mechanical Code .

  2. Natural ventilation shall not be required in kitchens where a local exhaust system is installed in accordance with the California Mechanical Code .

  3. Required ventilation openings shall be permitted to open into a thermally isolated sunroom or roofed porch, deck, or patio where not less than 40 percent of the roofed area perimeter is open to the outdoor air.

  4. Required ventilation openings shall be permitted to open into a thermally isolated sunroom provided there is an openable area between the adjoining room and the sunroom of not less than one-tenth of the floor area of the interior room and not less than 20 square feet (1.9 m [2] ). The minimum openable area of the sunroom to outdoor air shall be based on the total floor area of the adjoining room and the sunroom. 5. The windows, doors, louvers and other approved closeable openings not required by Section R319 may open into a passive solar energy collector for ventilation required by this section. The area of ventilation openings to the outside of the passive solar energy collector shall be increased to compensate for the openings required by the interior space.

R325.1.3 Adjoining rooms. For the purpose of determining light and ventilation requirements, rooms shall be considered to be a portion of an adjoining room where not less than one-half of the area of the common wall is open and unobstructed and provides an opening of not less than one-tenth of the floor area of the interior room and not less than 25 square feet (2.3 m [2] ).

Exceptions & meaning →

R325.2 Bathrooms.

Bathrooms, water closet compartments and other similar rooms shall be provided with aggregate glazing area in windows of not less than 3 square feet (0.3 m [2] ), one-half of which shall be openable.

Exception: The glazed areas shall not be required where artificial light and a local exhaust system are provided. The minimum local exhaust rates shall be 50 cubic feet per minute (25 L/s) for intermittent ventilation or 20 cubic feet per minute (10 L/s) for contin- uous ventilation in accordance with the California Mechanical Code, Chapter 4 . Exhaust air from the space shall be exhausted directly to the outdoors.

R325.2.1 Bathroom exhaust fans. Each bathroom containing a bathtub, shower or tub/shower combination shall be mechanically ventilated for purposes of humidity control in accordance with the California Mechanical Code, Chapter 4; and the California Green Building Standards Code, Chapter 4, Division 4.5.

Note: Window operation is not a permissible method of providing bathroom exhaust for humidity control.

3-72 2025 CALIFORNIA RESIDENTIAL CODE

BUILDING PLANNING

Exceptions & meaning →

R325.3 Ventilation.

Ventilation air rates shall be in compliance with the California Mechanical Code.

Exceptions & meaning →

R325.4 Opening location.

Outdoor intake and exhaust openings shall be located in accordance with Sections R325.4.1 and R325.4.2.

R325.4.1 Intake openings. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) from any hazardous or noxious contaminant, such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks.

For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious.

Exceptions:

  1. The 10-foot (3048 mm) separation is not required where the intake opening is located 3 feet (914 mm) or greater below the contaminant source.

  2. Vents and chimneys serving fuel-burning appliances shall be terminated in accordance with the applicable provisions of the California Mechanical Code.

  3. Clothes dryer exhaust ducts shall be terminated in accordance with the California Mechanical Code.

R325.4.2 Exhaust openings. Exhaust air shall not be directed onto walkways.

Exceptions & meaning →

R325.5 Outside opening protection.

Air exhaust and intake openings that terminate outdoors shall be protected with corrosionresistant screens, louvers or grilles having an opening size of not less than 1/4 inch (6 mm) and a maximum opening size of 1/2 inch (13 mm), in any dimension. Openings shall be protected against local weather conditions. Outdoor air exhaust and intake openings shall meet the provisions for exterior wall opening protectives in accordance with this code.

Exceptions & meaning →

R325.6 Interior stairway illumination.

Interior stairways shall be provided with an artificial light source to illuminate the landings and treads. The light source shall be capable of illuminating treads and landings to levels of not less than 1 footcandle (11 lux) as measured at the center of treads and landings. There shall be a wall switch at each floor level to control the light source where the stairway has six or more risers.

Exception: A switch is not required where remote, central or automatic control of lighting is provided.

Exceptions & meaning →

R325.7 Exterior stairway illumination.

Exterior stairways shall be provided with an artificial light source located at the top landing of the stairway. Exterior stairways providing access to a basement from the outdoor grade level shall be provided with an artificial light source located at the bottom landing of the stairway.

Exceptions & meaning →

R325.8 Required heating.

Where the winter design temperature in Table R301.2 is below 60°F (16°C), every dwelling unit shall be provided with heating facilities capable of maintaining a room temperature of not less than 68°F (20°C) at a point 3 feet (914 mm) above the floor and 2 feet (610 mm) from exterior walls in habitable rooms at the design temperature. The installation of one or more portable space heaters shall not be used to achieve compliance with this section.

Note: See Section R301.1.1.1 for limited-density owner-built rural dwellings.

Exceptions & meaning →

R325.9 Passive solar energy collectors.

When a passive solar energy collector is designed as a conditioned area it shall comply with the California Energy Code. Nonconditioned passive solar energy collectors are exempt from the California Energy Code.

Exceptions & meaning →

Explained in plain English

Guides that cite this section.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Residential Code (Title 24, Part 2.5)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.