Chapter 3 — BUILDING PLANNING

Section R325 — LIGHT, VENTILATION AND HEATING

2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · ingested 2026-07-07 · California

Full text via GoCodebook AI

We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.

Ask about this chapter

R325.1 Habitable rooms.

R325.1 Habitable rooms. Habitable space shall be provided natural light and natural ventilation in accordance with Sections R325.1.1 through R325.1.3. R325.1.1 Natural light. Habitable rooms shall have an aggregate area of glazed openings not less than 8 percent of the floor area of such rooms. Required glazed openings shall face directly onto a street, alley or public way, or a yard or court located on the same lot as the building. Exceptions: 1. Required glazed openings shall be permitted to face into a roofed porch, deck or patio adjacent to a street, alley, public way, yard or court,…

R325.2 Bathrooms.

R325.2 Bathrooms. Bathrooms, water closet compartments and other similar rooms shall be provided with aggregate glazing area in windows of not less than 3 square feet (0.3 m [2] ), one-half of which shall be openable. Exception: The glazed areas shall not be required where artificial light and a local exhaust system are provided. The minimum local exhaust rates shall be 50 cubic feet per minute (25 L/s) for intermittent ventilation or 20 cubic feet per minute (10 L/s) for contin- uous ventilation in accordance with the California Mechanical Code, Chapter 4 . Exhaust air from the space shall…

R325.3 Ventilation.

R325.3 Ventilation. Ventilation air rates shall be in compliance with the California Mechanical Code.

R325.4 Opening location.

R325.4 Opening location. Outdoor intake and exhaust openings shall be located in accordance with Sections R325.4.1 and R325.4.2. R325.4.1 Intake openings. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) from any hazardous or noxious contaminant, such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks. For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious. Exceptions: 1. The 10-foot (3048 mm) separation is not…

R325.5 Outside opening protection.

R325.5 Outside opening protection. Air exhaust and intake openings that terminate outdoors shall be protected with corrosionresistant screens, louvers or grilles having an opening size of not less than [1] / 4 inch (6 mm) and a maximum opening size of [1] / 2 inch (13 mm), in any dimension. Openings shall be protected against local weather conditions. Outdoor air exhaust and intake openings shall meet the provisions for exterior wall opening protectives in accordance with this code.

R325.6 Interior stairway illumination.

R325.6 Interior stairway illumination. Interior stairways shall be provided with an artificial light source to illuminate the landings and treads. The light source shall be capable of illuminating treads and landings to levels of not less than 1 footcandle (11 lux) as measured at the center of treads and landings. There shall be a wall switch at each floor level to control the light source where the stairway has six or more risers. Exception: A switch is not required where remote, central or automatic control of lighting is provided.

R325.7 Exterior stairway illumination.

R325.7 Exterior stairway illumination. Exterior stairways shall be provided with an artificial light source located at the top landing of the stairway. Exterior stairways providing access to a basement from the outdoor grade level shall be provided with an artificial light source located at the bottom landing of the stairway.

R325.8 Required heating.

R325.8 Required heating. Where the winter design temperature in Table R301.2 is below 60°F (16°C), every dwelling unit shall be provided with heating facilities capable of maintaining a room temperature of not less than 68°F (20°C) at a point 3 feet (914 mm) above the floor and 2 feet (610 mm) from exterior walls in habitable rooms at the design temperature. The installation of one or more portable space heaters shall not be used to achieve compliance with this section. Note: See Section R301.1.1.1 for limited-density owner-built rural dwellings.

R325.9 Passive solar energy collectors.

R325.9 Passive solar energy collectors. When a passive solar energy collector is designed as a conditioned area it shall comply with the California Energy Code. Nonconditioned passive solar energy collectors are exempt from the California Energy Code.