Section R335 — SPECIAL PROVISIONS FOR LICENSED 24-HOUR CARE FACILITIES IN A GROUP R-3.1
2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
R335.1 Scope. ¶
R335.1 Scope. The provisions of this section shall apply to 24-hour care facilities in a Group R-3.1 occupancy licensed by a governmental agency.
R335.2 General. ¶
R335.2 General. The provisions in this section shall apply in addition to general requirements in this code. R335.2.1 Restraint shall not be practiced in a Group R-3.1 occupancy. Exception: Occupancies which meet all the requirements for a Group I-3 occupancy. R335.2.2 Pursuant to Health and Safety Code Section 13133, regulations of the state fire marshal pertaining to Occupancies classi- fied as Residential Facilities (RF) and Residential-care Facilities for the Elderly (RCFE) shall apply uniformly throughout the state and no city, county, city and county, including a charter city or charter…
R335.3 Building height and area provisions. ¶
R335.3 Building height and area provisions. R335.3.1 Limitations six or less clients. Group R-3.1 occupancies where nonambulatory clients are housed above the first story, having more than two stories in height or having more than 3,000 square feet (279 m [2] ) of floor area above the first story shall not be of less than one-hour fire-resistance-rated construction throughout. In Group R-3.1 occupancies housing a bedridden client, the client sleeping room shall not be located above or below the first story. Exception: Clients who become bedridden as a result of a temporary illness as defined…
R335.4 Interior finish provisions. ¶
R335.4 Interior finish provisions. R335.4.1 Interior wall and ceiling finish. Group R-3.1 occupancies housing a bedridden client shall comply with Interior Wall and Ceiling Finish requirements specified for Group I-2 occupancies in Table 803.11 of the California Building Code.
R335.5 Fire protection system provisions. ¶
R335.5 Fire protection system provisions. R335.5.1 Automatic sprinkler systems in Group R-3.1 occupancies. An automatic sprinkler system shall be installed where required in Section R313. Exceptions: 1. Existing Group R-3 occupancies converted to Group R-3.1 occupancies not housing bedridden clients, not housing nonambulatory clients above the first floor, and not housing clients above the second floor. 2. Existing Group R-3 occupancies converted to Group R-3.1 occupancies housing only one bedridden client and complying with Section R335.6.3.3. 3. Pursuant to Health and Safety Code Section…
R335.6 Means of egress provisions. ¶
R335.6 Means of egress provisions. R335.6.1 General. In addition to the general means of egress requirements of Chapter 10 of the California Building Code, this section shall apply to Group R-3.1 occupancies. R335.6.2 Number of exits. 3-80 2025 CALIFORNIA RESIDENTIAL CODE on Jul 18, 2025 11:14 AM (CDT) THEREUNDER. BUILDING PLANNING R335.6.2.1. Group R-3.1 occupancies shall have a minimum of two exits. R335.6.3 Egress arrangements. R335.6.3.1. Egress through adjoining dwelling units shall not be permitted. R335.6.3.2 Group R-3.1 occupancies housing nonambulatory clients. In a Group R-3.1…
R335.7 Request for alternate means of protection for facilities housing bedridden clients. ¶
R335.7 Request for alternate means of protection for facilities housing bedridden clients. Request for alternate means of protection shall apply to Sections R335 through R335.7. Request for approval to use an alternative material, assembly or materials, equipment, method of construction, method of installation of equipment, or means of protection shall be made in writing to the local fire authority having jurisdiction by the facility, client or the client’s authorized representative. Sufficient evidence shall be submitted to substantiate the need for an alternate means of protection. The…
R335.8 Temporarily bedridden clients. ¶
R335.8 Temporarily bedridden clients. Clients who become temporarily bedridden as defined in Health and Safety Code Section 1569.72, as enforced by the Department of Social Services, may continue to be housed on any story in Group R-3.1 occupancies classified as Residential Care Facilities for the Elderly (RCFE). Every Residential Care Facility for the Elderly (RCFE) admitting or retaining a bedrid- den resident shall, within 48 hours of the resident's admission or retention in the facility, notify the local fire authority with jurisdiction of the estimated length of time the resident will…
R335.9 Group R. ¶
R335.9 Group R. Buildings housing protective social-care homes or in occupancies housing inmates who are not restrained need not be of one-hour fire-resistive construction when not more than two stories in height. In no case shall individual floor areas exceed 3,000 square feet (279 m [2] ). The fire-resistive protection of the exterior walls shall not be less than one hour where such walls are located within 5 feet (1524 mm) of the property line. Openings within such walls are not permitted. Openings in exterior nonrated walls need not be protected.