Section R315 — SLEEPING LOFTS
2025 California Residential Code (Title 24, Part 2.5) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
R315.1 Sleeping lofts. ¶
Where provided in dwelling units or sleeping units, sleeping lofts shall comply with this code as modified by Sections R315.2 through R315.5. Sleeping lofts constructed in compliance with this section shall be considered a portion of the story below. Such sleeping lofts shall not contribute to the number of stories as regulated by this code.
Exceptions: Sleeping lofts need not comply with Section R315 where they meet any of the following conditions:
- The sleeping loft has a depth of less than 3 feet (914 mm).
- The sleeping loft has a floor area of less than 35 square feet (3.3 m [2] ).
- The sleeping loft is not provided with a permanent means of egress.
R315.2 Sleeping loft limitations. ¶
Sleeping lofts shall comply with the following conditions:
- The sleeping loft floor area shall be less than 70 square feet (6.5 m [2] ).
- The sleeping loft ceiling height shall not exceed 7 feet (2134 mm) for more than one-half of the sleeping loft floor area.
R315.3 Sleeping loft ceiling height. ¶
The clear height below the sleeping loft floor construction shall not be less than 7 feet (2134 mm). The ceiling height above the finished floor of the sleeping loft shall not be less than 3 feet (914 mm). Spaces adjacent to the sleeping loft with a sloped ceiling measuring less than 3 feet (914 mm) from the finished floor to the finished ceiling shall not contribute to the sleeping loft floor area.
R315.4 Sleeping loft area. ¶
The aggregate area of all sleeping lofts and mezzanines within a room shall comply with Section R314.3.
Exception: The area of a single sleeping loft located within a dwelling unit or sleeping unit equipped with an automatic sprinkler system in accordance with Section R309 shall not be greater than two-thirds of the area of the room in which it is located, provided that no other sleeping lofts or mezzanines are open to the room in which the sleeping loft is located.
R315.5 Permanent egress for sleeping lofts. ¶
A permanent means of egress shall be provided for sleeping lofts. The means of egress shall comply with Section R318 as modified by Sections R315.5.1 through R315.5.3.
R315.5.1 Ceiling height at sleeping loft means of egress. A ceiling height of not less than 3 feet (914 mm) shall be provided for the entire width of the means of egress from the sleeping loft.
R315.5.2 Stairways. Stairways providing egress from sleeping lofts shall be permitted to comply with Sections R315.5.2.1 through R315.5.2.3.
3-60 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
BUILDING PLANNING
R315.5.2.1 Width. Stairways providing egress from a sleeping loft shall not be less than 17 inches (432 mm) in clear width at or above the handrail. The width below the handrail shall be not less than 20 inches (508 mm).
R315.5.2.2 Treads and risers. Risers for stairs providing egress from a sleeping loft shall be not less than 7 inches (178 mm) and not more than 12 inches (305 mm) in height. Tread depth and riser height shall be calculated in accordance with one of the following formulas:
- The tread depth shall be 20 inches (508 mm) minus four-thirds of the riser height.
- The riser height shall be 15 inches (381 mm) minus three-fourths of the tread depth.
R315.5.2.3 Landings. Landings at stairways providing egress from sleeping lofts shall comply with Section R318.7.6, except that the depth of landings in the direction of travel shall be not less than 24 inches (610 mm).
R315.5.3 Ladders. Ladders used as a means of egress from sleeping lofts shall comply with Sections R315.5.3.1 and R315.5.3.2.
R315.5.3.1 Size and capacity. Ladders providing egress from sleeping lofts shall have a rung width of not less than 12 inches (305 mm), and 10-inch (254 mm) to 14-inch (356 mm) spacing between rungs. Ladders shall be capable of supporting a 300pound (136 kg) load on any rung. Rung spacing shall be uniform within [3] / 8 inch (9.5 mm).
R315.5.3.2 Incline. Ladders shall be inclined at 70 to 80 degrees from horizontal.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Residential Code (Title 24, Part 2.5)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
-
▸ Chapter 3 — BUILDING PLANNING
Overview- Section R300 — SITE DRAINAGE
- Section R301 — DESIGN CRITERIA
- Section R302 — FIRE-RESISTANT CONSTRUCTION
- Section R303 — FOAM PLASTIC
- Section R304 — PROTECTION OF WOOD AND WOOD-BASED PRODUCTS AGAI…
- Section R305 — PROTECTION AGAINST SUBTERRANEAN TERMITES
- Section R306 — FLOOD-RESISTANT CONSTRUCTION
- Section R307 — STORM SHELTERS
- Section R308 — SITE ADDRESS
- Section R309 — AUTOMATIC SPRINKLER SYSTEMS
- Section R310 — SMOKE ALARMS
- Section R311 — CARBON MONOXIDE ALARMS
- Section R312 — MINIMUM ROOM AREAS
- Section R313 — CEILING HEIGHT
- Section R314 — MEZZANINES
- Section R315 — SLEEPING LOFTS
- Section R316 — HABITABLE ATTICS
- Section R317 — GARAGES AND CARPORTS
- Section R318 — MEANS OF EGRESS
- Section R319 — EMERGENCY ESCAPE AND RESCUE OPENINGS
- Section R320 — HANDRAILS
- Section R321 — GUARDS AND WINDOW FALL PROTECTION
- Section R322 — ACCESSIBILITY
- Section R323 — ELEVATORS AND PLATFORM LIFTS
- Section R324 — GLAZING
- Section R325 — LIGHT, VENTILATION AND HEATING
- Section R326 — SANITATION
- Section R327 — TOILET, BATH AND SHOWER SPACES
- Section R328 — AGING-IN-PLACE DESIGN AND FALL PREVENTION
- Section R329 — SOLAR ENERGY SYSTEMS
- Section R330 — ENERGY STORAGE SYSTEMS
- Section R331 — STATIONARY ENGINE GENERATORS
- Section R332 — STATIONARY FUEL CELL POWER SYSTEMS
- Section R333 — RESERVED
- Section R334 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECY…
- Section R335 — SPECIAL PROVISIONS FOR LICENSED 24-HOUR CARE FA…
- Section R336 — LARGE FAMILY DAY-CARE HOMES
- Section R337 — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR…
- Section R338 — ELECTRIC VEHICLE
- Section 339 — RESERVED
- Section R340 — POLLUTANT CONTROL
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AA — BOARD OF APPEALS
- Appendix AB — PERMIT FEES
- Appendix AC — RESERVED
- Appendix BA — RESERVED
- Appendix BB — TINY HOUSES
- Appendix BC — RESERVED
- Appendix BD — RESERVED
- Appendix BE — RADON CONTROL METHODS
- Appendix BF — PATIO COVERS
- Appendix BG — SOUND TRANSMISSION
- Appendix BH — AUTOMATIC VEHICULAR GATES
- Appendix BI — LIGHT STRAW-CLAY CONSTRUCTION
- Appendix BJ — STRAWBALE CONSTRUCTION
- Appendix BK — COB CONSTRUCTION (MONOLITHIC ADOBE)
- Appendix BL — HEMP-LIME (HEMPCRETE) CONSTRUCTION
- Appendix BM — 3D-PRINTED BUILDING CONSTRUCTION
- Appendix BN — EXTENDED PLATE WALL CONSTRUCTION
- Appendix BO — EXISTING BUILDINGS AND STRUCTURES
- Appendix CA — RESERVED
- Appendix CB — RESERVED
- Appendix CC — RESERVED
- Appendix CD — RESERVED
- Appendix CE — RESERVED
- Appendix CF — RESERVED
- Appendix CG — NONSEWERED SANITATION SYSTEMS
- Appendix CH — PRIVATE SEWAGE DISPOSAL
- Appendix CI — SWIMMING POOL SAFETY ACT
- Appendix CJ — EMERGENCY HOUSING
- Appendix CK — AREAS PROTECTED BY THE FACILITIES OF THE CENTRAL…