R311.1 General. Ca rbon monoxide alarms shall comply with Section R311. ¶
R311.1 General. Ca rbon monoxide alarms shall comply with Section R311. R311.1.1 Listings. Carbon monoxide alarms shall be listed and labeled in accordance with UL 2034. Combination carbon monoxide and smoke alarms shall be listed and labeled in accordance with UL 217 and UL 2034. No person shall install, market, distribute, offer for sale or sell any carbon monoxide device in the State of California unless the device and instructions have been approved and listed by the Office of the State Fire Marshal. R311.1.2 Installation. Carbon monoxide alarms, and combination carbon monoxide and smoke…
R311.2 Where required. ¶
R311.2 Where required. Carbon monoxide alarms shall be provided in accordance with Sections R311.2.1 and R311.2.2. Pursuant to Health and Safety Code Section 17926, carbon monoxide devices shall be installed in all existing dwelling units as required in this section. R311.2.1 Existing buildings and new construction. For existing buildings and new construction, carbon monoxide alarms shall be provided in dwelling units where either or both of the following conditions exist. 1. The dwelling unit contains a fuel-fired appliance or fireplace. 2. The dwelling unit has an attached garage with an…
R311.3 Location. ¶
R311.3 Location. Carbon monoxide alarms in dwelling units shall be installed and maintained in accordance with the manufacturer’s published instructions in the following locations: 1. Outside of each separate sleeping area in the immediate vicinity of the bedrooms. 2. On every occupiable level of a dwelling unit, including basements. 3. Where a fuel-burning appliance is located within a bedroom or its attached bathroom, a carbon monoxide alarm shall be installed within the bedroom.
R311.4 Combination alarms. ¶
R311.4 Combination alarms. Combination carbon monoxide and smoke alarms shall be permitted to be used in lieu of carbon monoxide alarms. Combination carbon monoxide/smoke alarms shall comply with Section R311 and all requirements for listing and approval by the Office of the State Fire Marshal for smoke alarms.
R311.5 Interconnectivity. ¶
R311.5 Interconnectivity. Where more than one carbon monoxide alarm is required to be installed within an individual dwelling unit in accordance with Section R311.3, the alarm devices shall be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit. Physical interconnection of carbon monoxide alarms shall not be required where listed wireless alarms are installed and all alarms sound upon activation of one alarm. Exception: Interconnection of carbon monoxide alarms in existing buildings built prior to January 1, 2011,…
R311.6 Power source. ¶
R311.6 Power source. Carbon monoxide alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and, where primary power is interrupted, shall receive power from a battery. Wiring shall be permanent and without a disconnecting switch other than those required for overcurrent protection. Exceptions: 1. Carbon monoxide alarms shall be permitted to be battery operated where installed in buildings without commercial power. 2. Carbon monoxide alarms installed in accordance with Section R311.2.2 shall be permitted to be battery powered.…
R311.7 Carbon monoxide detection systems. ¶
R311.7 Carbon monoxide detection systems. Carbon monoxide detection systems shall be permitted to be used in lieu of carbon monoxide alarms and shall comply with Sections R311.7.1 through R311.7.4. R311.7.1 General. Household carbon monoxide detection systems shall comply with NFPA 72. Carbon monoxide detectors shall be listed in accordance with UL 2075. R311.7.2 Location. Carbon monoxide detectors shall be installed and maintained in the locations specified in Section R311.3 or NFPA 72. R311.7.3 Permanent fixture. Where a household carbon monoxide detection system is installed, it shall…