Section A5.504
California Green Building Standards Code (Title 24, Part 11) · 2019 edition · updated 2026-09-12 · California
POLLUTANT CONTROL
A5.504.4.5.1 No-added formaldehyde. Use composite wood products approved by the California Air Resources Board (ARB) as no-added formaldehyde (NAF) based resins or ultra-low-emitting formaldehyde (ULEF) resins.
Notes:
See Title 17, Section 93120.3(c) and (d), respectively.
Documentation must be provided verifying that materials are certified to meet the pollutant emission limits. A list of manufacturers and their NAF and ULEF certified materials is provided at http://www.arb.ca.gov/toxics/compwood/ naf_ulef/ listofnaf_ulef.htm.
A5.504.4.9 Acoustical ceilings and wall panels. Comply with Chapter 8 in Title 24, Part 2, the California Building Code and with the VOC-emission limits defined in the 2009 CHPS criteria and listed on its High Performance Products Database.
A5.504.4.9.1 Verification of compliance. Documentation shall be provided verifying that acoustical finish materials meet the pollutant emission limits.
Note: Products compliant with CHPS criteria certified under the Greenguard Children & Schools program may also be used.
Note: [OSHPD 1, 2 &4] Documentation shall be provided that verifies that finish materials are certified to meet the pollutant emission limits.
A5.504.5 Hazardous particulates and chemical pollutants. Minimize and control pollutant entry into buildings and cross-contamination of regularly occupied areas.
A5.504.5.1 Entryway systems. Install permanent entryway systems measuring at least six feet in the primary direction of travel to capture dirt and particulates at entryways directly connected to the outdoors.
Qualifying entryways are those that serve as regular entry points for building users.
Acceptable entryway systems include, but are not limited to, permanently installed grates, grilles or slotted systems that allow cleaning underneath.
Roll-out mats are acceptable only when maintained regularly by janitorial contractors as documented in service contract or by in-house staff as documented by written policies and procedures.
A5.504.8 Finish material pollutant control. [OSHPD 1, 2 & 4] Finish materials shall comply with Sections A5.504.4.1 through A5.504.4.5.
A5.504.8.1 Adhesives, sealants and caulks. Adhesives, sealants and caulks used on the project shall meet the requirements of the following standards:
- Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable or SCAQMD Rule 1168 VOC limits, as shown in Tables A5.504.8.1 and A5.504.8.2. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and trichloroethylene), except for aerosol products as specified in Subsection 2, below.
ol or air quality management district rules where applicable or SCAQMD Rule 1168 VOC limits, as shown in Tables A5.504.8.1 and A5.504.8.2. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and trichloroethylene), except for aerosol products as specified in Subsection 2, below.
- Aerosol adhesives and smaller unit sizes of adhesives and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than one pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with Section 94507.
Note: Title 17 may be found at http://ccr.oal.ca.gov/.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
APPENDIX A6.1 – VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]
TABLE A5.504.8.1 ADHESIVE VOC LIMIT 1,2 Less Water and Less Exempt Compounds in Grams per Liter
| ARCHITECTURAL APPLICATIONS | CURRENT VOC LIMIT |
|---|---|
| Indoor carpet adhesives | 50 |
| Carpet pad adhesives | 50 |
| Outdoor carpet adhesives | 150 |
| Wood flooring adhesive | 100 |
| Rubber floor adhesives | 60 |
| Subfloor adhesives | 50 |
| Ceramic tile adhesives | 65 |
| VCT and asphalt tile adhesives | 50 |
| Drywall and panel adhesives | 50 |
| Cove base adhesives | 50 |
| Multipurpose construction adhesives | 70 |
| Structural glazing adhesives | 100 |
| Single-ply roof membrane adhesives | 250 |
| Other adhesive not specifically listed | 50 |
| SPECIALTY APPLICATIONS | |
| PVC welding | 510 |
| CPVC welding | 490 |
| ABS welding | 325 |
| Plastic cement welding | 250 |
| Adhesive primer for plastic | 550 |
| Contact adhesive | 80 |
| Special purpose contact adhesive | 250 |
| Structural wood member adhesive | 140 |
| Top and trim adhesive | 250 |
| SUBSTRATE SPECIFIC APPLICATIONS | |
| Metal to metal | 30 |
| Plastic foams | 50 |
| Porous material (except wood) | 50 |
| Wood | 30 |
| Fiberglass | 80 |
- If an adhesive is used to bond dissimilar substrates together the adhesive with the highest VOC content shall be allowed.
- For additional information regarding methods to measure the VOC content specified in this table, see South Coast Air Quality Management District Rule 1168, http://www.arb.ca.gov/DRDB/SC/CURHTML/R1168.PDF.
A5.504.8.3 Paints and coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Coatings Suggested Control Measure, as shown in Table A5.504.8.3, unless local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table A5.504.8.3, shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss coating, based on its gloss, as defined in Subsections 4.21, 4.36 and 4.37 of the 2007 California Air Resources Board, Suggested Control Measure and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in Table A5.504.8.3 shall apply.
TABLE A5.504.8.2 SEALANT VOC LIMIT Less Water and Less Exempt Compounds in Grams per Liter
| SEALANTS | CURRENT VOC LIMIT |
|---|---|
| Architectural | 250 |
| Marine deck | 760 |
| Nonmembrane roof | 300 |
| Roadway | 250 |
| Single-ply roof membrane | 450 |
| Other | 420 |
| SEALANT PRIMERS | |
| Architectural Nonporous Porous |
250 775 |
| Modified bituminous | 500 |
| Marine deck | 760 |
| Other | 750 |
Note: For additional information regarding methods to measure the VOC content specified in these tables, see South Coast Air Quality Management District Rule 1168: http://www.arb.ca.gov/DRDB/SC/CURHTML/ R1168.PDF.
A5.504.8.3.1 Aerosol paints and coatings. Aerosol paints and coatings shall meet the Product-Weighted MIR Limits for ROC in Section 94522(a)(3) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in Sections 94522(c)(2) and (d)(2) of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation 8 Rule 49.
A5.504.8.3.2 Verification. Verification of compliance with this section shall be provided at the request of the enforcing agency. Documentation may include, but is not limited to, the following:
Manufacturers product specification.
Field verification of on-site product containers.
A5.504.8.4 Carpet systems. All carpet installed in the building interior shall meet the testing and product requirements of one of the following:
Carpet and Rug Institute’s Green Label Plus Program.
California Department of Public Health Standard Practice for the testing of VOCs (Specification 01350).
NSF/ANSI 140 at the Gold level.
Scientific Certifications Systems Sustainable Choice.
206 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
APPENDIX A6.1 – VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]
TABLE A5.504.8.3 VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS 2, 3
Grams of VOC Per Liter of Coating, Less Water and Less Exempt Compounds
A5.504.8.4.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the Carpet and Rug Institute Green Label program.
A5.504.8.4.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table A5.504.8.1.
A5.504.8.5 Composite wood products. Hardwood plywood, particleboard and medium density fiberboard composite wood products used on the interior or exterior of the building shall meet the requirements for formaldehyde as specified in ARB’s Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections, as shown in Table A5.504.8.5
TABLE A5.504.8.5 FORMALDEHYDE LIMITS 1
| Product | Current Limit |
Jan 1, 2012 |
July 1, 2012 |
|---|---|---|---|
| Hardwood plywood veneer core | 0.05 | ||
| Hardwood plywood composite core | 0.08 | 0.05 | |
| Particle board | 0.09 | ||
| Medium density fiberboard | 0.11 | ||
| Thin medium density fiberboard2 | 0.21 | .13 |
| COATING CATEGORY | EFFECTIVE 1/1/2010 |
EFFECTIVE 1/1/2012 |
|---|---|---|
| Flat coatings | 50 | |
| Nonflat coatings | 100 | |
| Nonflat-high gloss coatings | 150 | |
| Specialty coatings | Specialty coatings | Specialty coatings |
| Aluminum roof coatings | 400 | |
| Basement specialty coatings | 400 | |
| Bituminous roof coatings | 50 | |
| Bituminous roof primers | 350 | |
| Bond breakers | 350 | |
| Concrete curing compounds | 350 | |
| Concrete/masonry sealers | 100 | |
| Driveway sealers | 50 | |
| Dry fog coatings | 150 | |
| Faux finishing coatings | 350 | |
| Fire-resistive coatings | 350 | |
| Floor coatings | 100 | |
| Form-release compounds | 250 | |
| Graphic arts coatings (sign paints) | 500 | |
| High-Temperature coatings | 420 | |
| Industrial maintenance coatings | 250 | |
| Low solids coatings1 | 120 | |
| Magnesite cement coatings | 450 | |
| Mastic texture coatings | 100 | |
| Metallic pigmented coatings | 500 | |
| Multicolor coatings | 250 | |
| Pretreatment wash primers | 420 | |
| Primers, sealers and undercoaters | 100 | |
| Reactive penetrating sealers | 350 | |
| Recycled coatings | 250 | |
| Roof coatings | 50 | |
| Rust preventative coatings | 400 | 250 |
| Shellacs: Clear Opaque |
730 550 |
|
| Specialty primers, sealers and undercoaters | 350 | 100 |
| Stains | 250 | |
| Stone consolidants | 450 | |
| Swimming pool coatings | 340 | |
| Traffic marking coatings | 100 | |
| Tub and tile refinish coatings | 420 | |
| Waterproofing membranes | 250 | |
| Wood coatings | 275 | |
| Wood preservatives | 350 | |
| Zinc-rich primers | 340 |
- Grams of VOC Per liter of coating, including water and including exempt compounds.
- The specified limits remain in effect unless revised limits are listed in subsequent columns in the table.
- Values in this table are derived from those specified by the California Air Resources Board, Architectural Coatings Suggested Control Measure, February 1, 2008. More information is available at Air Resources Board.
OC Per liter of coating, including water and including exempt compounds. 2. The specified limits remain in effect unless revised limits are listed in subsequent columns in the table. 3. Values in this table are derived from those specified by the California Air Resources Board, Architectural Coatings Suggested Control Measure, February 1, 2008. More information is available at Air Resources Board.
- Values in this table are derived from those specified by the California Air Resources Board, Air Toxics Control Measure for Composite Wood as tested in accordance with ASTM E1333-96 (2002). For additional information, see California Code of Regulations, Title 17, Sections 93120 through 93120.12.
- Thin medium density fiberboard has a maximum thickness of eight millimeters.
A5.504.8.5.2 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following:
Product certifications and specifications.
Chain of custody certifications.
Other methods acceptable to the enforcing agency.
A5.504.9 Environmental tobacco smoke (ETS) control.
[OSHPD 1, 2 & 4] Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building, if not already prohibited by other laws or regulations, or as enforced by ordinances, regulations or policies of any city, county, city and county, California Community College, campus of the California State University or campus of the University of California, whichever are more stringent. When ordinances, regulations or policies are not in place, post signage to inform building occupants of the prohibitions.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Green Building Standards Code (Title 24, Part 11)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GREEN BUILDING
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 6 — REFERENCED ORGANIZATIONS AND STANDARDS
- Chapter 7 — INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
- Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
- Appendix A4
▸Appendix A5
Overview- Section A5.101
- Section A5.102
- Section A5.103
- Section A5.104
- Section A5.105
- Section A5.106
- Section A5.201
- Section A5.202
- Section A5.203
- Section A5.211
- Section A5.212
- Section A5.213
- Section A5.301
- Section A5.302
- Section A5.303
- Section A5.304
- Section A5.305
- Section A5.401
- Section A5.402
- Section A5.403
- Section A5.404
- Section A5.405
- Section A5.406
- Section A5.408
- Section A5.409
- Section A5.501
- Section A5.502
- Section A5.504
- Section A5.507
- Section A5.508
- Section A5.601
- Section A5.106
- Section A5.202
- Section A5.203
- Section A5.204
- Section A5.205 — [OSHPD 1 & 4]
- Section A5.207 — [OSHPD 1, 2 & 4]
- Section A5.210 — [OSHPD 1, 2 & 4]
- Section A5.401
- Section A5.407 — [OSHPD 1, 2 & 4]
- Section A5.408
- Section A5.410
- Section A5.504
- Section A5.505 — [OSHPD 1, 2 & 4]