Section A5.504
California Green Building Standards Code (Title 24, Part 11) · 2019 edition · updated 2026-09-12 · California
POLLUTANT CONTROL
A5.504.1 Indoor air quality (IAQ) during construction. Maintain IAQ as provided in Sections A5.504.1.1 and A5.504.1.2.
A5.504.1.1 Temporary ventilation. Provide temporary ventilation during construction in accordance with Section 120.1 (Requirements for Ventilation) of the California Energy Code, CCR, Title 24, Part 6 and Chapter 4 of CCR, Title 8 and as follows:
Ventilation during construction shall be achieved through openings in the building shell using fans to produce a minimum of three air changes per hour.
If the building is occupied during demolition or construction, meet or exceed the recommended Control Measures of the Sheet Metal and Air Conditioning Contractors’ National Association (SMACNA) IAQ Guidelines for Occupied Buildings under Construction, 1995, Chapter 3.
A5.504.1.2 Additional IAQ measures. Employ additional measures as follows:
When using generators to generate temporary power, use generators meeting the requirements of CCR, Title 13, Chapter 9 or local ordinance, whichever is more stringent.
Protect on-site absorbent materials from moisture. Remove and replace any materials with evidence of mold, mildew or moisture infiltration.
Store odorous and high VOC-emitting materials offsite, without packaging, for a sufficient period to allow odors and VOCs to disperse.
When possible, once materials are on the jobsite, install odorous and high VOC-emitting materials prior to those that are porous or fibrous.
Clean oil and dust from ducts prior to use.
A5.504.2 IAQ postconstruction. After all interior finishes have been installed, flush out the building by supplying continuous ventilation with all air handling units at their maximum outdoor air rate and all supply fans at their maximum position and rate for at least 14 days.
During this time, maintain an internal temperature of at least 60°F and relative humidity no higher than 60 percent. If extenuating circumstances make these temperature and humidity limits unachievable, the flushout may be conducted under conditions as close as possible to these limits, provided that documentation of the extenuating circumstances is provided in writing.
Occupancy may start after 4 days, provided flush-out continues for the full 14 days. During occupied times, the thermal comfort conditions of Title 24 must be met.
For buildings that rely on natural ventilation, exhaust fans and floor fans must be used to improve air mixing and removal during the 14-day flush-out and windows should remain open.
Do not “bake out” the building by increasing the temperature of the space.
If continuous ventilation is not possible, flush-out air must total the equivalent of 14 days of maximum outdoor air. The equivalent of 14 days of maximum outdoor air (the target air volume) shall be calculated by multiplying the maximum feasible air flow rate (in ft 3 / m) by 14 days (20,160 minutes). The air volumes for each period of ventilation are then calculated and summed and the flush-out continues until the total equals the target air volume.
l the equivalent of 14 days of maximum outdoor air. The equivalent of 14 days of maximum outdoor air (the target air volume) shall be calculated by multiplying the maximum feasible air flow rate (in ft 3 / m) by 14 days (20,160 minutes). The air volumes for each period of ventilation are then calculated and summed and the flush-out continues until the total equals the target air volume.
A5.504.2.1 IAQ testing. If the engineer determines that building flush-out pursuant to Section A5.504.2 is not feasible, a testing alternative may be employed after all interior finishes have been installed, using testing protocols recognized by the United States Environmental Protection Agency (U.S. EPA).
148 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
A5.504.2.1.1 Maximum levels of contaminants. Allowable levels of contaminant concentrations measured by testing shall not exceed the following:
Carbon Monoxide (CO): 9 parts per million, not to exceed outdoor levels by 2 parts per million;
Formaldehyde: 27 parts per billion;
Particulates (PM10): 50 micrograms per cubic meter;
4-Phenylcyclohexene (4-PCH), if fabrics and carpets with styrene butadiene rubber (SBR) latex backing, are installed: 6.5 micrograms per cubic meter; and
Total Volatile Organic Compounds (TVOC): 300 micrograms per cubic meter.
A5.504.2.1.2 Test protocols. Testing of indoor air quality should include the following elements:
The contaminant sampling and averaging times and the measurement methods should be sufficient to achieve a Limit of Detection that is below the maximum allowable concentrations.
Testing should be conducted with the HVAC system operated at the minimum design outdoor air ventilation rate.
Air samplers and monitors should be located near likely sources of formaldehyde and other volatile organic compounds, at a height of 3 to 6 feet from the floor and well away from walls and air diffusers.
The test protocols should be justified with documentation to show that appropriate sampling methods and times were used.
A5.504.2.1.3 Noncomplying building areas. For each sampling area of the building exceeding the maximum concentrations specified in Section A5.504.2.1.1, flush out with outside air and retest samples taken from the same area. Repeat the procedures until testing demonstrates compliance.
Note: U.S. EPA-recognized testing protocols may be found on the Air Resources Board web site.
A5.504.4.5.1 No added formaldehyde Tier 1. Use composite wood products approved by the California Air Resources Board (ARB) as no-added formaldehyde (NAF) based resins or ultra-low emitting formaldehyde (ULEF) resins.
Notes:
See Title 17, Section 93120.3(c) and (d), respectively.
Documentation must be provided verifying that materials are certified to meet the pollutant emission limits. A list of manufacturers and their NAF and ULEF certified materials is provided at: http://www.arb.ca.gov/toxics/ compwood/naf_ulef/listofnaf_ulef.htm.
NONRESIDENTIAL VOLUNTARY MEASURES
A5.504.4.7 Resilient flooring systems, Tier 1. For 90 percent of floor area receiving resilient flooring, install resilient flooring that is:
Certified under the Resilient Floor Covering Institute (RFCI) FloorScore program;
Compliant with the VOC-emission limits and testing requirements specified in the California Department of Public Health’s 2010 Standard Method for the Testing and Evaluation Chambers, Version 1.1, February 2010;
Compliant with the Collaborative for High Performance Schools California (2014 CA-CHPS) Criteria and listed in the CHPS High Performance Product Database; or
Products certified under UL GREENGUARD Gold (formerly the Greenguard Children’s & Schools Program).
A5.504.4.7.1 Resilient flooring systems, Tier 2. For 100 percent of floor area receiving resilient flooring, install resilient flooring that is:
Certified under the Resilient Floor Covering Institute (RFCI) FloorScore program;
Compliant with the VOC-emission limits and testing requirements specified in the California Department of Public Health’s 2010 Standard Method for the Testing and Evaluation Chambers, Version 1.1, February 2010;
Compliant with the Collaborative for High Performance Schools California (2014 CA-CHPS) Criteria and listed in the CHPS High Performance Product Database; or
Products certified under UL GREENGUARD Gold (formerly the Greenguard Children’s & Schools Program).
Exception: Allowance may be permitted in Tier 2 for up to 5-percent specialty purpose flooring.
A5.504.4.7.2 Verification of compliance. Documentation shall be provided verifying that resilient flooring materials meet the pollutant emission limits.
A5.504.4.8 Thermal insulation, Tier 1. Comply with the following standards:
Chapters 12-13 (Standards for Insulating Material) in Title 24, Part 12, the California Referenced Stan- dards Code,
The VOC-emission limits defined in 2014 CACHPS criteria and listed on its High Performance Products Database.
California Department of Public Health 2010 Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as Specification 01350.)
A5.504.4.8.1 Thermal insulation, Tier 2. Thermal insulation, No-added Formaldehyde. Install thermal
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
nia Energy Code in accordance with Sections A5.507.1.1.1 and A5.507.1.1.2.
A5.507.1.1.1 Lighting. Provide individual task lighting and/or daylighting controls for at least 90 percent of the building occupants.
A5.507.1.1.2 Thermal comfort. Provide individual thermal comfort controls for at least 50 percent of the building occupants.
Occupants shall have control over at least one of the factors of air temperature, radiant temperature, air speed and humidity as described in ASHRAE 55-2004.
Occupants inside 20 feet of the plane of and within 10 feet either side of operable windows can substitute windows to control thermal comfort. The areas of operable window must meet the requirements of Section 120.1 (Requirement for Ventilation) of the California Energy Code.
A5.507.1.2 Multi-occupant spaces. Provide lighting and thermal comfort system controls for all shared multi-occupant spaces, such as classrooms and conference rooms.
A5.507.2 Daylight. Provide daylit spaces as required for toplighting and sidelighting in the California Energy Code. In constructing a design, consider the following:
Use of light shelves and reflective room surfaces to maximize daylight penetrating the rooms
Means to eliminate glare and direct sun light, including through skylights
Use of photosensors to turn off electric lighting when daylight is sufficient
Not using diffuse daylighting glazing where views are desired
A5.507.3 Views. Achieve direct line of sight to the outdoor environment via vision glazing between 2 feet 6 inches and 7 feet 6 inches above finish floor for building occupants in 90 percent of all regularly occupied areas as demonstrated by plan view and section cut diagrams.
A5.507.3.1 Interior office spaces. Entire areas of interior office spaces may be included in the calculation if at least 75 percent of each area has direct line of sight to perimeter vision glazing.
A5.507.3.2 Multi-occupant spaces. Include in the calculation the square footage with direct line of sight to perimeter vision glazing.
Exceptions to Sections A5.507.2 and A5.507.3. Copy/ printing rooms, storage areas, mechanical spaces, restrooms, auditoria and other intermittently or infrequently occupied spaces or spaces where daylight would interfere with use of the space.
A5.507.5 Acoustical control [DSA-SS]. Public Schools and Community Colleges: Unoccupied, furnished classrooms must have a maximum background noise level of no more than 45 dBA LAeq and a maximum (unoccupied, furnished) reverberation of 0.6-second time for classrooms with less than 10,000 cubic feet and a maximum (unoccupied, fur
NONRESIDENTIAL VOLUNTARY MEASURES
insulation which complies with Tier 1 plus does not contain any added formaldehyde.
A5.504.4.8.2 Verification of compliance. Documentation shall be provided verifying that thermal insulation materials meet the pollutant emission limits.
A5.504.4.9 Acoustical ceilings and wall panels. Comply with Chapter 8 in Title 24, Part 2, the California Building Code and with the VOC-emission limits defined in the 2009 CHPS criteria and listed on its High Performance Products Database.
A5.504.4.9.1 Verification of compliance. Documentation shall be provided verifying that acoustical finish materials meet the pollutant emission limits.
Note: Products compliant with CHPS criteria certified under the Greenguard Children & Schools program may also be used.
A5.504.5 Hazardous particulates and chemical pollutants. Minimize and control pollutant entry into buildings and cross-contamination of regularly occupied areas.
A5.504.5.1 Entryway systems. Install permanent entryway systems measuring at least six feet in the primary direction of travel to capture dirt and particulates at entryways directly connected to the outdoors.
Qualifying entryways are those that serve as regular entry points for building users.
Acceptable entryway systems include, but are not limited to, permanently installed grates, grilles or slotted systems that allow cleaning underneath.
Roll-out mats are acceptable only when maintained regularly by janitorial contractors as documented in service contract or by in-house staff as documented by written policies and procedures.
A5.504.5.2 Isolation of pollutant sources. In rooms where activities produce hazardous fumes or chemicals, such as garages, janitorial or laundry rooms and copy or printing rooms, exhaust them and isolate them from their adjacent rooms.
Exhaust each space with no air recirculation in accordance with ASHRAE 62.1, Table 6-4 to create negative pressure with respect to adjacent spaces with the doors to the room closed.
For each space, provide self-closing doors and deck to deck partitions or a hard ceiling.
Install low-noise, vented range hoods for all cooking appliances and in laboratory or other chemical mixing areas.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Green Building Standards Code (Title 24, Part 11)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GREEN BUILDING
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 6 — REFERENCED ORGANIZATIONS AND STANDARDS
- Chapter 7 — INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
- Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
- Appendix A4
▸Appendix A5
Overview- Section A5.101
- Section A5.102
- Section A5.103
- Section A5.104
- Section A5.105
- Section A5.106
- Section A5.201
- Section A5.202
- Section A5.203
- Section A5.211
- Section A5.212
- Section A5.213
- Section A5.301
- Section A5.302
- Section A5.303
- Section A5.304
- Section A5.305
- Section A5.401
- Section A5.402
- Section A5.403
- Section A5.404
- Section A5.405
- Section A5.406
- Section A5.408
- Section A5.409
- Section A5.501
- Section A5.502
- Section A5.504
- Section A5.507
- Section A5.508
- Section A5.601
- Section A5.106
- Section A5.202
- Section A5.203
- Section A5.204
- Section A5.205 — [OSHPD 1 & 4]
- Section A5.207 — [OSHPD 1, 2 & 4]
- Section A5.210 — [OSHPD 1, 2 & 4]
- Section A5.401
- Section A5.407 — [OSHPD 1, 2 & 4]
- Section A5.408
- Section A5.410
- Section A5.504
- Section A5.505 — [OSHPD 1, 2 & 4]