Section A5.303
California Green Building Standards Code (Title 24, Part 11) · 2019 edition · updated 2026-09-12 · California
INDOOR WATER USE
A5.303.2.3.1 Tier 1 – 12-percent savings. A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by 12 percent shall be provided. The reduction shall be based on the maximum allowable water use per plumb
ing fixture and fitting as required by the California Building Standards Code. The 12-percent reduction in potable water use shall be demonstrated by one of the following methods:
Prescriptive method. Each plumbing fixture and fitting shall not exceed the maximum flow rate at greater than or equal to 12-percent reduction as specified in Table A5.303.2.3.1; or
Performance method. A calculation demonstrating a 12-percent reduction in the building “water use baseline” as established in Table A5.303.2.2 shall be provided.
A5.303.2.3.2 Tier 2 – 20-percent savings. A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by 20 percent shall be provided. A calculation demonstrating a 20-percent reduction in the building “water use baseline” as established in Table A5.303.2.2 shall be provided.
A5.303.2.3.3 25-percent savings. A schedule of plumbing fixtures and fixture fittings that will reduce the overall use of potable water within the building by 25 percent shall be provided. A calculation demonstrating a 25-percent reduction in the building “water use baseline” as established in Table A5.303.2.2 shall be provided.
A5.303.2.3.4 Nonpotable water systems for indoor use. Utilizing nonpotable water systems (such as captured rainwater, treated graywater and recycled water) intended to supply water closets, urinals, and other allowed uses, may be used in the calculations demonstrating the 12-, 20- or 25-percent reduction. The nonpotable water systems shall comply with the current edition of the California Plumbing Code.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
NONRESIDENTIAL VOLUNTARY MEASURES
| TABLE A5.303.2.2 WATER USE BASELINE3 | ||||
|---|---|---|---|---|
| FIXTURE TYPE | BASELINE FLOW RATE | DURATION | DAILY USES | OCCUPANTS2 |
| Showerheads | 2.0 gpm @ 80 psi | 5 min. | 1 | X2a |
| Lavatory faucets nonresidential | 0.5 gpm @ 60 psi | .25 min. | 3 | X |
| Kitchen faucets | 1.8 gpm @ 60 psi | 4 min. | 1 | X2b |
| Replacement aerators | 2 gpm @ 60 psi | X | ||
| Wash fountains | 1.8 gpm/20 [rim space (in.) @ 60 psi] | X | ||
| Metering faucets | 0.20 gallons/cycle | .25 min. | 3 | X |
| Metering faucets for wash fountains | 0.20 gallons/cycle/20 [rim space (in.) @ 60 psi] | .25 min. | 1 male1 3 female |
X |
| Gravity tank type water closets | 1.28 gallons/flush | 1 flush | 1 male1 3 female |
X |
| Flushometer tank water closets | 1.28 gallons/flush | 1 flush | 1 male1 3 female |
X |
| Flushometer valve water closets | 1.28 gallons/flush | 1 flush | 1 male1 3 female |
X |
| Electromechanical hydraulic water closets |
1.28 gallons/flush | 1 flush | 1 male1 3 female |
X |
| Urinals | 0.5 or 0.1254 gallons/flush | 1 flush | 2 male | X |
- The daily use number shall be increased to three if urinals are not installed in the room.
- Refer to Table A, Chapter 4, 2019 California Plumbing Code, for occupant load factors. a. Shower use by occupants depends on the type of use of a building or portion of a building, e.g., total occupant load for a health club, but only a fraction of
the occupants in an office building as determined by the anticipated number of users. b. Kitchen faucet use is determined by the occupant load of the area served by the fixture. 3. Use worksheet WS-1 to calculate baseline water use. 4. Floor-mounted urinals @ 0.5 GPF or wall-mounted urinals @ 0.125 GPF.
| TABLE A5.303.2.3.1 FIXTURE FLOW RATES | ||
|---|---|---|
| FIXTURE TYPE | BASELINE FLOW RATE2 | MAXIMUM FLOW RATE AT≥** 12 PERCENT REDUCTION** |
| Showerheads | 2.0 gpm @ 80 psi | 1.8 gpm @ 80 psi |
| Lavatory faucets nonresidential3 | 0.5 gpm @ 60 psi | 0.35 gpm @ 60 psi |
| Kitchen faucets3 | 1.8 gpm @ 60 psi | 1.6 gpm @ 60 psi |
| Wash fountains | 1.8 gallons/cycle/20 [rim space (in.) @ 60 psi] | 1.6 gpm/20 [rim space (in.) @ 60 psi] |
| Metering faucets | 0.20 gallons/cycle | 0.18 gallons/cycle |
| Metering faucets for wash fountains | 0.20 gallons/cycle/20 [rim space (in.) @ 60 psi] | 0.18 gallons/cycle 20 [rim space (in.) @ 60 psi] |
| Gravity tank type water closets | 1.28 gallons/flush | 1.12 gallons/flush1 |
| Flushometer tank water closets | 1.28 gallons/flush | 1.12 gallons/flush1 |
| Flushometer valve water closets | 1.28 gallons/flush | 1.12 gallons/flush1 |
| Electromechanical hydraulic water closets | 1.28 gallons/flush | 1.12 gallons/flush1 |
| Urinals | 0.5 or 0.1254 gallons/flush | 0.44 or 0.11 gallons/flush |
- Includes water closets with an effective flush rate of 1.12 gallons or less when tested per ASME A 112.19.2 and ASME A 112.19.14.
- See Table A5.503.2.2 for additional notes and references.
- Where complying faucets are unavailable, aerators rated at 0.35 gpm or other means may be used to achieve reduction.
- Floor-mounted urinals @ 0.5 GPF or wall-mounted urinals @ 0.125 GPF.
138 2019 CALIFORNIA GREEN BUILDING STANDARDS CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
A5.303.3 Appliances and fixtures for commercial applica- tion. Appliances and fixtures shall meet the following:
Clothes washers shall have a maximum Water Factor (WF) that will reduce the use of water by 10 percent below the California Energy Commissions’ WF standards for commercial clothes washers located in Title 20 of the California Code of Regulations.
Dishwashers shall meet the following water use standards:
a. Residential—ENERGY STAR.
i. Standard Dishwashers – 4.25 gallons per cycle.
ii. Compact Dishwashers – 3.5 gallons per cycle.
b. Commercial—Shall be in accordance with
ENERGY STAR requirements. Refer to Table A5.303.3.
Ice makers shall be air cooled.
Food steamers shall be connectionless or boilerless – and shall consume no more than 2 gallons of water per pan per hour, including condensate water, for batch type steamers, and no more than 5 gallons of water per pan per hour, including condensate water, for cook to order steamers.
The use and installation of water softeners that discharge to the community sewer system may be limited or prohibited by local agencies if certain conditions are met.
Combination ovens shall use a maximum of 1.5 gallons of water per hour per pan, including condensate water.
Commercial pre-rinse spray valves manufactured on or after January 1, 2006 shall function at equal to or less than 1.6 gpm (0.10 L/s) at 60 psi (414 kPa) and
a. Be capable of cleaning 60 plates in an average
time of not more than 30 seconds per plate.
b. Be equipped with an integral automatic shutoff.
c. Operate at static pressure of at least 30 psi (207
kPa) when designed for a flow rate of 1.3 gpm (0.08 L/s) or less.
- Food waste pulping systems shall use no more than 2 gpm of potable water.
8.1. Note: potable water excludes on-site graywater use, such as dishwasher discharge water.
NONRESIDENTIAL VOLUNTARY MEASURES
A5.303.4 Water conserving plumbing fixtures and fittings.
A5.303.4.1 Nonwater supplied urinals. Nonwater supplied urinals are installed in accordance with the Califor- nia Plumbing Code .
Where approved, urinal, hybrids as defined in Chapter 2, shall be considered waterless urinals.
A5.303.5 Dual plumbing. New buildings and facilities shall be dual plumbed for potable and recycled water systems for toilet flushing when recycled water is available as determined by the enforcement authority.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Green Building Standards Code (Title 24, Part 11)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GREEN BUILDING
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 6 — REFERENCED ORGANIZATIONS AND STANDARDS
- Chapter 7 — INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
- Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
- Appendix A4
▸Appendix A5
Overview- Section A5.101
- Section A5.102
- Section A5.103
- Section A5.104
- Section A5.105
- Section A5.106
- Section A5.201
- Section A5.202
- Section A5.203
- Section A5.211
- Section A5.212
- Section A5.213
- Section A5.301
- Section A5.302
- Section A5.303
- Section A5.304
- Section A5.305
- Section A5.401
- Section A5.402
- Section A5.403
- Section A5.404
- Section A5.405
- Section A5.406
- Section A5.408
- Section A5.409
- Section A5.501
- Section A5.502
- Section A5.504
- Section A5.507
- Section A5.508
- Section A5.601
- Section A5.106
- Section A5.202
- Section A5.203
- Section A5.204
- Section A5.205 — [OSHPD 1 & 4]
- Section A5.207 — [OSHPD 1, 2 & 4]
- Section A5.210 — [OSHPD 1, 2 & 4]
- Section A5.401
- Section A5.407 — [OSHPD 1, 2 & 4]
- Section A5.408
- Section A5.410
- Section A5.504
- Section A5.505 — [OSHPD 1, 2 & 4]