Section A6.505 — [OSHPD 1, 2 & 4]—INDOOR MOISTURE CONTROL

2025 California Green Building Standards Code (Title 24, Part 11) · 2025 edition · updated 2026-07-25 · California

A6.505.2 Indoor moisture control. Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1203 and Chapter 14.

APPENDIX A6.1-36 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4]

FEATURE OR MEASURE COMPLIANCE LEVELS NOTES
FEATURE OR MEASURE Mandatory
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
FEATURE OR MEASURE Mandatory
CALGreen
Tier 1 Tier 2 Tier 2
DIVISION A6.1 – PLANNING AND DESIGN
SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development SECTION Site Development
**A6.106.9 Building orientation.**Locate and orient the building as follows:
1. When site and location permit, orient the building with the long sides facing north and
south.
2. Protect the building from thermal loss, drafts and degradation of the building envelope
caused by wind and wind-driven materials such as dust.
DIVISION A6.2 – ENERGY EFFICIENCY
SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures SECTION A6.203 Performance Measures
A6.203.1 Energy performance. [OSHPD 1]
**A6.203.1.1 CALGreen Tier 1. [OSHPD 1]**Buildings must comply with the latest edition of
“Savings By Design, Healthcare Modeling Procedures.”
A.5.203.1.2 CALGreen Tier 2. [OSHPD 1] Buildings must exceed the latest edition of “Savings
By Design, Healthcare Modeling Procedures” by 15 percent.
SECTION A6.204 Prescriptive Measures
**A6.204.1 ENERGY STAR equipment and appliances.**All equipment and appliances provided
by the builder shall be ENERGY STAR labeled if ENERGY STAR is applicable to that equipment
or appliance.
A6.204.4 Commissioning. Building commissioning for all building systems covered by T24,
Part 6, process systems and renewable energy systems shall be included in the design and
construction processes of the building project. Commissioning requirements shall include as
a minimum items listed in Section A6.204.4.
**A6.204.4.1 Owner’s Project Requirements (OPR).**Documented before the design phase of
the project begins the OPR shall include items listed in Section A6.204.4.
**A6.204.4.2 Basis of Design (BOD).**A written explanation of how the design of the building
systems meets the OPR shall be completed at the design phase of the building project and
updated periodically to cover the systems listed in Section A6.204.4.2.
**A6.204.4.3 Commissioning plan.**A commissioning plan describing how the project will be
commissioned shall be started during the design phase of the building project and shall
include as a minimum items listed in Section A6.204.4.3.
A6.204.4.4 Functional performance testingshall demonstrate the correct installation and
operation of each component, system and system-to-system interface in accordance with
the approved plans and specifications.
**A6.204.4.5 Post construction documentation and training.**A systems manual and
systems operations training are required.
**A6.204.4.5.1 Systems manual.**The systems manual shall be delivered to the building
owner and facilities operator and shall include the items listed in Section A6.204.4.5.1.
A6.204.4.5.2 Systems operations training. The training of the appropriate maintenance
staff for each equipment type and/or system shall include as a minimum items listed in
Section A6.204.4.5.2.
**A6.204.4.6 Commissioning report.**A complete report of commissioning process activities
undertaken through the design, construction and postconstruction phases of the building
project shall be completed and provided to the owner.
















**A6.204.6 Building orientation and shading.**Locate orient and shade the building as
required in Section A6.106.11.
SECTION A6.205 Building Envelope
A6.205.1 Fenestration products and exterior doors.
A6.205.1.1 Certification of fenestration products and exterior door other than field-
fabricated.
A6.205.1.2 Installation of field-fabricated fenestration and exterior doors.
A6.205.2 Joints and other openings.
A6.205.3 Installation and roofing products.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4] continued

FEATURE OR MEASURE COMPLIANCE LEVELS NOTES
FEATURE OR MEASURE Mandatory
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
FEATURE OR MEASURE Mandatory
CALGreen
Tier 1 Tier 2 Tier 2
SECTION A6.207 HVAC Design, Equipment and Installation
A6.207.1 Space-conditioning equipment certification by manufacturers.
A6.207.1.1 Efficiency.
A6.207.1.2 Controls for heat pumps with supplementary electric resistance heaters.
A6.207.1.3 Thermostats.
A6.207.1.4 Gas-and oil-fired furnace standby loss controls.








A6.207.2 Space conditioning systems.
A6.207.2.1 Supply air temperature reset controls.
A6.207.2.2 Electric resistance heating.
A6.207.2.3 Heat rejection systems.
A6.207.2.4 Hydronic system measures.
A6.207.2.5 Air distribution system duct leakage sealing.
A6.207.2.6 Variable air volume control for single zone systems.












A6.207.3 Service water-heating systems and equipment.
A6.207.3.1 Certification by manufacturers.
A6.207.3.2 Efficiency.
A6.207.3.3 Installation.






A6.207.4 Natural gas central furnaces, cooking equipment and pool and spa heaters.
Pilot lights prohibited.
A6.207.5 Controls for space-conditioning systems.
A6.207.5.1 Thermostatic controls for each zone.
A6.207.5.2 Criteria for zonal thermostatic controls.
A6.207.5.3 Heat pump controls.
A6.207.5.4 Dampers for air supply and exhaust equipment.
A6.207.5.5 Automatic demand shed controls.










A6.207.6 Pipe insulation.
SECTION A6.209 Lighting
A6.209.1 Lighting control devices, ballasts and luminaires.
A6.209.1.1 All devices: Instructions and calibration.
A6.209.1.2 Indicator lights.
A6.209.1.3 Automatic time switch control devices.
A6.209.1.4 Occupant sensors, motion sensors and vacancy sensors.
A6.209.1.5 Multilevel occupant sensor.
A6.209.1.6 Automatic daylighting control devices.
A6.209.1.7 Interior Photosensors.
A6.209.1.8 Multilevel astronomical time-switch controls.
A6.209.1.9 Outdoor astronomical time-switch controls.
A6.209.1.10 Dimmers.




















A6.209.2 Indoor lighting controls.
A6.209.2.1 Area controls.
A6.209.2.2 Multilevel lighting controls.
A6.209.2.3 Daylight areas.
A6.209.2.3.1 Daylight area.
A6.209.2.3.1.2 Daylight area, primary sidelit.
A6.209.2.3.1.3 Daylight area, secondary sidelit.
A6.209.2.3.1.4 Daylight area, skylit.
A6.209.2.3.2 Controls for luminaires providing general lighting that are in or are
partially in the skylit daylight area and or the primary sidelit daylight area.
A6.209.2.4 Shut-off controls.


















A6.209.3 Outdoor lighting controls and equipment.
A6.209.3.1 Outdoor lighting.
A6.209.3.2 Luminaire cutoff requirements.
A6.209.3.3 Controls for outdoor lighting.






APPENDIX A6.1-38 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4] continued

FEATURE OR MEASURE COMPLIANCE LEVELS NOTES
FEATURE OR MEASURE Mandatory
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
FEATURE OR MEASURE Mandatory
CALGreen
Tier 1 Tier 2 Tier 2
A6.209.4 Outdoor lighting.
A6.209.4.1 Outdoor lighting power trade-offs.
A6.209.4.2 Outdoor lighting power.
A6.209.4.3 Calculation of actual lighting power.
A6.209.4.4 Calculation of allowed lighting power.
A6.209.4.4.1 General hardscape lighting allowance.
A6.209.4.4.2 Additional lighting power allowance for specific applications.
A6.209.4.4.3 Additional lighting power allowance for local ordinance requirements.














A6.209.5 Signs.
A6.209.5.1 Maximum allowed lighting power.
A6.209.5.2 Alternate lighting sources.




A6.209.6 Sign lighting controls.
A6.209.7 Nonresidential lighting control acceptance.
SECTION A6.210 Appliances
A6.210.1 Appliances regulated by the appliance efficiency regulations.
DIVISION A6.4 – MATERIAL CONSERVATION AND RESOURCE EFFICIENCY
SECTION A6.407 Water Resistance and Moisture Management
A6.407.3 Weather Protection.
A6.407.4.1 Moisture control.
A6.407.4.2 Sprinklers.
A6.407.4.3 Entries and openings.






SECTION A6.408 Construction Waste Reduction, Disposal and Recycling
**A6.408.5 Construction waste diversion.**Establish a construction waste management plan
or meet local ordinance, whichever is more stringent.
**A6.408.6 Construction waste.**Recycle and/or salvage for reuse a minimum of 50 percent of
nonhazardous construction and demolition debris or meet local ordinance, whichever is
more stringent.
Exceptions:
1. Excavated soil and land-clearing debris.
2. Alternate waste reduction methods developed by working with local agencies if
diversion or recycle facilities capable of compliance with this item do not exist.
**A6.408.7 Excavated soil and land clearing debris.**100 percent of trees, stumps, rocks and
associated vegetation and soils resulting primarily from land clearing shall be reused or
recycled.
SECTION A6.410 Building Maintenance and Operation
**A6.410.6 Recycling by occupants.**Provide readily accessible areas that serve the entire
building and are identified for the depositing, storage and collection of nonhazardous
materials for recycling.
DIVISION A6.5 – ENVIRONMENTAL QUALITY
SECTION A6.504 Pollutant Control SECTION A6.504 Pollutant Control SECTION A6.504 Pollutant Control SECTION A6.504 Pollutant Control SECTION A6.504 Pollutant Control
**A6.504.4.5.1 No-added formaldehyde.**Use composite wood products approved by the
California Air Resources Board (ARB) as no-added formaldehyde (NAF) based resins or ultra-
low-emitting formaldehyde (ULEF) resins.
Notes:
1. See Title 17, Section93120.3(c) and (d), respectively.
2. Documentation must be provided verifying that materials are certified to meet the
pollutant emission limits. A list of manufacturers and theirNAF and ULEF certified materials
is provided at http://www.arb.ca.gov/toxics/compwood/naf_ulef/listofnaf_ulef.htm.
**A6.504.8 Finish material pollutant control.**Finish materials shall comply with Sections
A6.504.8.1 through A6.504.8.4.
A6.504.8.1 Adhesives, sealants and caulks. Adhesives, sealants and caulks used on the
project shall meet the requirements of the following standards.
1. Adhesives, adhesive bonding primers and adhesive primers, sealants and
sealant primers shall comply with Table A6.504.8.1.
2. Aerosol adhesives shall meet the requirements of_California Code of Regulations,_
Title 17, commencing with Section 94507, http://ccr.oal.ca.gov/.








on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

APPENDIX A6.1VOLUNTARY STANDARDS FOR HEALTH FACILITIES [OSHPD 1, 2 & 4]

NONRESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST [OSHPD 1, 2 and 4] continued

FEATURE OR MEASURE COMPLIANCE LEVELS NOTES
FEATURE OR MEASURE Mandatory
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
VOLUNTARY
CALGreen
FEATURE OR MEASURE Mandatory
CALGreen
Tier 1 Tier 2 Tier 2
**A6.504.8.3 Paints and coatings.**Architectural paints and coatings shall comply with Table
A6.504.8.3.
A6.504.8.3.2 Verification.
**A6.504.8.4 Carpet systems.**All carpet installed in the building interior shall meet the
testing and product requirements of one of the standards listed in Section A6.504.8.3.
**A6.504.8.4.1 Carpet cushion.**All carpet cushion installed in the building interior shall
meet the requirements of the Carpet and Rug Institute Green Label program.
**A6.504.8.4.2 Carpet adhesive.**All carpet adhesive shall meet the requirements of Table
A6.504.8.1.
**A6.504.8.5 Composite wood products.**Hardwood plywood, particleboard and medium
density fiberboard composite wood products used on the interior or exterior of the building
shall meet the requirements for formaldehyde as specified in Table A6.504.8.
**A6.504.8.5.2 Documentation.**Verification of compliance with this section shall be
provided as requested by the enforcing agency. Documentation shall include at least one
of the following.
1. Product certifications and specifications
2. Chain of custody certifications
3. Other methods acceptable to the enforcing agency












**A6.504.4.9 Acoustical ceilings and wall panels.**Comply with Chapter 8 in Title 24, Part 2
and with the VOC-emission limits defined in the CHPS Low-emitting Materials List.
**A6.504.5 Hazardous particulates and chemical pollutants.**Minimize and control pollutant
entry into buildings and cross-contamination of regularly occupied areas.
**A6.504.5.1 Entryway systems.**Install permanent entryway systems measuring at least six
feet in the primary direction of travel to capture dirt and particulates at entryways directly
connected to the outdoors as listed in Items 1 through 3 in Section A6.504.5.1.


**A6.504.9 Environmental tobacco smoke (ETS) control.**Prohibit smoking within 25 feet of
building entries, outdoor air intakes and operable windows and in buildings; or as enforced
by ordinances, regulations or policies of any city, county, city and county, California
Community College, campus of the California State University or campus of the University of
California, whichever are more stringent.
SECTION A6.505 Indoor Moisture Control
**A6.505.2 Indoor moisture control.**Buildings shall meet or exceed the provisions of
California Building Code, CCR, Title 24, Part 2, Section 1203 and Chapter 14.
SECTION A6.507 Environmental Comfort
Reserved

APPENDIX A6.1-40 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

Moisture content of building materials 4.505.3

Indoor Water Use – see Water Use, Indoor Innovative Concepts And Local Environmental Conditions A4.107, A4.108, A4.306, A4.411, A4.509 Installer and Special Inspector Qualifications Chapter 7

Life Cycle Assessment 5.409, A5.409 Materials and system assemblies A5.409.3

Product GWP compliance—prescriptive path 5.409.3, (WS-5), (WS-8), A5.409.3, Table 5.409.3, Table

A5.409.3 Whole building life cycle assessment 5.409.2, (WS-4), (WS7), (WS-9), A5.409.2 of additional impacts A5.409.4 Lighting Appendix A6.1(OSHPD) A5.209.1

Maintenance, Reduced and Enhanced Durability 4.406, A4.406, A5.406

Material Sources A4.405, A5.405 Bio-based materials (from renewable sources) A4.405.4, A5.405.2 Cement and concrete A5.405.5 Certified wood components A5.405.2.1 Concrete floors A4.405.2 Prefinished building materials A4.405.1 Recycled content A4.405.3, A5.405.4 Regional Materials A5.405.1 Reused materials A5.405.3

Model Water-Efficient Landscape Ordinance (MWELO) 4.304.1 Moisture Control, Indoor – see Indoor Moisture Control

Nonresidential Additions

and Alterations 301.3

Outdoor Air Quality 5.508, A5.508 Ozone depletion and greenhouse gas reductions 5.508.1, A5.508.1.3,

A5.508.1.4

Outdoor Water Use – see Water Use, Outdoor

Pollutant Control 4.504, 5.504, A4.504,

A5.504 Acoustical ceilings and wall panels 5.504.4.8

Adhesives, sealants and caulks Tables 4.504.1 & 4.504.2, 4.504.2.1, 5.504.4.1, Tables 5.504.4.1 & 5.504.4.2, Appendix A6.1 (OSHPD) Tables A5.504.8.1 & A5.504.8.2 Aerosol paints and coatings 4.504.2.3, 5.504.4.3.1, Appendix A6.1 (OSHPD), A5.504.8.3.1

Carpet systems 4.504.3, 5.504.4.4, Appendix A6.1 (OSHPD), A5.504.8.4 Composite wood products 4.504.5, Table 4.504.5, 5.504.4.5, Table 5.504.4.5, A4.504.1, Appendix A6.1 (OSHPD)A5.504.4.5.1, A5.504.8.5,

Additions and Alterations See Non-

residential Additions and Alterations Administration Chapter 1 Air Quality and Exhaust, Indoor – see Indoor Air Quality and Exhaust Appliances A4.303.3, A5.303.3, Appendix A6.1 (OSHPD) A5.207 Application Checklists A4.602, A5.602, Appendix A6.1 (OSHPD)

Bird Friendly Building Design A5.107 Building Envelope A4.204, Appendix A6.1 (OSHPD) A5.205 Building orientation Appendix A6.1(OSHPD), A5.204.6 Fenestration products and exterior doors Appendix A6.1(OSHPD), A5.205.1 Insulation and roofing products Appendix A6.1(OSHPD), A5.205.3 Life cycle assessment 5.409, A5.409 Building Maintenance and Operation 4.410, 5.410 Commissioning 5.410.2, A5.410.3 Sample compliance forms and templates Chapter 8 Operation and maintenance manual 4.410.1, 5.410.4.5 Recycling by occupants Appendix A6.1(OSHPD), A5.410, 5.410.1 Testing and adjusting 5.410.4

A6.1(OSHPD), A5.205.1 Insulation and roofing products Appendix A6.1(OSHPD), A5.205.3 Life cycle assessment 5.409, A5.409 Building Maintenance and Operation 4.410, 5.410 Commissioning 5.410.2, A5.410.3 Sample compliance forms and templates Chapter 8 Operation and maintenance manual 4.410.1, 5.410.4.5 Recycling by occupants Appendix A6.1(OSHPD), A5.410, 5.410.1 Testing and adjusting 5.410.4

Commissioning Commissioning Appendix A6.1 (OSHPD) A5.204, 5.410.2 Commissioning plan 5.410.2.3 Commissioning report 5.410.2.6 Construction Waste Reduction, Disposal and Recycling Appendix A6.1 (OSHPD) A5.408, 4.408, 5.408 Construction waste management 4.408.1, 5.408.1 Construction waste management plan 4.408.2, 5.408.1.1 Enhanced construction waste reduction

A4.408.1, A5.408.3.1 Excavated soil and land clearing debris 5.408.3

Deconstruction and Reuse of Existing Materials 4.105, A4.105 Reuse of materials A4.105.2

Deconstruction and Reuse of Existing Structures 5.105, A5.105 (Reserved) 4.105 Reuse of existing building 5.105.2, Chapter 8 (WS-3), A5.105.2, Chapter 8 (WS-6) Definitions Chapter 2 Durability, Enhanced and Reduced Maintenance 4.406, A4.406, A5.406 Choice of materials A5.406.1

Electric Vehicle (EV) Charging 4.106.4, 5.106.5.3, 5.106.5.5, 5.106.5.6, A4.106.8,

A5.106.5.3

INDEX

Alterations and additions 4.106.4.3, 5.106.5.4, 5.106.5.6.4 Electric vehicle charging stations (EVCS) 5.106.5.3.2, 5.106.5.6.2 EVCS alternative compliance 5.106.5.6.3 EVCS signage 5.106.5.3.5 Power allocation method 5.106.5.3.6, Table 5.106.5.3.6, A5.106.5.3.2 Tier 1, Table 5.106.5.3.2 Tier 1, A5.106.5.3.4 Tier 2, Table 5.106.5.3.4 Tier 2 Elevators, Escalators and Other Equipment A5.212 Energy Efficiency 4.201.1, A4.203.1, A4.204.1 Commissioning Appendix A6.1 (OSHPD) A5.204.4

ENERGY STAR equipment and appliances Appendix A6.1(OSHPD), A4.403.3, A5.204.1 General 4.201, 5.201, A5.201 Performance approach A4.203, A5.203 Outdoor lighting A5.203.1.1.1 Prescriptive approach Appendix A6.1(OSHPD), 203.3.1.2 Alterations to existing buildings A4.204.1, A4.204.1.2, A5.204.1,

A5.204.1.1 Energy Efficient Steel Framing A5.213 Environmental Comfort 4.507, 5.507,

A5.507

Acoustical control A4.507, A5.507.5 Daylight A5.507.2 Lighting and thermal comfort controls A5.507.1

Views A5.507.3

Fireplaces 4.503, 5.503 Foundation Systems A4.403 Frost protected foundation systems A4.403.1

Reduction in cement use A4.403.2 Framing, Energy Efficient Steel A5.213 Framing Techniques, Efficient A4.404, A5.404 Building systems A4.404.3 Lumber size A4.404.1

Pre-cut materials and details A4.404.4 Wood framing A5.404.1

Green Building Chapter 3 Mixed occupancy buildings 302 Phased projects 303 Voluntary tiers 304, 305 Voluntary measures 306

HVAC Design, Equipment and Installation Appendix A6.1 (OSHPD), A5.207

Indoor Air Quality And Exhaust 4.506, 5.506 Bathroom exhaust fans 4.506.1 Carbon dioxide monitoring 5.506.2 Carbon dioxide (CO 2 ) monitoring in classrooms 5.506.3

Filters 5.504.5, A4.506.1 Outside air delivery 5.506.1 Indoor Moisture Control 4.505, 5.505.1 Concrete slab foundations 4.505.2

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

INDEX

Appendix A6.1 (OSHPD), Table A5.504.8.5 Covering of duct openings and protection of mechanical equipment during construction 4.504.1, 5.504.3 Environmental tobacco smoke control 5.504.7, Appendix A6.1 (OSHPD), A5.504.9 Finish material pollutant control 4.504.2, 5.504.4 Hazardous particulates and chemical pollutants A5.504.5 Indoor air quality (IAQ) during construction 5.504.1, A5.504.1 IAQ Post-construction A5.504.2 Paints and coatings 4.504.2.2, 5.504.4.3 Resilient flooring systems 4.504.4, 5.504.4.6, A4.504.2, A5.504.4.7 Thermal insulation 5.504.4.7, A4.504.3,

A5.504.4.8

Product GWP Limits Table 5.409.3

Referenced Organizations and Standards Chapter 6 Renewable Energy A5.211

Site Development 4.106, 5.106, A4,106, A5.106 Bicycle parking and changing rooms 5.106.4, A5.106.4.3, Table A5.106.4.3 Bird friendly building design A5.107 Building orientation Appendix A6.1 (OSHPD), A5.106.9 Designated parking for clean air vehicles A5.106.5.1 Exterior wall shading A5.106.7 Grading and paving 4.106.3, 5.106.10 Heat island effect – cool roof Tables A4.106.5(1) – (4), A5.106.11.2, Table

A5.106.11.2 Heat island effect – hardscape alternatives A5.106.11, A5.106.11.1 Landscape design A4.106.3 Light pollution reduction 5.106.8 Low impact development A5.106.3 Reduce parking capacity A5.106.6 Shade trees 5.106.12, A5.106.11.3 Soil analysis and protection A4.106.2 Storm water management A5.106.2 Water permeable surfaces A4.106.4 Site Preservation A4.104, A5.104 Reduce development footprint and optimize open space A5.104.1 Site Selection A4.103, A5.103 Brownfield, greyfield or infill site development A5.103.2 Community connectivity A4.103.2, A5.103.1

Voluntary Measures 301.1, 306 Voluntary Tiers 304, 305, 306, A4.601, A5.601

Water Resistance and Moisture Management 5.407, 5.505, A4.407, Appendix A6.1 (OSHPD) A5.407 Moisture control 4.505, 5.407.2, 5.505, Appendix A6.1 (OSHPD) A5.407.9, Appendix A6.1 (OSHPD) A5.505.2 Weather protection 5.407.1, A5.407.3

Water Reuse Systems A4.305 Graywater A4.305.1, A5.304.8 Recycled water for landscape irrigation A4.305.3 Recycled water piping A4.305.2 Water Use, Indoor 4.303, 5.303, A4.303, A5.203

Appliances A4.303.3, A5.303.3, Appendix A6.1 (OSHPD) A5.210 Dual plumbing A5.303.5 Fixture flow rates 4.303.1, Table A5.303.2.3.1, 5.303.2.3.1, A4.303 Kitchen faucets and dishwashers

A4.303.1

Meters 4.303.2, 5.303.1 Multiple showerheads serving one shower 4.303.1.3.2, 5.303.3.3.2 Nonwater urinals and waterless toilets

A4.303.4, A5.303.4.1 Plumbing fixtures and fittings 4.303.1, 4.303.2, 5.303.3, 5.303.6 Tier 1, 12% savings; Tier 2, 20% savings; and 25% savings A5.303.2.1, A5.303.2.3.1, A5.303.2.3.2,

A5.303.2.3.3

Wastewater reduction 5.303.4

Water Use Baseline Table A5.303.2.2

Water Use, Outdoor 4.304, 5.304, A4.304, A5.304

Graywater irrigation system A5.304.8 Low-water consumption irrigation system A4.304.1 Outdoor potable water meters A4.304.3, A5.304.2 Potable water elimination A4.304.2 Previously developed sites A5.304.7 Rainwater or stormwater collection systems A4.304.1 Restoration of areas disturbed by construction A5.304.6 Worksheet Baseline Water Use Chapter 8, (WS-1) 12%, 20% or 25% Reduction Water Use Calculation Table Chapter 8, (WS-2) Building Reuse Chapter 8, (WS-3) Whole Building Life Cycle Assessment 5.409.2, Chapter 8, (WS-4) Product GWP Compliance— Prescriptive Path 5.409.3, Chapter 8, (WS-5) Building Reuse Tier 1 and Tier 2 Chapter 8, (WS-6) Whole Building Life Cycle Assessment A5.409.2, Chapter 8, (WS-7) Product GWP Compliance— Prescriptive Path A5.409.3, Chapter 8, (WS-8) Whole Building Life Cycle Assessment 5.409.2, A5.409.2, Chapter 8, (WS-9)

INDEX-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

HISTORY NOTE APPENDIX

California Code of Regulations, Title 24, Part 11

HISTORY:

For prior history, see the History Note Appendix to the California Green Building Standards Code, 2022 Edition, effective January 1, 2023.

  1. (BSC 03/24, HCD 04/24, DSA-SS 03/24, CEC 02/24)—Repeal the 2022 adoption of the California Green Building Standards Code, CCR Title 24, Part 11 and adopt the 2025 California Green Building Standards Code . Approved by the California Building Standards Commission on December 17, 2024, filed with the Secretary of State on January 10, 2025, and effective on January 1, 2026.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Green Building Standards Code (Title 24, Part 11)
2025 California Green Building Standards Code (Title 24, Part 11)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GREEN BUILDING
  4. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  5. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  6. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  7. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  8. Chapter 4 — RESIDENTIAL MANDATORY MEASURES
  9. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  10. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  11. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  12. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  13. Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
  14. Chapter 6 — REFERENCED ORGANIZATIONS AND STANDARDS
  15. Chapter 7 — INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
  16. Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
    Overview
    1. Section A4.101 — GENERAL
    2. Section A4.102 — DEFINITIONS
    3. Section A4.103 — SITE SELECTION
    4. Section A4.104 — SITE PRESERVATION
    5. Section A4.105 — DECONSTRUCTION AND REUSE OF EXISTING MATERIALS
    6. Section A4.106 — SITE DEVELOPMENT
    7. Section A4.107
    8. Section A4.108 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    9. Section A4.201 — GENERAL
    10. Section A4.202 — DEFINITIONS
    11. Section A4.203 — PERFORMANCE APPROACH FOR NEWLY CONSTRUCTED BU…
    12. Section A4.204 — REQUIREMENTS FOR ALTERATIONS TO EXISTING BUIL…
    13. Section A4.301 — GENERAL
    14. Section A4.302 — DEFINITIONS
    15. Section A4.303 — INDOOR WATER USE
    16. Section A4.304 — OUTDOOR WATER USE
    17. Section A4.305 — WATER REUSE SYSTEMS
    18. Section A4.306 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    19. Section A4.401 — GENERAL
    20. Section A4.402 — DEFINITIONS
    21. Section A4.403 — FOUNDATION SYSTEMS
    22. Section A4.404 — EFFICIENT FRAMING TECHNIQUES
    23. Section A4.405 — MATERIAL SOURCES
    24. Section A4.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
    25. Section A4.407 — WATER RESISTANCE AND MOISTURE MANAGEMENT
    26. Section A4.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    27. Section A4.409 — LIFE CYCLE ASSESSMENT
    28. Section A4.410 — BUILDING MAINTENANCE AND OPERATION
    29. Section A4.411 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    30. Section A4.501 — GENERAL
    31. Section A4.502 — DEFINITIONS
    32. Section A4.503 — FIREPLACES
    33. Section A4.504 — POLLUTANT CONTROL
    34. Section A4.505 — INTERIOR MOISTURE CONTROL
    35. Section A4.506 — INDOOR AIR QUALITY AND EXHAUST
    36. Section A4.507 — ENVIRONMENTAL COMFORT
    37. Section A4.508 — OUTDOOR AIR QUALITY
    38. Section A4.509 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
    39. Section A4.601 — GENERAL
    40. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST
    41. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    42. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    43. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    44. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    45. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    46. Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
    47. Section A5.101 — GENERAL
    48. Section A5.102 — DEFINITIONS
    49. Section A5.103 — SITE SELECTION
    50. Section A5.104 — SITE PRESERVATION
    51. Section A5.105 — DECONSTRUCTION AND REUSE OF EXISTING STRUCTURES
    52. Section A5.106 — SITE DEVELOPMENT
    53. Section A5.107 — BIRD-FRIENDLY BUILDING DESIGN
    54. Section A5.201 — GENERAL
    55. Section A5.202 — DEFINITIONS
    56. Section A5.203 — PERFORMANCE APPROACH
    57. Section A5.204 — MANDATORY REQUIREMENTS FOR ALTERATIONS TO EXI…
    58. Section A5.211 — RESERVED
    59. Section A5.212 — ELEVATORS, ESCALATORS AND OTHER EQUIPMENT
    60. Section A5.213 — ENERGY EFFICIENT FRAMING
    61. Section A5.301 — GENERAL
    62. Section A5.302 — DEFINITIONS
    63. Section A5.303 — INDOOR WATER USE
    64. Section A5.304 — OUTDOOR WATER USE
    65. Section A5.305 — WATER REUSE
    66. Section A5.401 — GENERAL
    67. Section A5.402 — DEFINITIONS
    68. Section A5.403 — FOUNDATION SYSTEMS
    69. Section A5.404 — EFFICIENT FRAMING TECHNIQUES
    70. Section A5.405 — MATERIAL SOURCES
    71. Section A5.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
    72. Section A5.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    73. Section A5.409 — LIFE CYCLE ASSESSMENT
    74. Section A5.501 — GENERAL
    75. Section A5.502 — DEFINITIONS
    76. Section A5.504 — POLLUTANT CONTROL
    77. Section A5.507 — ENVIRONMENTAL COMFORT
    78. Section A5.508 — OUTDOOR AIR QUALITY
    79. Section A6.106 — SITE DEVELOPMENT
    80. Section A6.202 — DEFINITIONS
    81. Section A6.203 — PERFORMANCE APPROACH
    82. Section A6.204 — PRESCRIPTIVE APPROACH
    83. Section A6.205 — [OSHPD 1 & 4]—BUILDING ENVELOPE
    84. Section A6.207 — [OSHPD 1, 2 & 4]—HVAC DESIGN, EQUIPMENT AND I…
    85. Section A6.210 — [OSHPD 1, 2 & 4]—APPLIANCES
    86. Section A6.401 — GENERAL
    87. Section A6.407 — [OSHPD 1, 2 & 4]—WATER RESISTANCE AND MOISTUR…
    88. Section A6.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
    89. Section A6.410 — BUILDING MAINTENANCE AND OPERATION
    90. Section A6.504 — POLLUTANT CONTROL
    91. Section A6.505 — [OSHPD 1, 2 & 4]—INDOOR MOISTURE CONTROL

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.