Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Section A4.204 — REQUIREMENTS FOR ALTERATIONS TO EXISTING BUILDINGS
2025 California Green Building Standards Code (Title 24, Part 11) · 2025 edition · updated 2026-07-25 · California
A4.204.1 Energy efficiency. Alterations to existing residential buildings shall comply with Sections A4.204.1.1 and A4.204.1.2.
A4.204.1.1 Altered space-conditioning system serving existing single-family dwelling units – mechanical cooling. When a space-conditioning system serving an existing single-family dwelling unit is altered in Climate Zones 1 through 14 and 16 by installation or replacement of an air conditioner, the altered system shall comply with either a or b below in addition to the requirements for installation specified by Title 24, Part 6, Sections 150.2(b)1E and 150.2(b)1F: a. A heat pump shall be the primary heating source and sized according to the system selection requirements specified by Title 24, Part 6 of Section 150.0(h)5. Supplemental heating may be provided by an existing gas furnace or existing electric resistance heating; or b. An air conditioner shall meet the following requirements: i. R-8 duct insulation for ducts located in unconditioned space; and ii. The duct system measured air leakage shall be equal to or less than 5 percent of the system air handler airflow as confirmed through field verification and diagnostic testing, per the requirements in Title 24, Part 6, Reference Residential Appendix Section RA3.1.4.3.1; and iii. Demonstrate, in every control mode, airflow greater than or equal to 400 CFM per ton of nominal cooling capacity through the return grilles, and an air-handling unit fan efficacy less than or equal to 0.35 W/CFM. The airflow rate and fan efficacy requirements in this section shall be confirmed through field verification and diagnostic testing, following the procedures outlined in Title 24, Part 6, Reference Residential Appendix RA3.3; and iv. In all climate zones refrigerant charge verification requirements shall meet the requirements in Title 24, Part 6 Section 150.2(b)1Fiib; and v. Vented attics shall have insulation installed to achieve a U -factor of 0.020 or insulation installed at the ceiling level shall result in an insulated thermal resistance of R-49 or greater for the insulation alone; and vi. Air seal all accessible areas of the ceiling plane between the attic and the conditioned space in accordance with the requirements in Title 24, Part 6 Section 150.2(b)1Jii.
Exception 1 to Section A4.204.1.1: Where the capacity of the existing main electrical service panel is insufficient to supply the electrical capacity of a heat pump and where the existing main electrical service panel is sufficient to supply a new or replacement air conditioner, as calculated according to the requirements of California Electrical Code Article 220.83 or 220.87. Documentation of electrical load calculations in accordance with Article 220 must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.
e the existing main electrical service panel is sufficient to supply a new or replacement air conditioner, as calculated according to the requirements of California Electrical Code Article 220.83 or 220.87. Documentation of electrical load calculations in accordance with Article 220 must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.
Exception 2 to Section A4.204.1.1: Where the required capacity of a heat pump to meet the system selection requirements of Section 150.0(h)5 is greater than or equal to 12,000 Btu/h more than the required capacity of an air conditioner to meet the design cooling load. Documentation of heating and cooling load calculations in accordance with 150.0(h) must be submitted to the enforcement agency prior to permitting for both the heat pump and proposed air conditioner.
A4.204.1.2 Altered pool and/or spa heating for existing multifamily buildings. Alteration of an existing multifamily pool and/or spa heating system shall meet the following:
Heating source sizing. Heating systems or equipment for pools or spas shall meet one of the sizing requirements of Items 1 through 5 below:
- A solar pool heating system with a solar collector surface area that is equivalent to 65 percent or greater of the surface areas of the pool or spa or a combination of both respectively; or
- A heat pump pool heater as the primary heating system that meets the sizing requirements of Reference Joint Appendix JA16.3. The control for the heat pump pool heater shall meet the requirements specified in Title 24, Part 6, Section 110.4(d). The supplementary heater can be of any energy source; or
- A heating system that derives at least 60 percent of the annual heating energy from on-site renewable energy or on-site recovered energy; or
- A combination of a solar pool heating system and heat pump pool heater without any additional supplementary heater; or
- A pool heating system determined by the Energy Commission Executive Director to use no more energy than the systems specified in Item 1, 2, 3, or 4 above.
Exception 1 to A4.204.1.2: Portable electric spas compliant with 20 CCR, Section 1605.3(g)(7) of the Appliance Efficiency Regulations.
Exception 2 to A4.204.1.2: A pool or spa that is heated solely by a solar pool heating system without any supplementary heater.
Exception 3 to A4.204.1.2: An existing building with inadequate Solar Access Roof Area (SARA) as specified in Title 24, Part 6, Section 170.2(f) for a solar pool heating system to be installed.
Exception 4 to A4.204.1.2: Heating systems which are used exclusively for permanent spa applications in existing buildings with gas availability.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25402, 25402.1, 25402.4 and 25402.8, Public Resources Code.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A4-12 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
A4 RESIDENTIAL VOLUNTARY MEASURES
DIVISION A4.3 – WATER EFFICIENCY AND CONSERVATION
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Green Building Standards Code (Title 24, Part 11)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — GREEN BUILDING
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 4 — RESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 5 — NONRESIDENTIAL MANDATORY MEASURES
- Chapter 6 — REFERENCED ORGANIZATIONS AND STANDARDS
- Chapter 7 — INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
-
▸ Chapter 8 — COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Overview- Section A4.101 — GENERAL
- Section A4.102 — DEFINITIONS
- Section A4.103 — SITE SELECTION
- Section A4.104 — SITE PRESERVATION
- Section A4.105 — DECONSTRUCTION AND REUSE OF EXISTING MATERIALS
- Section A4.106 — SITE DEVELOPMENT
- Section A4.107
- Section A4.108 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
- Section A4.201 — GENERAL
- Section A4.202 — DEFINITIONS
- Section A4.203 — PERFORMANCE APPROACH FOR NEWLY CONSTRUCTED BU…
- Section A4.204 — REQUIREMENTS FOR ALTERATIONS TO EXISTING BUIL…
- Section A4.301 — GENERAL
- Section A4.302 — DEFINITIONS
- Section A4.303 — INDOOR WATER USE
- Section A4.304 — OUTDOOR WATER USE
- Section A4.305 — WATER REUSE SYSTEMS
- Section A4.306 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
- Section A4.401 — GENERAL
- Section A4.402 — DEFINITIONS
- Section A4.403 — FOUNDATION SYSTEMS
- Section A4.404 — EFFICIENT FRAMING TECHNIQUES
- Section A4.405 — MATERIAL SOURCES
- Section A4.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
- Section A4.407 — WATER RESISTANCE AND MOISTURE MANAGEMENT
- Section A4.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
- Section A4.409 — LIFE CYCLE ASSESSMENT
- Section A4.410 — BUILDING MAINTENANCE AND OPERATION
- Section A4.411 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
- Section A4.501 — GENERAL
- Section A4.502 — DEFINITIONS
- Section A4.503 — FIREPLACES
- Section A4.504 — POLLUTANT CONTROL
- Section A4.505 — INTERIOR MOISTURE CONTROL
- Section A4.506 — INDOOR AIR QUALITY AND EXHAUST
- Section A4.507 — ENVIRONMENTAL COMFORT
- Section A4.508 — OUTDOOR AIR QUALITY
- Section A4.509 — INNOVATIVE CONCEPTS AND LOCAL ENVIRONMENTAL C…
- Section A4.601 — GENERAL
- Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST
- Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
- Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
- Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
- Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
- Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
- Section A4.602 — RESIDENTIAL OCCUPANCIES APPLICATION CHECKLIST…
- Section A5.101 — GENERAL
- Section A5.102 — DEFINITIONS
- Section A5.103 — SITE SELECTION
- Section A5.104 — SITE PRESERVATION
- Section A5.105 — DECONSTRUCTION AND REUSE OF EXISTING STRUCTURES
- Section A5.106 — SITE DEVELOPMENT
- Section A5.107 — BIRD-FRIENDLY BUILDING DESIGN
- Section A5.201 — GENERAL
- Section A5.202 — DEFINITIONS
- Section A5.203 — PERFORMANCE APPROACH
- Section A5.204 — MANDATORY REQUIREMENTS FOR ALTERATIONS TO EXI…
- Section A5.211 — RESERVED
- Section A5.212 — ELEVATORS, ESCALATORS AND OTHER EQUIPMENT
- Section A5.213 — ENERGY EFFICIENT FRAMING
- Section A5.301 — GENERAL
- Section A5.302 — DEFINITIONS
- Section A5.303 — INDOOR WATER USE
- Section A5.304 — OUTDOOR WATER USE
- Section A5.305 — WATER REUSE
- Section A5.401 — GENERAL
- Section A5.402 — DEFINITIONS
- Section A5.403 — FOUNDATION SYSTEMS
- Section A5.404 — EFFICIENT FRAMING TECHNIQUES
- Section A5.405 — MATERIAL SOURCES
- Section A5.406 — ENHANCED DURABILITY AND REDUCED MAINTENANCE
- Section A5.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
- Section A5.409 — LIFE CYCLE ASSESSMENT
- Section A5.501 — GENERAL
- Section A5.502 — DEFINITIONS
- Section A5.504 — POLLUTANT CONTROL
- Section A5.507 — ENVIRONMENTAL COMFORT
- Section A5.508 — OUTDOOR AIR QUALITY
- Section A6.106 — SITE DEVELOPMENT
- Section A6.202 — DEFINITIONS
- Section A6.203 — PERFORMANCE APPROACH
- Section A6.204 — PRESCRIPTIVE APPROACH
- Section A6.205 — [OSHPD 1 & 4]—BUILDING ENVELOPE
- Section A6.207 — [OSHPD 1, 2 & 4]—HVAC DESIGN, EQUIPMENT AND I…
- Section A6.210 — [OSHPD 1, 2 & 4]—APPLIANCES
- Section A6.401 — GENERAL
- Section A6.407 — [OSHPD 1, 2 & 4]—WATER RESISTANCE AND MOISTUR…
- Section A6.408 — CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RE…
- Section A6.410 — BUILDING MAINTENANCE AND OPERATION
- Section A6.504 — POLLUTANT CONTROL
- Section A6.505 — [OSHPD 1, 2 & 4]—INDOOR MOISTURE CONTROL