913.1 General. Where provided, fire pumps shall be installed¶
in accordance with this section and NFPA 20.
913.2 Protection against interruption of service. The fire¶
pump, driver and controller shall be protected in accordance with NFPA 20 against possible interruption of service through damage caused by explosion, fire, flood, earthquake, rodents, insects, windstorm, freezing, vandalism and other adverse conditions.
913.2.1 Protection of fire pump rooms. Rooms where fire pumps are located shall be separated from all other areas of the building in accordance with Section 913.2.1 of the California Building Code . 913.2.2 Circuits supplying fire pumps. Cables used for survivability of circuits supplying fire pumps shall be protected using one of the following methods:
- Cables used for survivability of required critical circuits shall be listed in accordance with UL 2196 and shall have a fire-resistance rating of not less than 1 hour.
- Electrical circuit protective systems shall have a fire-restistance rating of not less than 1 hour. Elec
trical circuit protective systems shall be installed in accordance with their listing requirements. 3. Construction having a fire-resistance rating of not less than 1 hour.
913.3 Temperature of pump room. Suitable means shall¶
be provided for maintaining the temperature of a pump room or pump house, where required, above 40°F (5°C).
913.3.1 Engine manufacturer’s recommendation. Temperature of the pump room, pump house or area where engines are installed shall never be less than the minimum recommended by the engine manufacturer. The engine manufacturer’s recommendations for oil heaters shall be followed.
913.4 Valve supervision. Where provided, the fire pump¶
suction, discharge and bypass valves, and isolation valves on the backflow prevention device or assembly shall be supervised open by one of the following methods:
- Central-station, proprietary or remote-station signaling service.
- Local signaling service that will cause the sounding of an audible signal at a constantly attended location.
- Locking valves open.
- Sealing of valves and approved weekly recorded inspection where valves are located within fenced enclosures under the control of the owner. 913.4.1 Test outlet valve supervision. Fire pump test outlet valves shall be supervised in the closed position.
913.5 Testing and maintenance. Fire pumps shall be¶
inspected, tested and maintained in accordance with the requirements of this section and California Code of Regula- tions, Title 19, Division 1, Chapter 5 . Records of inspection, testing and maintenance shall be maintained.
913.5.1 Acceptance test. Acceptance testing shall be done in accordance with the requirements of NFPA 20. 913.5.2 Generator sets. Engine generator sets supplying emergency or standby power to fire pump assemblies shall be periodically tested in accordance with NFPA 110. Records of testing shall be maintained. 913.5.3 Transfer switches. Automatic transfer switches shall be periodically tested in accordance with NFPA 110. Records of testing shall be maintained. 913.5.4 Pump room environmental conditions. Tests of pump room environmental conditions, including heating, ventilation and illumination, shall be made to ensure proper manual or automatic operation of the associated equipment.
913.6 Fire pumps in high-rise buildings. Engine-driven¶
fire pumps and electric drive fire pumps supplied by genera- tors shall both be provided with an on-premises fuel supply, suf- ficient for not less than 8-hour full-demand operation at 100 percent of the rated pump capacity in addition to all other required supply demands in accordance with Sections 9.6 and 11.4.2 of NFPA 20 and this section. (Also see Section 604.2.14.1.)
214 2019 CALIFORNIA FIRE CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.