911.1 General. Explosion control shall be provided in the

following locations:

  1. Where a structure, room or space is occupied for purposes involving explosion hazards as identified in Table 911.1.

  2. Where quantities of hazardous materials specified in Table 911.1 exceed the maximum allowable quantities in Table 5003.1.1(1).

Such areas shall be provided with explosion (deflagration) venting, explosion (deflagration) prevention systems or barricades in accordance with this section and NFPA 69, or NFPA 495 as applicable. Deflagration venting shall not be utilized as a means to protect buildings from detonation hazards.

TABLE 911.1 EXPLOSION CONTROL REQUIREMENTS f

MATERIAL CLASS EXPLOSION CONTROL METHODS
MATERIAL CLASS Barricade construction Explosion (deflagration) venting or explosion
(deflagration) prevention systems
** Hazard Category** ** Hazard Category** ** Hazard Category** ** Hazard Category**
Combustible dustsa — Not required Required
Cryogenic fluids Flammable Not required Required
Explosives Division 1.1
Division 1.2
Division 1.3
Division 1.4
Division 1.5
Division 1.6
Required
Required
Not required
Not required
Required
Required
Not required
Not required
Required
Required
Not required
Not required
Flammable gas Gaseous
Liquefied
Not required
Not required
Required
Required
Flammable liquids IAb
IBc
Not required
Not required
Required
Required
Organic peroxides Unclassified detonable
I
Required
Required
Not permitted
Not permitted
Oxidizer liquids and solids 4 Required Not permitted
Pyrophoric Gases Not required Required
Unstable (reactive) 4
3 detonable
3 nondetonable
Required
Required
Not required
Not permitted
Not permitted
Required
Water-reactive liquids and solids 3
2e
Not required
Not required
Required
Required
** Special Uses** ** Special Uses** ** Special Uses** ** Special Uses**
Acetylene generator rooms — Not required Required
Grain processing — Not required Required
Liquefied petroleum gas distribution facilities — Not required Required
Where explosion hazards existd Detonation
Deflagration
Required
Not required
Not permitted
Required

a. Combustible dusts that are generated during manufacturing or processing. See definition of “Combustible dust” in Chapter 2. b. Storage or use. c. In open use or dispensing. d. Rooms containing dispensing and use of hazardous materials where an explosive environment can occur because of the characteristics or nature of the

hazardous materials or as a result of the dispensing or use process. e. A method of explosion control shall be provided where Class 2 water-reactive materials can form potentially explosive mixtures. f. Explosion venting is not required for Group H-5 Fabrication Areas complying with Chapter 27 and the California Building Code .

212 2019 CALIFORNIA FIRE CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

Exceptions & meaning →

911.2 Required deflagration venting. Areas that are

required to be provided with deflagration venting shall comply with the following:

  1. Walls, ceilings and roofs exposing surrounding areas shall be designed to resist a minimum internal pressure of 100 pounds per square foot (psf) (4788 Pa). The minimum internal design pressure shall be not less than five times the maximum internal relief pressure specified in Item 5 of this section.

  2. Deflagration venting shall be provided only in exterior walls and roofs.

Exception: Where sufficient exterior wall and roof venting cannot be provided because of inadequate exterior wall or roof area, deflagration venting shall be allowed by specially designed shafts vented to the exterior of the building.

  1. Deflagration venting shall be designed to prevent unacceptable structural damage. Where relieving a deflagration, vent closures shall not produce projectiles of sufficient velocity and mass to cause life threatening injuries to the occupants or other persons on the property or adjacent public ways.

  2. The aggregate clear area of vents and venting devices shall be governed by the pressure resistance of the construction assemblies specified in Item 1 of this section and the maximum internal pressure allowed by Item 5 of this section.

  3. Vents shall be designed to withstand loads in accordance with the California Building Code . Vents shall consist of any one or any combination of the following to relieve at a maximum internal pressure of 20 pounds per square foot (958 Pa), but not less than the loads required by the California Building Code :

5.1. Exterior walls designed to release outward.

5.2. Hatch covers.

5.3. Outward swinging doors.

5.4. Roofs designed to uplift.

5.5. Venting devices listed for the purpose.

  1. Vents designed to release from the exterior walls or roofs of the building when venting a deflagration shall discharge directly to the exterior of the building where an unoccupied space not less than 50 feet (15 240 mm) in width is provided between the exterior walls of the building and the lot line.

Exception: Vents complying with Item 7 of this section.

  1. Vents designed to remain attached to the building when venting a deflagration shall be so located that the discharge opening shall be not less than 10 feet (3048 mm) vertically from window openings and exits in the building and 20 feet (6096 mm) horizontally from exits in the building, from window openings and exits in adjacent buildings on the same lot and from the lot line.

  2. Discharge from vents shall not be into the interior of the building.

FIRE PROTECTION AND LIFE SAFETY SYSTEMS

Exceptions & meaning →

911.3 Explosion prevention systems. Explosion prevention

systems shall be of an approved type and installed in accordance with the provisions of this code and NFPA 69.

Exceptions & meaning →

911.4 Barricades. Barricades shall be designed and installed

in accordance with NFPA 495.