2307.1 General.¶
Motor fuel-dispensing facilities for liquefied petroleum gas (LP-gas) fuel shall be in accordance with this section and Chapter 61.
2307.2 Approvals. Storage vessels and equipment used for¶
the storage or dispensing of LP-gas shall be approved or listed in accordance with Sections 2307.2.1 and 2307.2.2.
2307.2.1 Approved equipment. Containers, pressure relief devices (including pressure relief valves), pressure regulators and piping for LP-gas shall be approved.
2307.2.2 Listed equipment. Hoses, hose connections, vehicle fuel connections, dispensers, LP-gas pumps and electrical equipment used for LP-gas shall be listed.
2307.3 Attendants.¶
Motor fuel-dispensing operations for LPgas shall be conducted by qualified attendants or in accordance with Section 2307.7 by persons trained in the proper handling of LP-gas.
2307.4 Location of dispensing operations and equipment.¶
The point of transfer for LP-gas dispensing operations shall be separated from buildings and other exposures in accordance with the following:
Not less than 25 feet (7620 mm) from buildings where the exterior wall is not part of a fire-resistance-rated assembly having a rating of 1 hour or greater.
Not less than 25 feet (7620 mm) from combustible overhangs on buildings, measured from a vertical line dropped from the face of the overhang at a point nearest the point of transfer.
Not less than 25 feet (7620 mm) from the lot line of property that can be built on.
Not less than 25 feet (7620 mm) from the centerline of the nearest mainline railroad track.
Not less than 10 feet (3048 mm) from public streets, highways, thoroughfares, sidewalks and driveways.
Not less than 10 feet (3048 mm) from buildings where the exterior wall is part of a fire-resistance-rated assembly having a rating of 1 hour or greater.
Exception: The point of transfer for LP-gas dispensing operations need not be separated from canopies that are constructed in accordance with the California Building Code and that provide weather protection for the dispensing equipment.
LP-gas containers shall be located in accordance with Chapter 61. LP-gas storage and dispensing equipment shall be located outdoors.
2307.5 Additional requirements for LP-gas dispensers¶
and equipment. LP-gas dispensers and related equipment shall comply with the following provisions.
- Pumps shall be fixed in place and shall be designed to allow control of the flow and to prevent leakage and accidental discharge.
360 2019 CALIFORNIA FIRE CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
Dispensing devices installed within 10 feet (3048 mm) of where vehicle traffic occurs shall be protected against physical damage by mounting on a concrete island 6 inches (152 mm) or more in height, or shall be protected in accordance with Section 312.
Dispensing devices shall be securely fastened to their mounting surface in accordance with the dispenser manufacturer’s instructions.
2307.6 Installation of LP-gas dispensing devices and¶
equipment. The installation and operation of LP-gas dispensing systems shall be in accordance with Sections 2307.6.1 through 2307.6.4 and Chapter 61. LP-gas dispensers and dispensing stations shall be installed in accordance with the manufacturer’s specifications and their listing.
2307.6.1 Product control valves. The dispenser system piping shall be protected from uncontrolled discharge in accordance with the following:
Where mounted on a concrete base, a means shall be provided and installed within 1 /2 inch (12.7 mm) of the top of the concrete base that will prevent flow from the supply piping in the event that the dispenser is displaced from its mounting.
A manual shutoff valve and an excess flow-control check valve shall be located in the liquid line between the pump and the dispenser inlet where the dispensing device is installed at a remote location and is not part of a complete storage and dispensing unit mounted on a common base.
An excess flow-control check valve or an emergency shutoff valve shall be installed in or on the dispenser at the point at which the dispenser hose is connected to the liquid piping.
A listed automatic-closing type hose nozzle valve with or without a latch-open device shall be provided on island-type dispensers.
2307.6.2 Hoses. Hoses and piping for the dispensing of LP-gas shall be provided with hydrostatic relief valves. The hose length shall not exceed 18 feet (5486 mm). An approved method shall be provided to protect the hose against mechanical damage.
2307.6.3 Emergency breakaway devices. Dispenser hoses shall be equipped with a listed emergency breakaway device designed to retain liquid on both sides of the breakaway point. Where hoses are attached to hoseretrieving mechanisms, the emergency breakaway device shall be located such that the breakaway device activates to protect the dispenser from being displaced.
2307.6.4 Vehicle impact protection. Where installed within 10 feet of vehicle traffic, LP-gas storage containers, pumps and dispensers shall be protected in accordance with Section 2307.5, Item 2.
2307.7 Public fueling of motor vehicles.¶
Self-service LPgas dispensing systems, including key, code and card lock dispensing systems, shall be limited to the filling of permanently mounted containers providing fuel to the LP-gas powered vehicle.
MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
The requirements for self-service LP-gas dispensing systems shall be in accordance with the following:
The arrangement and operation of the transfer of product into a vehicle shall be in accordance with this section and Chapter 61.
The system shall be provided with an emergency shutoff switch located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, dispensers.
The owner of the LP-gas motor fuel-dispensing facility or the owner’s designee shall provide for the safe operation of the system and the training of users.
The dispenser and hose-end valve shall release not more than 1 /8 fluid ounce (4 cc) of liquid to the atmosphere upon breaking the connection with the fill valve on the vehicle.
Portable fire extinguishers shall be provided in accordance with Section 2305.5.
Warning signs shall be provided in accordance with Section 2305.6.
The area around the dispenser shall be maintained in accordance with Section 2305.7.
2307.8 Overfilling. LP-gas containers shall not be filled with¶
LP-gas in excess of the volume determined using the fixed maximum liquid level gauge installed on the container, the volume determined by the overfilling prevention device installed on the container or the weight determined by the required percentage of the water capacity marked on the container.