Skip to content

Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES

Section 2303

California Fire Code (Title 24, Part 9) · 2019 edition · updated 2026-09-10 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

2303.1 Location of dispensing devices. Dispensing devices

shall be located as follows:

  1. Ten feet (3048 mm) or more from lot lines.

  2. Ten feet (3048 mm) or more from buildings having combustible exterior wall surfaces or buildings having noncombustible exterior wall surfaces that are not part of a 1-hour fire-resistance-rated assembly or buildings having combustible overhangs.

Exception: Canopies constructed in accordance with the California Building Code providing weather protection for the fuel islands.

  1. Such that all portions of the vehicle being fueled will be on the premises of the motor fuel-dispensing facility.

  2. Such that the nozzle, where the hose is fully extended, will not reach within 5 feet (1524 mm) of building openings.

  3. Twenty feet (6096 mm) or more from fixed sources of ignition.

2303.1.1 Protection of dispensing devices. Where dis- pensing devices are mounted at grade, they shall be pro- tected at each end with a minimum of two concrete filled steel posts, 6 inches (152 mm) in diameter, having a mini- mum 3-foot-deep (914 mm) footing not less than 15 inches (38 mm) in diameter and projecting above grade at a min- imum of 3 feet (914 mm) and be located not less than 4 feet (1219 mm) nor more than 5 feet (1524 mm) from fuel dis-

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES

pensers or point-of-sale devices, or equivalent means approved by the fire chief.

Exceptions & meaning →

2303.2 Emergency disconnect switches.

An approved emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be provided with ready access and shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be provided with ready access and be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.

2303.2.1 Height. The height of the emergency disconnect switch shall be not less than 42 inches (1067 mm) and not more than 48 inches (1372 mm) measured vertically, from the floor level to the activating button.

Exceptions & meaning →

Get a plain-English answer with a citation back to this text.

Ask AI about this code
▸Contents — California Fire Code (Title 24, Part 9)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.