Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
908 Emergency Alarm Systems — 2025 California Fire Code
California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Fire Code (Title 24, Part 9) § 908 · Effective January 1, 2026 · Official source: Building Standards Commission
908.1 Group H occupancies.¶
Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter 50.
908.2 Group H-5 occupancy.¶
Emergency alarms for notification of an emergency condition in an HPM facility shall be provided as required in Section 2703.12.
908.3 Fire alarm system interface.¶
Where an emergency alarm system is interfaced with a building’s fire alarm system, the signal produced at the fire alarm control unit shall be a supervisory signal.
908.4 Carbon dioxide enrichment systems.¶
A gas detection system shall be provided in rooms and indoor areas in which carbon diox- ide enrichment processes are located in accordance with Section 5307.3.2.