908.1 Group H occupancies.

Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter 50.

Exceptions & meaning →

908.2 Group H-5 occupancy.

Emergency alarms for notification of an emergency condition in an HPM facility shall be provided as required in Section 2703.12.

Exceptions & meaning →

908.3 Fire alarm system interface.

Where an emergency alarm system is interfaced with a building’s fire alarm system, the signal produced at the fire alarm control unit shall be a supervisory signal.

Exceptions & meaning →

908.4 Carbon dioxide enrichment systems.

A gas detection system shall be provided in rooms and indoor areas in which carbon diox- ide enrichment processes are located in accordance with Section 5307.3.2.