Section 3007 — OPERATION AND MAINTENANCE
2025 California Fire Code (Title 24, Part 9) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
3007.1 Furnace system information. ¶
3007.1 Furnace system information. An approved, clearly worded, and prominently displayed safety design data form or manufacturer’s nameplate shall be provided stating the safe operating condition for which the furnace system was designed, built, altered or extended.
3007.2 Oven nameplate. ¶
3007.2 Oven nameplate. Safety data for Class A solvent atmosphere ovens shall be furnished on the manufacturer’s nameplate. The nameplate shall provide the following design data: 1. The solvent used. 2. The number of gallons (L) used per batch or per hour of solvent entering the oven. 3. The required purge time. 4. The oven operating temperature. 5. The exhaust blower rating for the number of gallons (L) of solvent per hour or batch at the maximum operating temperature. Exception: For low-oxygen ovens, the maximum allowable oxygen concentration shall be included in place of the exhaust blower…
3007.3 Training. ¶
3007.3 Training. Operating, maintenance and supervisory personnel shall be thoroughly instructed and trained in the operation of ovens or furnaces.
3007.4 Equipment maintenance. ¶
3007.4 Equipment maintenance. Equipment shall be maintained in accordance with the manufacturer’s instructions. 30-4 2025 CALIFORNIA FIRE CODE on Jul 18, 2025 11:14 AM (CDT) THEREUNDER. CALIFORNIA FIRE CODE – MATRIX ADOPTION TABLE CHAPTER 31 – TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTHER MEMBRANE STRUCTURES (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.) Adopting AgencyBSCBSC-<brCGSFMCol5HCDCol7Col8DSACol10OSHPDCol12Col13Col14Col15Col16BSCCDPHAGRDWRCECCASLSLC…