Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS

Section 1116 — EXISTING GROUP L AND GROUP H-8 OCCUPANCIES [SFM]

2025 California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

1116.1 Repairs general.

Additions, alterations or repairs may be made to any building or structure without requiring the existing build- ing or structure to comply with all the requirements of this code section, provided the addition, alteration or repair conforms to the requirements of this section.

1116.2 Unsafe condition.

Additions, repairs or alterations shall not be made to an existing building or structure that will cause the exist- ing building or structure to be in violation of any of the provisions of this code, nor shall such additions or alterations cause the existing building or structure to become unsafe, or to be in violation of any of the provisions of this code. An unsafe condition shall be deemed to have been created if an addition or alteration will cause the existing building or structure to become structurally unsafe or overloaded; will not provide adequate egress in compliance with the provisions of this code or will obstruct existing exits; will create a fire hazard; will reduce required fire resistance or will otherwise create conditions dangerous to human life.

1116.3 Changes in use or occupancy.

Any buildings that have alternations or additions, which involves a change in use or occupancy, shall not exceed the height, number of stories and area permitted for new buildings.

1116.4 Buildings not in compliance with code.

Additions or alterations shall not be made to an existing building or structure when such existing building or structure is not in full compliance with the provisions of this code except when such addition or alteration will result in the existing building or structure being no more hazardous, based on life safety, fire safety and sanitation, than before such additions or alterations are undertaken.

1116.5 Maintenance of structural and fire resistive integrity.

Alterations or repairs to an existing building or structure that are nonstructural and do not adversely affect any structural member of any part of the building or structure having required fire resistance may be made with the same materials of which the building or structure is constructed. The installation or replacement of glass shall be as required for new installations.

11-28 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS

1116.6 Continuation of existing use.

Buildings in existence at the time of the adoption of this code may have their existing use or occu- pancy continued if such use or occupancy was legal at the time of the adoption of this code, provided such continued use is not dangerous to life.

1116.7 Maximum allowable quantities.

Existing Group H-8 laboratory suites approved prior to January 1, 2008 shall not exceed the maximum allowable quantities listed in Tables 1116.7(1) and 1116.7(2).

TABLE 1116.7(1)–EXEMPT AMOUNTS OF HAZARDOUS MATERIALS, LIQUIDS AND CHEMICALS
PRESENTING A PHYSICAL HAZARD BASIC QUANTITIES PER LABORATORY SUITE1
When two units are given, values within parentheses are in cubic feet (cu. ft) or pounds (lb)

CONDITION CONDITION STORAGE STORAGE STORAGE USE CLOSED SYSTEMS USE CLOSED SYSTEMS USE CLOSED SYSTEMS USE OPEN SYSTEMS USE OPEN SYSTEMS USE OPEN SYSTEMS
MATERIAL CLASS Solid
Pounds
(cu. ft)
Liquid
Gallons
(lb)
Gas
(cu. ft)
Solid
Pounds
(cu. ft)
Liquid
Gallons
(lb)
Gas
(cu. ft)
Solid
Pounds
(cu. ft)
Liquid
Gallons
(lb)
Gas
(cu. ft)
1.1 Combustible liquid II 1202 120 30
1.1 Combustible liquid III-A 3302 330 80
1.1 Combustible liquid III-B 13,2002 13,200 3,300
1.2 Combustible dust lbs./1000 cu. ft. 1 1 1
1.3 Combustible fiber
_ (loose)
(baled)_
(100)
(1,000)


(100)
(1,000)


(20)
(200)


1.4 Cryogenic, flammable or oxidizing 45 45 10
2.1 Explosives 12 (1)2 1/4 (1/4) 1/4 (1/4)
3.1 Flammable solid 1252 25 25
3.2 Flammable gas
_ (gaseous)
(liquefied)_


152
7502


152
7502



3.3 Flammable liquid
combination I-A, I-B, I-C
I-A 302 30 10
3.3 Flammable liquid
combination I-A, I-B, I-C
I-B 602 60 15
3.3 Flammable liquid
combination I-A, I-B, I-C
I-C 902 90 20
3.3 Flammable liquid
combination I-A, I-B, I-C
1202 120 30
4.1 Organic peroxide, unclassified
detonatable
12 (1)2 1/4 (1/4) 1/4 (1/4)
4.2 Organic peroxide I 52 (5)2 (1) (1) 1 1
4.2 Organic peroxide II 502 (50)2 50 (50) 10 (10)
4.2 Organic peroxide III 1252 (125)2 125 (125) 25 (25)
4.2 Organic peroxide IV 500 (500) 500 (500) 100 (100)
4.2 Organic peroxide V N.L. N.L. N.L. N.L. N.L. N.L.
4.3 Oxidizer 4 12 (1)2 1/4
2
(1/4) 1/4 (1/4)
4.3 Oxidizer 3 102 (10)2 2 (2) 2 (2)
4.3 Oxidizer 2 2502 (250)2 50 (250) 50 (50)
4.3 Oxidizer 1 1,0002 (1,000)2 1,000 (1,000) 200 (200)
4.4 Oxidizer, Gas
_ (gaseous)
(liquefied)_


152
1,5002


152
1,5002



5.1 Pyrophoric 42 (4)2 502 1 (1) 102 0 0 0
6.1 Unstable (reactive) 4 12 (1)2 102 1/4 (1/4) 22 1/4 (1/4) 0
6.1 Unstable (reactive) 3 52 (5)2 502 1 (1) 102 1 (1) 0
6.1 Unstable (reactive) 2 502 (50)2 2502 50 (50) 2502 10 (10) 0
6.1 Unstable (reactive) 1 1252 1252 7502 125 (125) 7502 25 (25) 0
7.1 Water (reactive) 3 52 (5)2 5 (5) 1 (1)
7.1 Water (reactive) 2 502 (50)2 50 (50) 10 (10)
7.1 Water (reactive) 1 1252 (125)2 125 (125)2 25 (25)

1. A laboratory suite is a space up to 10,000 square feet (929 m2) bounded by not less than a one-hour fire-resistive occupancy separation within which the exempt amounts of
hazardous materials may be stored, dispensed, handled or used. Up through the third floor and down through the first basement floor, the quantity in this table shall apply.
Fourth, fifth and sixth floors and the second and third basement floor level quantity shall be reduced to 75 percent of this table. The seventh through 10th floor and below the third
basement floor level quantity shall be reduced to 50 percent of this table.
2. Quantities may be increased 100 percent when stored in approved exhausted gas cabinets, exhausted enclosures or fume hoods.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS

TABLE 1116.7(2)–EXEMPT AMOUNTS OF HAZARDOUS MATERIALS, LIQUIDS AND CHEMICALS
PRESENTING A HEALTH HAZARD MAXIMUM QUANTITIES PER LABORATORY SUITE1
When two units are given, values within parentheses are in pounds (lbs.)

MATERIAL STORAGE STORAGE STORAGE USE CLOSED SYSTEMS USE CLOSED SYSTEMS USE CLOSED SYSTEMS USE OPEN SYSTEMS USE OPEN SYSTEMS
MATERIAL Solid lb Liquid
Gallons
(lb)
Gas
(cu. ft)
Solid lb Liquid
Gallons
(lb)
Gas
(cu. ft)
Solid lb Liquid
Gallons
(lb)
1. Corrosives 5,000 500 6502 5,000 500 650 1,000 100
_2a. Highly toxics2 _ 40 10 65 5 1 65 2 1/4
2b. Toxics 500 50 6502 500 50 650 5 1/2
3. Irritants 5,000 500 650 5,000 500 650 1,000 100
4. Sensitizers 5,000 500 650 5,000 500 650 1,000 100
5. Other health hazards 5,000 500 650 5,000 500 650 1,000 100

1. A laboratory suite is a space up to 10,000 square feet (929 m2) bounded by not less than a one-hour fire-resistive occupancy separation within which the exempt amounts of
hazardous materials may be stored, dispensed, handled or used. Up through the third floor and down through the first basement floor, the quantity in this table shall apply.
Fourth, fifth and sixth floors and the second and third basement floor level quantity shall be reduced to 75 percent of this table. The seventh through 10th floor and below the third
basement floor level quantity shall be reduced to 50 percent of this table.
2. Permitted only when stored or used in approved exhausted gas cabinets, exhausted enclosures or fume hoods. Quantities of high toxics in use in open systems need not be
reduced above the third floor or below the first basement floor level. Individual container size shall be limited to 2 pounds (0.91 kg) for solids and1/4 gallon (0.95 L) for liquids.

11-30 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CALIFORNIA FIRE CODE – MATRIX ADOPTION TABLE

CHAPTER 12 – ENERGY SYSTEMS

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency BSC BSC-
CG
T-24 T-19* 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended sections
listed below)
X
Adopt only those sections
that are listed below
[California Code of Regulations,
Title 19, Division 1]
Chapter / Section
1203.1.2 X
1203.1.3.1 X
1203.1.5.1 X
1203.2.11 X
1205.2.4 X
1205.3.4 X
1207.11.3 X
1207.11.4 X
Table 1207.11.4 X
  • The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

12-2 2025 CALIFORNIA FIRE CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Fire Code (Title 24, Part 9)
2025 California Fire Code (Title 24, Part 9)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REQUIREMENTS
  4. Chapter 4 — EMERGENCY PLANNING AND PREPAREDNESS
  5. Chapter 5 — FIRE SERVICE FEATURES
  6. Chapter 6 — BUILDING SERVICES AND SYSTEMS
  7. Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
  8. Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHI…
  9. Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
  10. Chapter 10 — MEANS OF EGRESS
  11. Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
  12. Chapter 12 — ENERGY SYSTEMS
  13. Chapter 20 — AVIATION FACILITIES
  14. Chapter 21 — DRY CLEANING
  15. Chapter 22 — COMBUSTIBLE DUST-PRODUCING OPERATIONS
  16. Chapter 23 — MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES
  17. Chapter 24 — FLAMMABLE FINISHES
  18. Chapter 25 — FRUIT AND CROP RIPENING
  19. Chapter 26 — FUMIGATION AND INSECTICIDAL FOGGING
  20. Chapter 27 — SEMICONDUCTOR FABRICATION FACILITIES
  21. Chapter 28 — LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS A…
  22. Chapter 29 — MANUFACTURE OF ORGANIC COATINGS
  23. Chapter 30 — INDUSTRIAL OVENS
  24. Chapter 31 — TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTH…
  25. Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
  26. Chapter 33 — FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
  27. Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
  28. Chapter 35 — WELDING AND OTHER HOT WORK
  29. Chapter 36 — MARINAS
  30. Chapter 37 — COMBUSTIBLE FIBERS
  31. Chapter 38 — RESERVED
  32. Chapter 39 — PROCESSING AND EXTRACTION FACILITIES
  33. Chapter 40 — STORAGE OF DISTILLED SPIRITS AND WINES
  34. Chapter 41 — TEMPORARY HEATING AND COOKING OPERATIONS
  35. Chapter 48 — MOTION PICTURE AND TELEVISION PRODUCTION STUDIO S…
  36. Chapter 49 — REQUIREMENTS FOR WILDLAND-URBAN INTERFACE FIRE AR…
  37. Chapter 50 — HAZARDOUS MATERIALS—GENERAL PROVISIONS
  38. Chapter 51 — AEROSOLS
  39. Chapter 52 — RESERVED
  40. Chapter 53 — COMPRESSED GASES
  41. Chapter 54 — CORROSIVE MATERIALS
  42. Chapter 55 — CRYOGENIC FLUIDS
  43. Chapter 56 — EXPLOSIVES AND FIREWORKS
  44. Chapter 57 — FLAMMABLE AND COMBUSTIBLE LIQUIDS
  45. Chapter 58 — FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS
  46. Chapter 59 — FLAMMABLE SOLIDS
  47. Chapter 60 — HIGHLY TOXIC AND TOXIC MATERIALS
  48. Chapter 61 — LIQUEFIED PETROLEUM GASES
  49. Chapter 62 — ORGANIC PEROXIDES
  50. Chapter 63 — OXIDIZERS, OXIDIZING GASES AND OXIDIZING CRYOGENI…
  51. Chapter 64 — PYROPHORIC MATERIALS
  52. Chapter 65 — PYROXYLIN (CELLULOSE NITRATE) PLASTICS
  53. Chapter 66 — UNSTABLE (REACTIVE) MATERIALS
  54. Chapter 67 — WATER-REACTIVE SOLIDS AND LIQUIDS
  55. Chapter 80 — REFERENCED STANDARDS
  56. Appendix Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON US…
  57. Appendix A — BOARD OF APPEALS
  58. Appendix B — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  59. Appendix BB — FIRE-FLOW REQUIREMENTS FOR BUILDINGS
  60. Appendix C — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  61. Appendix CC — FIRE HYDRANT LOCATIONS AND DISTRIBUTION
  62. Appendix D — FIRE APPARATUS ACCESS ROADS
  63. Appendix E — HAZARD CATEGORIES
  64. Appendix F — HAZARD RANKING
  65. Appendix G — CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS
  66. Appendix H — HAZARDOUS MATERIALS MANAGEMENT PLANS AND HAZARDOU…
  67. Appendix I — FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS
  68. Appendix J — BUILDING INFORMATION SIGN
  69. Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY…
  70. Appendix L — REQUIREMENTS FOR FIREFIGHTER AIR REPLENISHMENT SY…
  71. Appendix M — HIGH-RISE BUILDINGS—RETROACTIVE AUTOMATIC SPRINKL…
  72. Appendix N — INDOOR TRADE SHOWS AND EXHIBITIONS
  73. Appendix O — VALET TRASH AND RECYCLING COLLECTION IN GROUP R-2…
  74. Appendix P — TEMPORARY HAUNTED HOUSES, GHOST WALKS AND SIMILAR…
  75. Appendix Q — COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZ…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.