Chapter 11 — CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS
Section 1105 — CONSTRUCTION REQUIREMENTS FOR EXISTING GROUP I-2
2025 California Fire Code (Title 24, Part 9) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
1105.1 General. Existing Group I-2 shall meet all of the following requirements: ¶
1105.1 General. Existing Group I-2 shall meet all of the following requirements: 1. The minimum fire safety requirements in Section 1103. 2. The minimum means of egress requirements in Section 1104. 3. The additional egress and construction requirements in Section 1105. Where the provisions of this chapter conflict with the construction requirements that applied at the time of construction, the most restrictive provision shall apply.
1105.2 Applicability. ¶
1105.2 Applicability. The provisions of Sections 1105.3 through 1105.8, 1105.10 and 1105.11 shall apply to the existing Group I-2 fire area.
1105.3 Construction. ¶
1105.3 Construction. Group I-2, Condition 2 shall not be located on a floor level higher than the floor level limitation in Table 1105.3 based on the type of construction. 11-18 2025 CALIFORNIA FIRE CODE on Jul 18, 2025 11:14 AM (CDT) THEREUNDER. CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS TABLE 1105.3—FLOOR LEVEL LIMITATIONS FOR GROUP I-2, CONDITION 2Col2Col3Col4Col5Col6 ------------------ CONSTRUCTION TYPEAUTOMATIC SPRINKLER SYSTEMALLOWABLE FLOOR LEVELaALLOWABLE FLOOR LEVELaALLOWABLE FLOOR LEVELaALLOWABLE FLOOR LEVELa CONSTRUCTION TYPEAUTOMATIC SPRINKLER SYSTEM1234 or more IANote bPPPP…
1105.4 Incidental uses in existing Group I-2. ¶
1105.4 Incidental uses in existing Group I-2. Incidental uses associated with and located within existing single-occupancy or mixed-occupancy Group I-2 buildings and that generally pose a greater level of risk to such occupancies shall comply with the provisions of Sections 1105.4.1 through 1105.4.3.2.1. Incidental uses in Group I-2 occupancies are limited to those listed in Table 1105.4. TABLE 1105.4—INCIDENTAL USES IN EXISTING GROUP I-2 OCCUPANCIESCol2 ------ ROOM OR AREASEPARATION AND/OR PROTECTION Furnace room where any piece of equipment is over 400,000 Btu per hour input1 hour or…
1105.5 Corridor construction. ¶
1105.5 Corridor construction. In Group I-2, in areas housing patient sleeping or care rooms, corridor walls and the opening protectives therein shall provide a barrier designed to resist the passage of smoke in accordance with Sections 1105.5.1 through 1105.5.7. 1105.5.1 Materials. The walls shall be of materials permitted by the building type of construction. 1105.5.2 Fire-resistance rating. Unless required elsewhere in this code, corridor walls are not required to have a fire-resistance rating. Corridor walls that were installed as fire-resistance-rated assemblies in accordance with the…
1105.6 Means of egress. ¶
1105.6 Means of egress. In addition to the means of egress requirements in Section 1104, Group I-2 facilities shall meet the means of egress requirements in Sections 1105.6.1 through 1105.6.8. 1105.6.1 Two means of egress. A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which the means of egress originated. Smoke compartments that do not contain an exit shall be provided with direct access to not less than two adjacent smoke compartments. 1105.6.2 Size of door. Means of egress doors used for…
1105.7 Smoke compartments. ¶
1105.7 Smoke compartments. Smoke compartments shall be provided in existing Group I-2, Condition 2, in accordance with Sections 1105.7.1 through 1105.7.6. 1105.7.1 Design. Smoke barriers shall be provided to subdivide each story used for patients sleeping with an occupant load of more than 30 patients into not fewer than two smoke compartments. 1105.7.1.1 Refuge areas. Refuge areas shall be provided within each smoke compartment. The size of the refuge area shall accommodate the occupants and care recipients from the adjoining smoke compartment. Where a smoke compartment is adjoined by two or…
1105.8 Group I-2 care suites. ¶
1105.8 Group I-2 care suites. Care suites in existing Group I-2, Condition 2 occupancies shall comply with Sections 407.4.4 through 407.4.4.7.2 of the California Building Code .
1105.9 Group I-2 automatic sprinkler system. ¶
1105.9 Group I-2 automatic sprinkler system. An automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be provided throughout the floor containing the Group I-2 fire area. The sprinkler system shall be provided throughout the floor where the Group I-2 occupancy is located, on all floors between the Group I-2 occupancy fire area and the level of exit discharge, the level of exit discharge, and all floors below the level of exit discharge. Exception: Floors classified as an open parking garage are not required to be sprinklered.
1105.10 Group I-2 automatic fire alarm system. ¶
1105.10 Group I-2 automatic fire alarm system. An automatic fire alarm system shall be installed in existing Group I-2 occupancies in accordance with Section 907.2.6.2. Exception: Manual fire alarm boxes in patient sleeping areas shall not be required at exits if located at all nurses’ control stations or other constantly attended staff locations, provided such that manual fire alarm boxes are visible, are provided with ready access, and travel distances required in Section 907.4.2.1 are not exceeded.
1105.11 Essential electrical systems. ¶
1105.11 Essential electrical systems. Essential electrical systems in Group I-2, Condition 2 occupancies shall be in accordance with Sections 1105.11.1 and 1105.11.2. 1105.11.1 Where required. Where required by NFPA 99, Group I-2, Condition 2 occupancies shall be provided with an essential electrical system in accordance with NFPA 99. 1105.11.2 Installation and duration. In Group I-2, Condition 2 occupancies, the installation and duration of operation of existing essential electrical systems shall be based on a hazard vulnerability analysis conducted in accordance with NFPA 99.
1105.12 Group I-2 separations between construction areas. ¶
1105.12 Group I-2 separations between construction areas. In an existing Group I-2 occupancy, areas of construction, alteration or demolition shall be separated from occupied portions of the building. Where, in accordance with Section 701.2, the maintenance of fire- resistance-rated construction is not required, separations used to separate areas of construction, alteration, or demolition from occu- pied portions of the building shall be constructed of materials that comply with one of the following: 1. Floors and nonbearing walls and partitions in accordance with California Building Code…