Section 3125B — RECIRCULATION PIPING SYSTEM AND COMPONENTS
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
3125B.1 Line sizes. ¶
Pipes shall be sized so flow velocity of piping systems including all pipes and fittings other than inlet devices or venturi throats shall not exceed 6 feet per second (1.829 m/s) in any suction or copper piping and 8 feet per second (2.438 m/s) in any portion of the return system.
3125B.1.1 Materials. All piping, tubing and fittings shall comply with the applicable standards for potable water system materials set forth in Chapter 6 of the California Plumbing Code.
3125B.2 Gauges. ¶
A pressure and vacuum gauge shall be provided for each pump system. Each gauge shall have a scale range approxi- mately 1 [1] / 4 times the maximum anticipated working pressure or vacuum and shall be accurate within 2 percent of scale. The pressure gauge located on the filter shall be marked with the clean start up pressure reading.
3125B.3 Flow meter. ¶
A flow meter shall be provided on each recirculation system accurate to within 10 percent of flow and installed according to the manufacturer’s written instructions with increments in the range of normal flow.
3125B.4 Basket strainer. ¶
A basket strainer shall be provided on the suction side of the recirculation pump. A basket strainer will not be required on pumps connected to vacuum filters where the filter elements are not removed for cleaning.
3125B.5 Backwash piping. ¶
Piping, including necessary valves conforming to Section 3125B.1, shall be provided for each filter vessel or element which requires periodic backwashing.
3125B.6 Valves. ¶
Valves shall not be located in any deck area surrounding a pool. Valves shall be installed on all recirculation, backwash- ing and drain system lines which require shutoff isolation, adjustment or control of the rate of flow. Each valve shall be installed in the equipment area and labeled as to its purpose.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
-
▸ Chapter 31B — PUBLIC POOLS
Overview- Section 3101B — SCOPE
- Section 3102B — DEFINITIONS
- Section 3103B — PLAN REVIEW
- Section 3104B — CONSTRUCTION
- Section 3105B — PLAN COMPLIANCE INSPECTIONS
- Section 3106B — SPECIAL REQUIREMENTS FOR SPRAY GROUNDS
- Section 3107B — ALTERNATIVE EQUIPMENT, MATERIALS AND METHODS O…
- Section 3108B — POOL CONSTRUCTION
- Section 3109B — POOL GEOMETRY
- Section 3110B — PERMANENT MARKINGS
- Section 3111B — STEPS, RECESSED STEPS, LADDERS AND STAIRS
- Section 3112B — HANDHOLDS
- Section 3113B — DIVING BOARDS AND PLATFORMS
- Section 3114B — POOL DECKS
- Section 3115B — POOL LIGHTING
- Section 3116B — DRESSING, SHOWER AND TOILET FACILITIES
- Section 3117B — DRINKING FOUNTAINS
- Section 3118B — HOSE BIBBS
- Section 3119B — POOL ENCLOSURE
- Section 3120B — REQUIRED SIGNS
- Section 3121B — INDOOR POOL VENTILATION
- Section 3122B — POOL EQUIPMENT ENCLOSURE
- Section 3123B — GENERAL REQUIREMENTS
- Section 3124B — TURNOVER TIME
- Section 3125B — RECIRCULATION PIPING SYSTEM AND COMPONENTS
- Section 3126B — RECIRCULATION PUMP CAPACITY
- Section 3127B — WATER SUPPLY INLETS
- Section 3128B — FILTERS (ALL TYPES)
- Section 3129B — RAPID SAND PRESSURE FILTERS
- Section 3130B — DIATOMACEOUS EARTH FILTERS
- Section 3131B — HIGH-RATE SAND FILTERS
- Section 3132B — CARTRIDGE FILTERS
- Section 3133B — CHEMICAL FEEDERS
- Section 3134B — DISINFECTANT FEEDERS
- Section 3135B — GAS CHLORINATION EQUIPMENT ROOM
- Section 3136B — POOL SKIMMING SYSTEMS
- Section 3137B — POOL FITTINGS
- Section 3138B — SPA POOL SPECIAL REQUIREMENTS
- Section 3139B — SOLAR HEATING INSTALLATIONS
- Section 3140B — CLEANING SYSTEMS
- Section 3141B — WASTEWATER DISPOSAL
- Section 3142B — RESERVED
- Section 3143B — RESERVED
- Section 3144B — RESERVED
- Section 3145B — RESERVED
- Section 3146B — RESERVED
- Section 3147B — RESERVED
- Section 3148B — RESERVED
- Section 3149B — RESERVED
- Section 3150B — RESERVED
- Section 3151B — RESERVED
- Section 3152B — RESERVED
- Section 3153B — RESERVED
- Section 3154B — RESERVED
- Section 3155B — RESERVED
- Section 3156B — RESERVED
- Section 3157B — RESERVED
- Section 3158B — RESERVED
- Section 3159B — RESERVED
- Section 3160B — GROUND FAULT CIRCUIT INTERRUPTERS
- Section 3161B — WADING POOLS
- Section 3162B — ANTI-ENTRAPMENT DEVICES AND SYSTEMS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING