Section 3119B — POOL ENCLOSURE
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
3119B.1 Enclosure. ¶
The pool shall be enclosed by one or a combination of the following: a fence, portion of a building, wall or other approved durable enclosure. Doors, openable windows, gates of living units or associated private premises shall not be permitted as part of the pool enclosure. The enclosure, doors and gates shall meet all of the following specifications:
1. The enclosure shall have a minimum effective perpendicular height of 5 feet (1524 mm) as measured from the outside as depicted in Figure 31B-4; and
2. Openings, holes or gaps in the enclosure, doors and/or gates shall not allow the passage of a 4-inch (102 mm) diameter sphere. The enclosure shall be constructed over a hard and permanent material equivalent to concrete; and
3. The enclosure shall be designed and constructed so that it cannot be readily climbed by small children. Horizontal and diago- nal member designs which might serve as a ladder for small children are prohibited. Horizontal members shall be spaced at least 48 inches (1219 mm) apart. No planters or other structures that can be climbed shall be permitted within 5 feet (1524 mm) of the outside of the pool enclosure or within a 5 foot (1524 mm) arc as depicted in Figure 31B-5. The area 5 feet (1524 mm) outside of the pool enclosure shall be a common area open to the public; and 4. Chain link may be used, provided that the openings are not greater than 1 [3] / 4 inches (44 mm) measured horizontally.
3119B.2 Gates. ¶
Gates and doors opening into the pool enclosure also shall meet the following specifications:
1. Gates and doors shall be equipped with self-closing and self-latching devices. The self-latching device shall keep the gate or door securely closed. Gates and doors shall open outwardly away from the pool except where otherwise prohibited by law. Hand activated door or gate opening hardware shall be located at a height no lower than 42 inches (1067 mm) but no higher than 44 inches (1179 mm) above the deck or walkway; and
2. Gates and doors shall be capable of being locked during times when the pool is closed. Exit doors which comply with Chapter 10, Title 24, California Code of Regulations shall be considered as meeting these requirements; and
3. The pool enclosure shall have at least one means of egress without a key for emergency purposes. Unless all gates or doors are so equipped, those gates and/or doors which will allow egress without a key shall have a sign in letters at least 4 inches (102 mm) high stating EMERGENCY EXIT; and
4. The enclosure shall be constructed so that all persons will be required to pass through common pool enclosure gates or doors in order to gain access to the pool area. All gates and doors exiting the pool area shall open into a public area or a walkway accessible by all patrons of the pool.
3119B.3 Retroactivity. ¶
Sections 3119B.1 and 3119B.2 shall apply only to public pool enclosures constructed on or after July 1, 1994. Notwithstanding the foregoing effective date, no fence enclosure shall be less than 4 feet (1219 mm) in height.
3119B.4 Enclosure of pools constructed prior to July 1, 1994. ¶
The enforcing agent may allow the installation of an enclosure which reduces the pool deck to less than 4 feet (1219 mm) in width when the physical characteristics of a site preclude providing a 4-foot (1219 mm) wide deck around the perimeter of an existing pool.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
-
▸ Chapter 31B — PUBLIC POOLS
Overview- Section 3101B — SCOPE
- Section 3102B — DEFINITIONS
- Section 3103B — PLAN REVIEW
- Section 3104B — CONSTRUCTION
- Section 3105B — PLAN COMPLIANCE INSPECTIONS
- Section 3106B — SPECIAL REQUIREMENTS FOR SPRAY GROUNDS
- Section 3107B — ALTERNATIVE EQUIPMENT, MATERIALS AND METHODS O…
- Section 3108B — POOL CONSTRUCTION
- Section 3109B — POOL GEOMETRY
- Section 3110B — PERMANENT MARKINGS
- Section 3111B — STEPS, RECESSED STEPS, LADDERS AND STAIRS
- Section 3112B — HANDHOLDS
- Section 3113B — DIVING BOARDS AND PLATFORMS
- Section 3114B — POOL DECKS
- Section 3115B — POOL LIGHTING
- Section 3116B — DRESSING, SHOWER AND TOILET FACILITIES
- Section 3117B — DRINKING FOUNTAINS
- Section 3118B — HOSE BIBBS
- Section 3119B — POOL ENCLOSURE
- Section 3120B — REQUIRED SIGNS
- Section 3121B — INDOOR POOL VENTILATION
- Section 3122B — POOL EQUIPMENT ENCLOSURE
- Section 3123B — GENERAL REQUIREMENTS
- Section 3124B — TURNOVER TIME
- Section 3125B — RECIRCULATION PIPING SYSTEM AND COMPONENTS
- Section 3126B — RECIRCULATION PUMP CAPACITY
- Section 3127B — WATER SUPPLY INLETS
- Section 3128B — FILTERS (ALL TYPES)
- Section 3129B — RAPID SAND PRESSURE FILTERS
- Section 3130B — DIATOMACEOUS EARTH FILTERS
- Section 3131B — HIGH-RATE SAND FILTERS
- Section 3132B — CARTRIDGE FILTERS
- Section 3133B — CHEMICAL FEEDERS
- Section 3134B — DISINFECTANT FEEDERS
- Section 3135B — GAS CHLORINATION EQUIPMENT ROOM
- Section 3136B — POOL SKIMMING SYSTEMS
- Section 3137B — POOL FITTINGS
- Section 3138B — SPA POOL SPECIAL REQUIREMENTS
- Section 3139B — SOLAR HEATING INSTALLATIONS
- Section 3140B — CLEANING SYSTEMS
- Section 3141B — WASTEWATER DISPOSAL
- Section 3142B — RESERVED
- Section 3143B — RESERVED
- Section 3144B — RESERVED
- Section 3145B — RESERVED
- Section 3146B — RESERVED
- Section 3147B — RESERVED
- Section 3148B — RESERVED
- Section 3149B — RESERVED
- Section 3150B — RESERVED
- Section 3151B — RESERVED
- Section 3152B — RESERVED
- Section 3153B — RESERVED
- Section 3154B — RESERVED
- Section 3155B — RESERVED
- Section 3156B — RESERVED
- Section 3157B — RESERVED
- Section 3158B — RESERVED
- Section 3159B — RESERVED
- Section 3160B — GROUND FAULT CIRCUIT INTERRUPTERS
- Section 3161B — WADING POOLS
- Section 3162B — ANTI-ENTRAPMENT DEVICES AND SYSTEMS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING