Section 3110B — PERMANENT MARKINGS
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
3110B.1 General. ¶
No markings, designs or lettering shall be permitted on the pool shell except for slip resistant lane markings, depth marking lines and safety markings.
3110B.2 Lane markings. ¶
Slip resistant lane lines at the bottom of the pool shall not exceed 12 inches (305 mm) in width.
3110B.3 Depth marking line. ¶
There shall be installed a straight line of slip resistant tile a minimum of 4 inches (102 mm) and not greater than 6 inches (152 mm) wide of a color contrasting with the background of the pool shell across the bottom of the pool where the water depth is 4 [1] / 2 feet (1372 mm).
Exception: Pools having a maximum water depth of 5 feet (1524 mm) or less shall not be required to have a depth marking line.
3110B.4 Water depth markers. ¶
3110B.4.1 Location. The water depth shall be clearly marked at the following locations:
1. Maximum depth; and
2. Minimum depth; and
3. Each end; and
4. Both sides at the shallowest and deepest part of the pool; and
5. At the break in the bottom slope between the shallow and deep portions of the pool (see also Section 3109B.3); and
6. Along the perimeter of the pool at distances not to exceed 25 feet (7620 mm).
Exception: A spa or wading pool shall have a minimum of two depth markers indicating the maximum depth.
Note: For an illustration diagram pertaining to this section see Figure 31B-8.
3110B.4.2 Position. Where required by Section 3110B.4.1, depth markers shall be located in the following positions:
1. On the coping or on the deck, the depth markers shall be placed as close as possible but no more than 3 feet (914 mm) from the pool water; and
2. For pools with skimmer systems the depth markers shall be high at the waterline which typically will result in the depth markers being submerged approximately 50 percent; or
3. For pools with perimeter overflow systems where coping cantilevers over the gutter depth markers may be positioned at the face of the cantilevered coping, the back wall above the gutter or immediately below the waterline which will result in the depth markers being completely submerged; or
4. For pools with rim flow gutters, depth markers shall be positioned immediately below the waterline which will result in the depth markers being completely submerged.
3110B.4.3 Tolerance. Depth markers shall be positioned to indicate the water depth accurate to the nearest 6 inches (152 mm) as measured at the waterline.
3110B.4.4 Size of markers. Depth markers shall:
1. Have numerals a minimum of 4 inches (102 mm) in height and of a color contrasting with the background and be marked in units of feet and inches. Abbreviations of FT and IN may be used in lieu of feet and inches; and
2. Be made of a durable material that is resistant to weathering; and
3. Be slip resistant when they are located on the pool deck.
3110B.5 No diving markers. ¶
For pool water depths 6 feet (1830 mm) or less no diving markers with the universal symbol of no diving, which is a red circle with a slash through it superimposed over the image of a diver, shall be installed on the deck directly adjacent to the depth markers required by Section 3110B.4.1. No diving markers shall comply with Section 3110B.4.4(2-3).
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
-
▸ Chapter 31B — PUBLIC POOLS
Overview- Section 3101B — SCOPE
- Section 3102B — DEFINITIONS
- Section 3103B — PLAN REVIEW
- Section 3104B — CONSTRUCTION
- Section 3105B — PLAN COMPLIANCE INSPECTIONS
- Section 3106B — SPECIAL REQUIREMENTS FOR SPRAY GROUNDS
- Section 3107B — ALTERNATIVE EQUIPMENT, MATERIALS AND METHODS O…
- Section 3108B — POOL CONSTRUCTION
- Section 3109B — POOL GEOMETRY
- Section 3110B — PERMANENT MARKINGS
- Section 3111B — STEPS, RECESSED STEPS, LADDERS AND STAIRS
- Section 3112B — HANDHOLDS
- Section 3113B — DIVING BOARDS AND PLATFORMS
- Section 3114B — POOL DECKS
- Section 3115B — POOL LIGHTING
- Section 3116B — DRESSING, SHOWER AND TOILET FACILITIES
- Section 3117B — DRINKING FOUNTAINS
- Section 3118B — HOSE BIBBS
- Section 3119B — POOL ENCLOSURE
- Section 3120B — REQUIRED SIGNS
- Section 3121B — INDOOR POOL VENTILATION
- Section 3122B — POOL EQUIPMENT ENCLOSURE
- Section 3123B — GENERAL REQUIREMENTS
- Section 3124B — TURNOVER TIME
- Section 3125B — RECIRCULATION PIPING SYSTEM AND COMPONENTS
- Section 3126B — RECIRCULATION PUMP CAPACITY
- Section 3127B — WATER SUPPLY INLETS
- Section 3128B — FILTERS (ALL TYPES)
- Section 3129B — RAPID SAND PRESSURE FILTERS
- Section 3130B — DIATOMACEOUS EARTH FILTERS
- Section 3131B — HIGH-RATE SAND FILTERS
- Section 3132B — CARTRIDGE FILTERS
- Section 3133B — CHEMICAL FEEDERS
- Section 3134B — DISINFECTANT FEEDERS
- Section 3135B — GAS CHLORINATION EQUIPMENT ROOM
- Section 3136B — POOL SKIMMING SYSTEMS
- Section 3137B — POOL FITTINGS
- Section 3138B — SPA POOL SPECIAL REQUIREMENTS
- Section 3139B — SOLAR HEATING INSTALLATIONS
- Section 3140B — CLEANING SYSTEMS
- Section 3141B — WASTEWATER DISPOSAL
- Section 3142B — RESERVED
- Section 3143B — RESERVED
- Section 3144B — RESERVED
- Section 3145B — RESERVED
- Section 3146B — RESERVED
- Section 3147B — RESERVED
- Section 3148B — RESERVED
- Section 3149B — RESERVED
- Section 3150B — RESERVED
- Section 3151B — RESERVED
- Section 3152B — RESERVED
- Section 3153B — RESERVED
- Section 3154B — RESERVED
- Section 3155B — RESERVED
- Section 3156B — RESERVED
- Section 3157B — RESERVED
- Section 3158B — RESERVED
- Section 3159B — RESERVED
- Section 3160B — GROUND FAULT CIRCUIT INTERRUPTERS
- Section 3161B — WADING POOLS
- Section 3162B — ANTI-ENTRAPMENT DEVICES AND SYSTEMS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING