Section 3106B — SPECIAL REQUIREMENTS FOR SPRAY GROUNDS
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
3106B Spray grounds. All applicable provisions of this chapter shall apply to a spray ground unless specifically addressed in this section.
3106B.1 All parts of the spray ground shall be designed and constructed so that there are no safety hazards. ¶
3106B.2 Walking surface. ¶
A minimum 4-foot wide walking surface shall extend around the perimeter of the splash zone of a spray ground.
3106B.3 The recirculation system shall be in operation at all times that the spray… ¶
four turnover cycles prior to opening for proper disinfection and filtration.
3106B.4 There shall be no standing water within the splash zone. ¶
3106B.5 Nozzles that spray from the ground level shall be flush with the ground with… ¶
water features that extend above the ground must be clearly visible.
3106B.6 The splash zone shall be sloped so that only water from the spray ground water… ¶
adjacent to the splash zone shall be sloped away from the spray ground to deck drains or other surface water disposal systems.
3106B.7 All foggers and misters that produce finely atomized mists shall be supplied… ¶
the surge basin.
3106B.8 When multiple pumps are used the control systems for the spray ground water… ¶
shall be electrically interconnected so that when the recirculation pump is off the spray ground water feature pump also is off.
3106B.9 The spray ground shall have a surge basin or treatment tank constructed of… ¶
nontoxic and watertight including materials such as concrete, fiberglass, high density polyethylene, stainless steel or other materials as approved by the enforcing agent which can withstand all anticipated loadings under full and empty conditions as determined by an engineer or architect who has experience working on public pools.
3106B.10 The total volume of the surge basin shall be at least 4,000 gallons or a… ¶
of all the spray ground pumps and the recirculation pump combined, whichever is higher.
3106B.11 The turnover time shall be one-half hour or less. ¶
3106B.12 The suction intake for the spray ground or water feature pump in the surge… ¶
return line.
3106B.13 When separate pumps are used, the suction intake for the recirculation pump… ¶
surge basin and on the opposite side from the suction intake for the spray ground pump.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PUBLIC POOLS
3106B.14 The surge basin shall be designed to have easy access for cleaning and inspection. ¶
The basin shall have at least one ladder_ access and shall have at least one 3-foot by 3-foot access opening. Lids shall be locked or require a tool to open.
3106B.15 The surge basin shall be equipped with an automatic make up water fill device… ¶
approved backflow prevention device in accordance with Chapter 6 of the California Plumbing Code.
3106B.16 Ultraviolet light disinfection shall be used to supplement disinfection… ¶
ment process is provided that has been determined by a nationally recognized testing laboratory to be capable of providing at least the equivalent level of reduction of cryptosporidium as the ultraviolet light disinfection system specified in this section. The ultraviolet light disinfection unit shall comply with the applicable requirements established by the NSF/ANSI 50-2010 performance standard effective August 2010.
3106B.17 An accurately calibrated ultraviolet light intensity meter that has been… ¶
tion spectrum shall be installed in the wall of the disinfection chamber at the point of greatest water depth from the light source.
3106B.18 The ultraviolet light unit shall be located on the recirculation system and… ¶
the spray features.
3106B.19 The ultraviolet light disinfection system must be equipped with an automatic… ¶
feature pump if the ultraviolet dosage rate drops below 40 mJ/cm [2] .
3106B.20 Artificial lighting shall be provided at all spray ground pads which are used… ¶
lighting so that all portions of the spray pad and deck may be seen easily. Lighting that may be exposed to the feature pool water shall be installed in accordance with the manufacturer’s specifications and the California Electrical Code.
3106B.21 A means of diverting runoff from the splash zone shall be installed on the… ¶
to divert water to the storm drainage system when the spray ground is not in operation.
3106B.22 A removable and cleanable catch screen or basket shall be installed on the… ¶
reservoir to prevent larger debris from collecting in the surge basin.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
-
▸ Chapter 31B — PUBLIC POOLS
Overview- Section 3101B — SCOPE
- Section 3102B — DEFINITIONS
- Section 3103B — PLAN REVIEW
- Section 3104B — CONSTRUCTION
- Section 3105B — PLAN COMPLIANCE INSPECTIONS
- Section 3106B — SPECIAL REQUIREMENTS FOR SPRAY GROUNDS
- Section 3107B — ALTERNATIVE EQUIPMENT, MATERIALS AND METHODS O…
- Section 3108B — POOL CONSTRUCTION
- Section 3109B — POOL GEOMETRY
- Section 3110B — PERMANENT MARKINGS
- Section 3111B — STEPS, RECESSED STEPS, LADDERS AND STAIRS
- Section 3112B — HANDHOLDS
- Section 3113B — DIVING BOARDS AND PLATFORMS
- Section 3114B — POOL DECKS
- Section 3115B — POOL LIGHTING
- Section 3116B — DRESSING, SHOWER AND TOILET FACILITIES
- Section 3117B — DRINKING FOUNTAINS
- Section 3118B — HOSE BIBBS
- Section 3119B — POOL ENCLOSURE
- Section 3120B — REQUIRED SIGNS
- Section 3121B — INDOOR POOL VENTILATION
- Section 3122B — POOL EQUIPMENT ENCLOSURE
- Section 3123B — GENERAL REQUIREMENTS
- Section 3124B — TURNOVER TIME
- Section 3125B — RECIRCULATION PIPING SYSTEM AND COMPONENTS
- Section 3126B — RECIRCULATION PUMP CAPACITY
- Section 3127B — WATER SUPPLY INLETS
- Section 3128B — FILTERS (ALL TYPES)
- Section 3129B — RAPID SAND PRESSURE FILTERS
- Section 3130B — DIATOMACEOUS EARTH FILTERS
- Section 3131B — HIGH-RATE SAND FILTERS
- Section 3132B — CARTRIDGE FILTERS
- Section 3133B — CHEMICAL FEEDERS
- Section 3134B — DISINFECTANT FEEDERS
- Section 3135B — GAS CHLORINATION EQUIPMENT ROOM
- Section 3136B — POOL SKIMMING SYSTEMS
- Section 3137B — POOL FITTINGS
- Section 3138B — SPA POOL SPECIAL REQUIREMENTS
- Section 3139B — SOLAR HEATING INSTALLATIONS
- Section 3140B — CLEANING SYSTEMS
- Section 3141B — WASTEWATER DISPOSAL
- Section 3142B — RESERVED
- Section 3143B — RESERVED
- Section 3144B — RESERVED
- Section 3145B — RESERVED
- Section 3146B — RESERVED
- Section 3147B — RESERVED
- Section 3148B — RESERVED
- Section 3149B — RESERVED
- Section 3150B — RESERVED
- Section 3151B — RESERVED
- Section 3152B — RESERVED
- Section 3153B — RESERVED
- Section 3154B — RESERVED
- Section 3155B — RESERVED
- Section 3156B — RESERVED
- Section 3157B — RESERVED
- Section 3158B — RESERVED
- Section 3159B — RESERVED
- Section 3160B — GROUND FAULT CIRCUIT INTERRUPTERS
- Section 3161B — WADING POOLS
- Section 3162B — ANTI-ENTRAPMENT DEVICES AND SYSTEMS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING