Chapter 12 — INTERIOR ENVIRONMENT
Section 1210 — TOILET AND BATHROOM REQUIREMENTS
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[P] 1210.1 Required fixtures. The number and type of plumbing fixtures provided in any occupancy shall comply with the California Plumbing Code.
[P] 1210.2 Finish materials. Walls, floors and partitions in toilet and bathrooms shall comply with Sections 1210.2.1 through 1210.2.5.
[OSHPD 1, 2, 3 & 5] Facilities subject to OSHPD 1, 2, 3 & 5 shall also comply with Section 1224.4.11.
[OSHPD 4] Facilities subject to OSHPD 4 shall also comply with Section 1227.9.
[P] 1210.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches (102 mm).
[P] 1210.2.2 Walls and partitions. Walls and partitions within 2 feet (610 mm) of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet (1219 mm) above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
Exception: This section does not apply to the following buildings and spaces:
- Dwelling units and sleeping units.
- Toilet rooms that are not for use by the general public and that have not more than one water closet.
Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture.
1210.2.3 Adult changing table surround. Walls and partitions within 2 feet (610 mm) measured horizontally from each end of the adult changing table and to a height of not less than 72 inches (1829 mm) above the floor shall have a smooth, hard, nonabsorbent surface, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
[P] 1210.2.4 Showers. Shower compartments and walls above bathtubs with installed shower heads shall be finished with a smooth, nonabsorbent surface to a height not less than 72 inches (1829 mm) above the drain inlet.
[P] 1210.2.5 Waterproof joints. Built-in tubs with showers shall have waterproof joints between the tub and adjacent wall.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
INTERIOR ENVIRONMENT
[P] 1210.3 Privacy. Public restrooms shall be visually screened from outside entry or exit doorways to ensure user privacy within the restroom. This provision shall also apply where mirrors would compromise personal privacy. Privacy at water closets and urinals shall be provided in accordance with Sections 1210.3.1 and 1210.3.2.
Exception: Visual screening shall not be required for single-occupant toilet rooms with a lockable door.
[P] 1210.3.1 Water closet compartment. Each water closet utilized by the public or employees shall occupy a separate compartment with walls or partitions and a door enclosing the fixtures to ensure privacy.
Exceptions:
- Water closet compartments shall not be required in a single-occupant toilet room with a lockable door.
- Toilet rooms located in child day care facilities and containing two or more water closets shall be permitted to have one water closet without an enclosing compartment.
- This provision is not applicable to toilet areas located within Group I-3 occupancy housing areas.
[P] 1210.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches (305 mm) from and extend not less than 60 inches (1524 mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches (457 mm) or to a point not less than 6 inches (152 mm) beyond the outermost front lip of the urinal measured from the finished backwall surface, whichever is greater.
Exceptions:
- Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door.
- Toilet rooms located in child day care facilities and containing two or more urinals shall be permitted to have one urinal without partitions.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
-
▸ Chapter 12 — INTERIOR ENVIRONMENT
Overview- Section 1201 — GENERAL
- Section 1202 — VENTILATION
- Section 1203 — TEMPERATURE CONTROL
- Section 1204 — LIGHTING
- Section 1205 — YARDS OR COURTS
- Section 1206 — SOUND TRANSMISSION
- Section 1207 — ENHANCED CLASSROOM ACOUSTICS
- Section 1208 — INTERIOR SPACE DIMENSIONS
- Section 1209 — ACCESS TO UNOCCUPIED SPACES
- Section 1210 — TOILET AND BATHROOM REQUIREMENTS
- Section 1211 — UV GERMICIDAL IRRADIATION SYSTEMS
- Section 1212 — [HCD 1 & HCD 2]—GARAGE DOOR SPRINGS
- Section 1213 — [HCD 1]—POLLUTANT CONTROL
- Section 1214 — RESERVED
- Section 1215 — RESERVED
- Section 1216 — RESERVED
- Section 1217 — RESERVED
- Section 1218 — RESERVED
- Section 1219 — RESERVED
- Section 1220 — RESERVED
- Section 1221 — RESERVED
- Section 1222 — RESERVED
- Section 1223 — RESERVED
- Section 1224 — [OSHPD 1]—HOSPITALS
- Section 1225 — [OSHPD 2]-SKILLED NURSING AND INTERMEDIATE-CARE…
- Section 1226 — [OSHPD 3]-CLINICS
- Section 1227 — [OSHPD 4]-CORRECTIONAL TREATMENT CENTERS
- Section 1228 — [OSHPD 5]—ACUTE PSYCHIATRIC HOSPITALS
- Section 1229 — [OSHPD 6] — CHEMICAL DEPENDENCY RECOVERY HOSPIT…
- Section 1230 — [BSCC] — MINIMUM STANDARDS FOR JUVENILE FACILIT…
- Section 1231 — [BSCC] — LOCAL DETENTION
- Section 1232 — RESERVED
- Section 1233 — RESERVED
- Section 1234 — RESERVED
- Section 1235 — [DPH]—SANITARY CONTROL OF SHELLFISH (PLANTS AND…
- Section 1236 — [DPH]—LABORATORY ANIMAL QUARTERS
- Section 1237 — [DPH]—WILD ANIMAL QUARANTINE FACILITIES
- Section 1238 — RESERVED
- Section 1239 — RESERVED
- Section 1240 — [AGR]—MEAT AND POULTRY PROCESSING PLANTS
- Section 1241 — [AGR]—COLLECTION CENTERS AND FACILITIES
- Section 1242 — [AGR]—RENDERERS
- Section 1243 — [AGR]—HORSEMEAT AND PET FOOD ESTABLISHMENTS
- Section 1244 — RESERVED
- Section 1245 — RESERVED
- Section 1246 — RESERVED
- Section 1247 — RESERVED
- Section 1248 — RESERVED
- Section 1249 — RESERVED
- Section 1250 — [CA]—PHARMACIES
- Section 1251 — [CA]—VETERINARY PREMISES
- Section 1252 — [CA]—BARBER COLLEGES AND SHOPS
- Section 1253 — [CA]—SCHOOLS OF COSMETOLOGY, COSMETOLOGICAL EST…
- Section 1254 — [CA]—ACUPUNCTURE OFFICES
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING