Sec. 17.08.010. - Water service requirements.¶
(a) Minimum requirement. With respect to water service, the following water service requirements are hereby established and shall require that any new construction of habitable structures and accessory buildings over 1,000 square feet of interior additions or remodeling of habitable structures or accessory buildings which adds over 1,000 square feet within the City and for which a permit is required to be issued:
| Lot Size | Any Lot |
|---|---|
| Fire Flow Req. | 1,250 GPM |
| Duration Req. | Two Hours |
| Fire Hydrant Spacing | 500 Feet |
(b) Service. All such water service shall be connected to the existing domestic water service system.
(c) Computation of available fire flow shall be based upon a minimum of 20 pounds per square inch gauge of residual operation pressure remaining in the street main from which the flow is measured.
(d) The City Council may reduce the 1,250 GPM fire flow requirement upon the recommendation of the Planning Commission in exceptional circumstances and where the applicant proves to the satisfaction of the Council that the condition set forth in Chapter 4 of the Bradbury Zoning Code exist.