Section 513C — DETAILED SYSTEM DESIGN REQUIREMENTS

513C.1 Wall Anchorage.

San Francisco Building Inspection Commission Codes · edición 2022 · actualizado 2026-07-08 · San Francisco

Esta sección aún no está traducida y se muestra en inglés.

513C.1 Wall Anchorage.

513C.1.1 Anchor locations. All unreinforced masonry walls shall be anchored at the roof and floor levels as required in Section 510C.2. Ceilings of plaster, gypsum board or similar heavier materials, when not attached directly to roof or floor framing, and abutting masonry walls, shall be either anchored to the walls at a maximum spacing of 6 feet (1.829 m) or removed.

513C.1.2 Anchor requirements. Anchors shall consist of bolts installed through the wall as specified in Table 5C-E, or by an approved equivalent at a maximum anchor spacing of 6 feet (1.829 m). All existing wall anchors shall be secured to the joists to develop the required forces.

513C.1.3 Minimum wall anchorage. Anchorage of masonry walls to each floor or roof shall resist a minimum force determined in accordance with San Francisco Building Code Chapter 16 or 200 pounds per linear foot (298 kg/m), whichever is greater, acting normal to the wall at the level of the floor or roof. Anchor spacing shall not exceed 6 feet (1.829 m) on center. Existing through-the-wall anchors, if used, must meet the requirements of this chapter or must be upgraded.

513C.1.4 Anchors at corners. At the roof and floor levels, both shear and tension anchors shall be provided within 2 feet (0.609 m) horizontally from the inside of the corners of the walls.

513C.1.5 Anchors with limited access. When access to the exterior face of the masonry wall is prevented, wall anchors conforming to Item 4.b. in Table 5C-E may be used.

513C.1.6 Anchors at interior and party walls. When floor or roof framing aligns vertically at party and interior masonry walls, continuous anchors shall be utilized to directly connect the floor or roof framing on either side of the wall. Where the roof or floor framing is offset more than the least depth of any adjacent framing, the intervening wall section shall be investigated for cross wythe shear assuming that the diaphragm to wall tensions on either side of the wall are acting in opposite directions.