1013.1 General.

San Francisco Building Inspection Commission Codes · edición 2022 · actualizado 2026-07-08 · San Francisco

Esta sección aún no está traducida y se muestra en inglés.

1013.1 General. An installation for which a permit is required shall not be put into service until it has been [ ] certified by a licensed boiler contractor or inspected by an approved insuring company inspector and an operating permit has been issued.

It shall be the duty of the owner or his authorized representative to notify the Authority Having Jurisdiction that the installation [ ] has been certified or inspected. It also shall be the duty of the owner or his authorized representative to post in a conspicuous position on the installation a notice in substantially the following form: “Warning! This installation has not been inspected and approved by the Authority Having Jurisdiction and shall not be covered or concealed until so inspected and approved,” and it shall be unlawful for anyone other than the Authority Having Jurisdiction to

remove such notice. The Authority Having Jurisdiction shall require such tests as it deems necessary to determine that the installation [ ] complies with the provision of this section. Such tests shall be made by the owner or his authorized representative in the presence of the Authority Having Jurisdiction.

Exception: On installations designed and supervised by a registered professional engineer, the Authority Having Jurisdiction shall have the authority to permit inspection and testing by such registered design professional.

GoCodebook ofrece acceso público limitado, búsqueda, citas, explicación multilingüe e interpretación práctica de normas de construcción legalmente adoptadas. No sustituye a las publicaciones oficiales del ICC ni de los códigos de California.