Section 1003A — GENERAL REQUIREMENTS FOR SECURITY

1003A.2 Door assemblies.

San Francisco Building Inspection Commission Codes · edición 2022 · actualizado 2026-07-08 · San Francisco

Esta sección aún no está traducida y se muestra en inglés.

1003A.2 Door assemblies. Excluding main entry doors, all exterior swinging doors, and swinging interior and exterior entry doors, including assemblies and related hardware, which are directly accessible from the ground level or by stairs or by ramp, or from roof areas, or parking lot, or garage areas, shall meet the requirements of Grade 20 of ANSI/ASTM F476, Standard Test Methods for Security of Swinging Door Assemblies.

All such doors shall be self-closing continuously locked, and openable from the interior with no special effort or knowledge or key. Where electrically operated locks are used, they must be self-latching and locking and shall have manual release capability from the interior requiring no special effort or knowledge or key.

1003A.2.1 Main entrance. All main entry doors, including electrically operated main entry doors, shall be provided with a primary locking device. “Main entry doors” shall be defined as exterior doors leading directly into the lobby, registration areas or employee entrances.

1003A.2.2 Viewer. Each door shall be provided with a minimum 135-degree viewer which does not have sighting capability when viewed from the outside. Mounting height shall not exceed 58 inches (1473 mm).