CRC · California Residential Code
Regulators, Pressure Controls & Safety Devices
This hub orients readers to CRC requirements for water, gas and heating regulators, overpressure and relief devices and points to the primary code sections to consult.
Last reviewed: July 6, 2026
Overview
This area of the CRC organizes the requirements that keep residential water, gas and heating systems within safe operating pressures — including pressure‑reducing/regulating valves, overpressure protection, venting of regulator diaphragms, low‑pressure and back‑pressure protection, and safety relief devices. For potable water systems the code sets triggers and equipment standards (for example where static pressure exceeds 80 psi requires a pressure regulator and downstream expansion control) at §608.2 and related expansion‑tank and relief provisions at §608.3 .
Fuel‑gas pressure regulation, overpressure protection, detection of regulator failure and venting of diaphragm vents are covered in the fuel‑gas chapters adopted for residential use (see, e.g., §1208.15 and overpressure requirements in §1208.10) and in corresponding mechanical provisions for line regulators and overpressure devices at §1308.6–§1308.8 . Hydronic and heating equipment safety devices — pressure/temperature relief valves, discharge piping and installation rules — are addressed in the mechanical/hydronic chapters (for example §1206.1 and the discharge piping requirements in §1206.2) to ensure relief openings, materials and discharge routing prevent injury or damage .
These provisions are practical: they tell you when a regulator or relief device is required, how it must be installed and vented, how failures must be detectable, and what listings/specifications the devices must meet — so designers, installers and inspectors can choose compliant devices and layouts without guesswork. For specific installations consult the cited sections and the product manufacturer’s instructions referenced by those sections .
In this section
Code references
Grounded in the retrieved California Residential Code — click a citation to read the verbatim passage:
CRC § 1208.14.1 Medium relevance — show source text
1208.14.1 Special Local Conditions. Where local conditions include earthquake, tornado, unstable ground, or flood hazards, special consideration shall be given to increased strength and flexibility of piping supports and connections. [NFPA 54:5.13.2]
1208.15 Pressure Regulator and Pressure Control Venting. The venting of the atmospheric side of diaphragms in line pressure regulators, gas appliance regulators, and gas pressure limit controls shall be in accordance with all of the following:
(1) An independent vent pipe to the outdoors, sized in accordance with the device manufacturer’s instructions, shall be provided where the location of a device is such that a discharge of fuel gas will cause a hazard. For devices other than appliance regulators, vents are not required to be independent where the vents are connected to a common manifold designed in accordance with engineering methods to minimize backpressure in the event of diaphragm failure and such design is approved.
Exceptions:
(1) A regulator and vent limiting means combination listed as complying with CSA/ANSI Z21.80/CSA 6.22, shall not be required to be vented to the outdoors.
«
«
«
«
«
222 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
(2) A listed gas appliance regulator factory equipped with a vent limiting device is not required to be vented to the outdoors.
(2) Materials for vent piping shall be in accordance with Section 1208.5 through Section 1208.5.12.5.
(3) The vent terminus shall be designed to prevent the entry of water, insects, and other foreign matter that could cause blockage.
(4) Vent piping shall be installed to minimize static loads and bending moments placed on the regulators and gas pressure control devices.
(5) Vents shall terminate not less than 3 feet (914 mm) from a possible source of ignition.
(6) At locations where a vent termination could be submerged during floods or snow accumulations, an antiflood-type breather vent fitting shall be installed, or the vent terminal shall be located above the height of the expected flood waters or snow.
(7) Vent piping from pressure regulators and gas pressure controls shall not be connected to a common manifold
that serves a bleed line from a diaphragm-type gas valve.
[NFPA 54:5.14]
TABLE 1208.13
MANUAL GAS VALVE STANDARDS
[NFPA 54: TABLE 5.11]
1209.0 Excess Flow Valve.
1209.1 General. Where automatic excess flow valves are installed, they shall be listed in accordance with ANSI Z21.93/CSA 6.30 and shall be sized and installed in accor dance with the manufacturers’ instructions. [NFPA 54:5.12]
1210.0 Gas Piping Installation.
CRC § 1308.13.1 Medium relevance — show source text
1308.13.1 Special Local Conditions. Where local conditions include earthquake, tornado, unstable ground, or flood hazards, special consideration shall be given to increased strength and flexibility of piping supports and connections. [NFPA 54:5.13.2]
1308.14 Pressure Regulator and Pressure Control Venting. The venting of the atmospheric side of diaphragms in line pressure regulators, gas appliance regulators, and gas pressure limit controls shall be in accordance with all of the following:
(1) An independent vent pipe to the outdoors, sized in accordance with the device manufacturer’s instructions, shall be provided where the location of a device is such that a discharge of fuel gas will cause a hazard. For devices other than appliance regulators, vents are not required to be independent where the vents are connected to a common manifold designed in accordance with engineering methods to minimize backpressure in the event of diaphragm failure and such design is approved.
»
»
»
»
»
»
sure relieving valve or pressure limiting device inoperative, one of the following shall be accomplished:
(1) The valve shall be locked in the open position. Instruct authorized personnel in the importance of leaving the shutoff valve open and of being present while the shutoff valve is closed so that it can be locked in the open position before leaving the premises.
(2) Duplicate relief valves shall be installed, each having adequate capacity to protect the system, and arrange the isolating valves or three-way valve so that only one relief valve can be rendered inoperative at a time.
[NFPA 54:5.8.7] 1308.9.6 Discharge of Vents. The discharge stacks, vents, or outlet parts of all pressure relieving and pressure limiting devices shall be located so that gas is safely discharged to the outdoors. Discharge stacks or vents shall be designed to prevent the entry of water, insects, or other foreign material that could cause blockage. The discharge stack or vent line shall be at least the same size as the outlet of the pressure relieving device. [NFPA 54:5.8.8.1, 5.8.8.2] 1308.9.7 Size of Fittings, Pipe, and Openings. The fittings, pipe, and openings located between the system to be protected and the pressure relieving device shall be sized to prevent hammering of the valve and to prevent impairment of relief capacity. [NFPA 54:5.8.9] 1308.10 Backpressure Protection. Protective devices shall be installed as close to the equipment as practical where the design of equipment connected is such that air, oxygen, or standby gases could be forced into the gas supply system. Gas and air combustion mixers incorporating double diaphragm “zero” or “atmosphere” governors or regulators shall require no further protection unless connected directly to compressed air or oxygen at pressures of 5 psi (34 kPa) or more. [NFPA 54:5.9.1.1, 5.9.1.2]
1308.10.1 Protective Devices. Protective devices shall include but not be limited to the following:
(1) Check valves.
(2) Three-way valves (of the type that completely closes one side before starting to open the other side).
(3) Reverse flow indicators controlling positive shutoff valves.
CRC § 112.3 Medium relevance — show source text
(9) A device shall be provided that will automatically shut off the oil supply to the appliance if the oil pressure at the appliance inlet exceeds a gauge pressure of 8 psig (55 kPa). The device shall not be required under either of the following conditions:
(a) Where the distribution system is supplied from a gravity tank and the maximum hydrostatic head of oil in the tank is such that the oil pressure at the appliance inlet will not exceed a gauge pressure of 8 psig (55 kPa).
(b) Where a means is provided to automatically shut off the oil supply if the pressure-regulating device provided in accordance with Section D 112.3(8) fails to regulate the pressure as required.
(10) Only appliances equipped with primary safety controls specifically listed for the appliance shall be connected to a centralized oil distribution system. [NFPA 31:9.2.10 – 9.2.15]
2025 CALIFORNIA MECHANICAL CODE 407
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX D
D 113.0 Fuel Supply Systems Installation.
D 113.1 Flexible Gas Connector. Except for manufactured homes located on an all-weather wood, concrete, or concrete block foundation system or on a foundation constructed in accordance with the local building code or, in the absence of a local code, with a recognized model building code, each gas supply connector shall be listed for outside manufactured home use, shall be not more than 6 feet (1829 mm) in length, and shall have a capacity rating to supply the connected load.
[NFPA 501A:4.4.1]
D 113.2 Use of Approved Pipe and Fittings of Exten- sion. Where it is necessary to extend a manufactured home inlet to permit connection of the 6 foot (1829 mm) listed connector to the site gas outlet, the extension shall be of approved materials of the same size as the manufactured home inlet and shall be adequately supported at no more than 4 foot (1219 mm) intervals to the manufactured home. [NFPA 501A:4.4.2]
D 113.3 Mechanical Protection. All gas outlet risers, regulators, meters, valves, and other exposed equipment shall be protected against accidental damage. [NFPA 501A:4.4.3]
D 113.4 Special Rules on Atmospherically Con- trolled Regulators. Atmospherically controlled regulators shall be installed in such a manner that moisture cannot enter the regulator vent and accumulate above the diaphragm. Where the regulator vent is obstructed due to snow and icing conditions, shields, hoods, or other suitable devices shall be provided to guard against closing of the vent opening. [NFPA 501A:4.4.4.1 – 4.4.4.2]
D 113.5 Fuel Gas Piping Test. The manufactured home fuel gas piping system shall be tested only with air before it is connected to the gas supply. The manufactured home gas piping system shall be subjected to a pressure test with all appliance shutoff valves in their closed positions. [NFPA 501A:4.4.5]
D 113.5.1 Procedures. The fuel gas piping test shall consist of air pressure at not less than 10 inches water column or more than 14 inches water column (2.5 kPa to 3.5 kPa).
CRC § 5.9.2 Medium relevance — show source text
(1) Check valves.
(2) Three-way valves (of the type that completely closes one side before starting to open the other side).
(3) Reverse flow indicators controlling positive shutoff valves.
(4) Normally closed air-actuated positive shutoff pressure regulators. [NFPA 54:5.9.2] 1308.11 Low-Pressure Protection. A protective device shall be installed between the meter and the appliance or equipment if the operation of the appliance or equipment is such that it could produce a vacuum or a dangerous reduction in gas pressure at the meter. Such protective devices include, but are not limited to, mechanical, diaphragm-operated, or electrically operated low-pressure shutoff valves. [NFPA 54:5.10]
1308.12 Shutoff Valves. Shutoff valves shall be selected in
accordance with Table 1308.12. Shutoff valves of size 1 inch
(25 mm) National Pipe Thread and smaller shall be listed and labeled. Where used outdoors, such use shall be in accordance with the manufacturer’s recommendation. [NFPA 54:5.11]
«
«
282 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
Exceptions: (1) A regulator and vent limiting means combination listed as complying with CSA/ANSI Z21.80/CSA 6.22, shall not be required to be vented to the outdoors.
(2) A listed gas appliance regulator factory equipped with a vent limiting device is not required to be vented to the outdoors.
(2) Materials for vent piping shall be in accordance with Section 1308.4 through Section 1308.4.10.5. (3) The vent terminus shall be designed to prevent the entry of water, insects, and other foreign matter that could cause blockage. (4) Vent piping shall be installed to minimize static loads and bending moments placed on the regulators and gas pressure control devices.
(5) Vents shall terminate not less than 3 feet (914 mm) from a possible source of ignition. (6) At locations where a vent termination could be submerged during floods or snow accumulations, an antiflood-type breather vent fitting shall be installed, or the vent terminal shall be located above the height of the expected floodwaters or snow.
(7) Vent piping from pressure regulators and gas pressure controls shall not be connected to a common manifold that serves a bleed line from a diaphragm-type gas valve.
[NFPA 54:5.14]
1309.0 Excess Flow Valve.
1309.1 General. Where automatic excess flow valves are installed, they shall be listed in accordance with ANSI Z21.93/CSA 6.30 and shall be sized and installed in accordance with the manufacturers’ instructions. [NFPA 54:5.12]
1310.0 Gas Piping Installation. 1310.1 Piping Underground. Underground gas piping shall be installed with sufficient clearance from any other underground structure to avoid contact therewith, to allow maintenance, and to protect against damage from proximity to other structures. Underground plastic piping shall be installed with sufficient clearance or shall be insulated from any source of heat so as to prevent the heat from impairing the serviceability of the pipe.
CRC § 802.12.3 Medium relevance — show source text
802.12.3 Additional Devices. Appliances requiring controlled chimney draft shall be permitted to be equipped with listed double-acting barometric draft regulators installed and adjusted in accordance with the manufacturer’s instructions. [NFPA 54:12.13.4]
802.12.4 Location. Draft hoods and barometric draft
regulators shall be installed in the same room or enclosure as the appliance in such a manner as to prevent any difference in pressure between the hood or regulator and the combustion air supply. [NFPA 54:12.13.5]
802.12.5 Positioning. Draft hoods and draft regulators shall be installed in the position for which they were designed with reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the appliance or adjacent construction. The appliance and its draft hood shall be located so that the relief opening is accessible for checking vent operation. [NFPA 54:12.13.6]
802.12.6 Clearance. A draft hood shall be located so
that its relief opening is not less than 6 inches (152 mm) from any surface except that of the appliance it serves and the venting system to which the draft hood is connected. Where a greater or lesser clearance is indicated on the appliance label, the clearance shall not be less than that specified on the label. Such clearances shall not be reduced. [NFPA 54:12.13.7]
802.13 Manually Operated Dampers. A manually operated damper shall not be placed in any appliance vent connector. Fixed baffles and balancing baffles shall not be classified as manually operated dampers. Balancing baffles shall be mechanically locked in the desired position before
placing the appliance in service. Balancing baffles shall be listed in accordance with UL 378. [NFPA 54:12.14.1 – 12.14.3]
802.14 Automatically Operated Vent Dampers. An automatically operated vent damper shall be listed. [NFPA 54:12.15]
802.14.1 Listing. Automatically operated vent dampers for oil-fired appliances shall comply with UL 17. The automatic damper control shall comply with UL 378.
802.15 Obstruction of Flow. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney, or vent. The following shall not be considered as obstructions:
(1) Draft regulators and safety controls specifically listed for installation in venting systems and installed in accordance with the manufacturer’s installation instructions.
(2) Approved draft regulators and safety controls designed and installed in accordance with engineering methods.
(3) Listed heat reclaimers and automatically operated vent dampers installed in accordance with the manufacturers’ installation instructions.
(4) Vent dampers serving listed appliances installed in accordance with Section 803.1 or Section 803.2 or engineering methods.
(5) Approved economizers, heat reclaimers, and recuperators installed in venting systems of appliances not required to be equipped with draft hoods, provided the appliance manufacturer’s instructions cover the installation of such a device in the venting system and performance in accordance with Section 802.3 and Section
802.3.1 is obtained. [NFPA 54:12.16]
803.0 Sizing of Category I Venting Systems.
CRC § 5.9.1.1 Medium relevance — show source text
Gas and air combustion mixers incorporating double diaphragm “zero” or “atmosphere” governors or regulators shall require no further protection unless connected directly to compressed air or oxygen at pressures of 5 psi (34 kPa) or more. [NFPA 54:5.9.1.1 – 5.9.1.2]
1208.11.1 Protective Devices. Protective devices
shall include but not be limited to the following:
(1) Check valves.
(2) Three-way valves (of the type that completely closes one side before starting to open the other side).
(3) Reverse flow indicators controlling positive shutoff valves.
(4) Normally closed air-actuated positive shutoff pressure regulators. [NFPA 54:5.9.2]
1208.12 Low-Pressure Protection. A protective device shall be installed between the meter and the appliance or equipment if the operation of the appliance or equipment is such that it could produce a vacuum or a dangerous reduction in gas pressure at the meter. Such protective devices include, but are not limited to, mechanical, diaphragm-operated, or electrically operated low-pressure shutoff valves. [NFPA 54:5.10]
1208.13 Shutoff Valves. Shutoff valves shall be selected in
accordance with Table 1208.13. Shutoff valves of size 1 inch
(25 mm) National Pipe Thread and smaller shall be listed and labeled. Where used outdoors, such use shall be in accordance with the manufacturer’s recommendation. [NFPA 54:5.11]
1208.14 Expansion and Flexibility. Piping systems shall be designed to prevent failure from thermal expansion or contraction. [NFPA 54:5.13.1]
1208.14.1 Special Local Conditions. Where local conditions include earthquake, tornado, unstable ground, or flood hazards, special consideration shall be given to increased strength and flexibility of piping supports and connections. [NFPA 54:5.13.2]
1208.15 Pressure Regulator and Pressure Control Venting. The venting of the atmospheric side of diaphragms in line pressure regulators, gas appliance regulators, and gas pressure limit controls shall be in accordance with all of the following:
(1) An independent vent pipe to the outdoors, sized in accordance with the device manufacturer’s instructions, shall be provided where the location of a device is such that a discharge of fuel gas will cause a hazard. For devices other than appliance regulators, vents are not required to be independent where the vents are connected to a common manifold designed in accordance with engineering methods to minimize backpressure in the event of diaphragm failure and such design is approved.
Exceptions:
(1) A regulator and vent limiting means combination listed as complying with CSA/ANSI Z21.80/CSA 6.22, shall not be required to be vented to the outdoors.
«
«
«
«
«
222 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
(2) A listed gas appliance regulator factory equipped with a vent limiting device is not required to be vented to the outdoors.
(2) Materials for vent piping shall be in accordance with Section 1208.5 through Section 1208.5.12.5.
CRC § 1208.10.1 Medium relevance — show source text
1208.10.1 Overpressure Protection Required. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches water column (3.5 kPa) are required to be equipped with overpressure protection by Section 1208.8, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s installation instructions. [NFPA 54:5.8.2.2]
1208.10.2 Overpressure Protection Devices. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by this section independently of any other pressure control equipment in the piping system. [NFPA 54:5.8.2.3] 1208.10.3 Detection of Failure. Each gas piping system for which an overpressure protection device is required by this section shall be designed and installed so that a failure of the primary pressure control device(s) is detectable. [NFPA 54:5.8.2.4] 1208.10.4 Flow Capacity. If a pressure relief valve is used to meet the requirements of this section, it shall have a flow capacity such that the pressure in the protected system is maintained at or below the limits specified in Section 1208.10 under the following conditions:
(1) The line pressure regulator for which the relief valve is providing overpressure protection has failed wide
open.
(2) The gas pressure at the inlet of the line pressure regulator for which the relief valve is providing overpressure protection is not less than the regulator’s normal operating inlet pressure. [NFPA 54:5.8.2.5]
1208.11 Backpressure Protection. Protective devices shall be installed as close to the equipment as practical where the design of equipment connected is such that air, oxygen, or standby gases could be forced into the gas supply system.
Gas and air combustion mixers incorporating double diaphragm “zero” or “atmosphere” governors or regulators shall require no further protection unless connected directly to compressed air or oxygen at pressures of 5 psi (34 kPa) or more. [NFPA 54:5.9.1.1 – 5.9.1.2]
1208.11.1 Protective Devices. Protective devices
shall include but not be limited to the following:
(1) Check valves.
(2) Three-way valves (of the type that completely closes one side before starting to open the other side).
(3) Reverse flow indicators controlling positive shutoff valves.
(4) Normally closed air-actuated positive shutoff pressure regulators. [NFPA 54:5.9.2]
1208.12 Low-Pressure Protection. A protective device shall be installed between the meter and the appliance or equipment if the operation of the appliance or equipment is such that it could produce a vacuum or a dangerous reduction in gas pressure at the meter. Such protective devices include, but are not limited to, mechanical, diaphragm-operated, or electrically operated low-pressure shutoff valves. [NFPA 54:5.10]
1208.13 Shutoff Valves. Shutoff valves shall be selected in
accordance with Table 1208.13. Shutoff valves of size 1 inch
(25 mm) National Pipe Thread and smaller shall be listed and labeled. Where used outdoors, such use shall be in accordance with the manufacturer’s recommendation. [NFPA 54:5.11]
CRC § 507.3 Medium relevance — show source text
507.3 Appliance Support . . . . . . . . . . . . .88
507.4 Ground Support . . . . . . . . . . . . . . .88
507.5 Drainage Pan . . . . . . . . . . . . . . . . .88
507.6 Added or Converted
Equipment or Appliances . . . . . . . .88
507.7 Type of Gas(es) . . . . . . . . . . . . . . .88
507.8 Safety Shutoff Devices for Unlisted LP-Gas Appliance Used Indoors . . . . . . . . . . . . . . . . .89
507.9 Use of Air or Oxygen Under Pressure . . . . . . . . . . . . . . . . . . . . .89
507.10 Protection of Gas Appliances from Fumes or Gases other
than Products of Combustion . . . . .89
507.11 Process Air . . . . . . . . . . . . . . . . . . .89
507.12 Flammable Vapors . . . . . . . . . . . . .89
507.13 Installation in Residential Garages . . . . . . . . . . . . . . . . . . . . .89
507.14 Installation in Commercial Garages . . . . . . . . . . . . . . . . . . . . .89
507.15 Installation in Aircraft Hangars . . . .89
507.16 Venting of Flue Gases . . . . . . . . . .89
507.17 Extra Device or Attachment . . . . . .89
507.18 Addition to Existing System . . . . . .89
507.19 Avoiding Strain on Gas Piping . . . .89
507.20 Gas Appliance Pressure Regulators . . . . . . . . . . . . . . . . . . .89
507.21 Bleed Lines for Diaphragm-Type Valves . . . . . . . . . . . . . . . . . . . . . . .89
2025 CALIFORNIA PLUMBING CODE xxxi
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
TABLE OF CONTENTS
507.22 Combination of Appliances and Equipment . . . . . . . . . . . . . . . .90
507.23 Installation Instructions . . . . . . . . . .90
507.24 Protection of Outdoor
Appliances . . . . . . . . . . . . . . . . . . .90
507.25 Accessibility for Service . . . . . . . . .90
507.26 Clearance to Combustible
Materials . . . . . . . . . . . . . . . . . . . . .90
508.0 Appliances on Roofs, in Attics or Under-Floor Spaces . . . . . . . . . .90
508.1 General . . . . . . . . . . . . . . . . . . . . . .90
508.2 Installation of Appliances on Roofs . . . . . . . . . . . . . . . . . . . . .90
508.3 Appliances on Roofs . . . . . . . . . . .90
508.4 Appliances in Attics and Under-Floor Spaces . . . . . . . . . . . .91
CRC § 1308.6.1 Medium relevance — show source text
FUEL GAS PIPING
»
»
»
»»
»
»
»
»
»
1308.6.1 Listing. Line pressure regulators shall be listed in accordance with CSA/ANSI Z21.80/CSA 6.22
where the outlet pressure is set to 2 psi (14 kPa) or less.
[NFPA 54:5.7.2]
1308.6.2 Location. The gas pressure regulator shall be accessible for servicing. [NFPA 54:5.7.3]
1308.6.3 Regulator Protection. Pressure regulators shall be protected against physical damage. [NFPA 54:5.7.4]
1308.6.4 Regulator Vents. Regulator vents shall be in accordance with Section 1308.14. [NFPA 54:5.7.5]
1308.6.5 Identification. Line pressure regulators at multiple regulator installations shall be marked by a metal tag or other permanent means designating the building or the part of the building being supplied.
[NFPA 54:5.7.6]
1308.7 Overpressure Protection. Where the serving gas supplier delivers gas at a pressure greater than 2 psi for piping systems serving appliances designed to operate at a gas pressure of 14 inches water column or less, overpressure protection devices shall be installed. Piping systems serving equipment designed to operate at inlet pressures greater than 14 inches water column (3.5 kPa) shall be equipped with overpressure protection devices as required by the appliance manufacturer’s installation instructions. [NFPA 54:5.8.1]
1308.8 Pressure Limitation Requirements. Where piping systems serving appliances designed to operate with a gas supply pressure of 14 inches water column (3.5 kPa) or less are required to be equipped with overpressure protection by Section 1308.7, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance to 2 psi (14 kPa) or less upon a failure of the line pressure regulator. [NFPA 54:5.8.2.1]
1308.8.1 Overpressure Protection Required. Where piping systems serving appliances designed to operate with a gas supply pressure greater than 14 inches water column (3.5 kPa) are required to be equipped with overpressure protection by Section 1308.7, each overpressure protection device shall be adjusted to limit the gas pressure to each connected appliance as required by the appliance manufacturer’s installation instructions. [NFPA 54:5.8.2.2]
1308.8.2 Overpressure Protection Devices. Each overpressure protection device installed to meet the requirements of this section shall be capable of limiting the pressure to its connected appliance(s) as required by this section independently of any other pressure control equipment in the piping system. [NFPA 54:5.8.2.3]
1308.8.3 Detection of Failure. Each gas piping system for which an overpressure protection device is required by this section shall be designed and installed so that a failure of the primary pressure control device(s) is detectable. [NFPA 54:5.8.2.4]
1308.8.4 Flow Capacity. If a pressure relief valve is used to meet the requirements of this section, it shall
CRC § 607.5 Medium relevance — show source text
installation instructions. Such vent shall be screened with a cor rosion-resistant material of not less than number 24 mesh.
607.5 Overflow. Tanks shall have not less than a 16 square inch (0.01 m [2] ) overflow that is screened with a corrosionresistant material of not less than number 24 mesh.
607.6 Valves. Pressurized tanks shall be provided with a listed pressure-relief valve installed in accordance with the manufacturer’s installation instructions. The relief valve shall be discharged in accordance with Section 608.5. Where a potable water supply tank is located above the fixtures, appliances, or system components it serves, it shall be equipped with a vacuum relief valve that complies with ANSI Z21.22/CSA 4.4.
608.0 Water Pressure, Pressure Regulators, Pres- sure Relief Valves, and Vacuum Relief Valves. 608.1 Inadequate Water Pressure. Where the water pressure in the main or other source of supply will not provide a residual water pressure of not less than 15 pounds force per square inch (psi) (103 kPa), after allowing for friction and other pressure losses, a tank and a pump or other means that will provide said 15 psi (103 kPa) pressure shall be installed. Where fixtures, fixture fittings, or both are installed that, require a residual pressure exceeding 15 psi (103 kPa), that minimum residual pressure shall be provided.
608.2 Excessive Water Pressure. Where static water pressure in the water supply piping exceeds 80 psi (552 kPa), an approved-type pressure regulator preceded by an adequate strainer shall be installed and the static pressure reduced to 80 psi (552 kPa) or less. Pressure regulators for potable water distribution systems shall comply with ASSE 1003 or AWWA C530. Pressure regulator(s) equal to or exceeding 1 [1] ⁄ 2 inches (40 mm) shall not require a strainer. Such regulator(s) shall control the pressure to water outlets in the building unless otherwise approved by the Authority Having Jurisdiction. Each such regulator and strainer shall be accessibly located aboveground or in a vault equipped with a properly sized and sloped boresighted drain to daylight, shall be protected from freezing, and shall have the strainer readily accessible for cleaning without removing the regulator or strainer body or disconnecting the supply piping. Pipe size determinations shall be based on 80 percent of the reduced pressure where using Table 610.4.
An approved expansion tank shall be installed in the cold water distribution piping downstream of each such regulator to prevent pressure exceeding 80 psi from developing due to thermal expansion. Expansion tanks used in potable water systems intended to supply drinking water shall comply with NSF/ANSI/CAN 61. The expansion tank shall be properly sized, securely fastened to the structure, and installed in accordance with the manufacturer’s installation instructions and listing. Systems designed by a licensed plumbing contractor or registered design professionals shall be permitted to use approved pressure relief valves in lieu of expansion tanks provided such relief valves have a maximum pressure relief setting of 100 psi (689 kPa) or less. 608.3 Expansion Tanks, and Combination Tempera- **ture and Pressure-Relief Valves.
CRC § 403.13 Medium relevance — show source text
(a) Where the distribution system is supplied from a gravity tank and the maximum hydrostatic head of oil in the tank is such that the oil pressure at the appliance inlet will not exceed a gauge pressure of 8 psig (55 kPa).
(b) Where a means is provided to automatically shut off the oil supply if the pressure-regulating device provided in accordance with Section E 403.13(8) fails to regulate the pressure as required.
(10)Only appliances equipped with primary safety controls specifically listed for the appliance shall be connected to a centralized oil distribution system. [NFPA 31:9.2.10 – 9.2.15]
E 404.0 Fuel Supply Systems Installation.
E 404.1 Flexible Gas Connector. Except for manufactured homes located on an all-weather wood, concrete, or concrete block foundation system or on a foundation constructed in accordance with the local building code or, in the absence of a local code, with a recognized model building code, each gas supply connector shall be listed for outside manufactured home use, shall be not more than 6 feet (1829 mm) in length, and shall have a capacity rating to supply the connected load.
[NFPA 501A:4.4.1]
E 404.2 Use of Approved Pipe and Fittings of Exten- sion. Where it is necessary to extend a manufactured home inlet to permit connection of the 6 foot (1829 mm) listed connector to the site gas outlet, the extension shall be of approved materials of the same size as the manufactured home inlet and shall be adequately supported at no more than 4 foot (1219 mm) intervals to the manufactured home. [NFPA 501A:4.4.2]
2025 CALIFORNIA PLUMBING CODE 411
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
APPENDIX E
E 404.3 Mechanical Protection. All gas outlet risers, regulators, meters, valves, and other exposed equipment shall be protected against accidental damage. [NFPA 501A:4.4.3]
E 404.4 Special Rules on Atmospherically Con- trolled Regulators. Atmospherically controlled regulators shall be installed in such a manner that moisture cannot enter the regulator vent and accumulate above the diaphragm. Where the regulator vent is obstructed due to snow and icing conditions, shields, hoods, or other suitable devices shall be provided to guard against closing of the vent opening. [NFPA 501A:4.4.4.1 – 4.4.4.2]
E 404.5 Fuel Gas Piping Test. The manufactured home fuel gas piping system shall be tested only with air before it is connected to the gas supply. The manufactured home gas piping system shall be subjected to a pressure test with all appliance shutoff valves in their closed positions. [NFPA 501A:4.4.5]
E 404.5.1 Procedures. The fuel gas piping test shall consist of air pressure at not less than 10 inches water column or more than 14 inches water column (2.5 kPa to 3.5 kPa). The fuel gas piping system shall be isolated from the air pressure source and shall maintain this pressure for not less than 10 minutes without perceptible leakage.
CRC § 610.4. Medium relevance — show source text
** Where static water pressure in the water supply piping exceeds 80 psi (552 kPa), an approved-type pressure regulator preceded by an adequate strainer shall be installed and the static pressure reduced to 80 psi (552 kPa) or less. Pressure regulators for potable water distribution systems shall comply with ASSE 1003 or AWWA C530. Pressure regulator(s) equal to or exceeding 1 [1] ⁄ 2 inches (40 mm) shall not require a strainer. Such regulator(s) shall control the pressure to water outlets in the building unless otherwise approved by the Authority Having Jurisdiction. Each such regulator and strainer shall be accessibly located aboveground or in a vault equipped with a properly sized and sloped boresighted drain to daylight, shall be protected from freezing, and shall have the strainer readily accessible for cleaning without removing the regulator or strainer body or disconnecting the supply piping. Pipe size determinations shall be based on 80 percent of the reduced pressure where using Table 610.4.
An approved expansion tank shall be installed in the cold water distribution piping downstream of each such regulator to prevent pressure exceeding 80 psi from developing due to thermal expansion. Expansion tanks used in potable water systems intended to supply drinking water shall comply with NSF/ANSI/CAN 61. The expansion tank shall be properly sized, securely fastened to the structure, and installed in accordance with the manufacturer’s installation instructions and listing. Systems designed by a licensed plumbing contractor or registered design professionals shall be permitted to use approved pressure relief valves in lieu of expansion tanks provided such relief valves have a maximum pressure relief setting of 100 psi (689 kPa) or less. 608.3 Expansion Tanks, and Combination Tempera- ture and Pressure-Relief Valves. A water system provided with a check valve, backflow preventer, or other normally closed device that prevents dissipation of building pressure back into the water main, independent of the type of water heater used, shall be provided with an approved, listed, and adequately sized expansion tank or other approved device having a similar function to control thermal expansion. Prepressurized water expansion tanks shall comply with IAPMO/ANSI Z1088. Such expansion tank or other approved device shall be installed on the building side of the check valve, backflow preventer, or other device and shall be sized, securely fastened to the structure, and installed in accordance with the manufacturer’s installation instructions.
A water system containing storage water heating equipment shall be provided with an approved, listed, adequately sized combination temperature and pressure-relief valve, except for listed nonstorage instantaneous heaters having an inside diameter of not more than 3 inches (80 mm). Each such approved combination temperature and pressure-relief valve shall be installed on the water-heating device in an approved location based on its listing requirements and the manufacturer’s installation instructions. Each such combination temperature and pressure-relief valve shall be provided with a drain in accordance with Section 608.5.
Frequently asked questions
When is a pressure regulator required for potable water?
A pressure‑reducing regulator is required where static water pressure exceeds 80 psi; the code also requires an approved means to control thermal expansion downstream of that regulator (see §608.2–§608.3) .
What are the venting requirements for gas regulator diaphragms?
Line and appliance regulator diaphragm vents must be routed per the code so atmospheric discharge does not create a hazard; §1208.15 specifies independent venting to outdoors (or approved listed vent‑limited combinations) and minimum separation from ignition sources .
What must I know about relief valve discharge piping for boilers and hydronic systems?
Relief devices must discharge full‑size, without isolation, to an approved visible location or drain, sized and routed to prevent injury or property damage; see the mechanical requirements for relief/discharge piping and installation at §1206.1–§1206.2 .
More in California Residential Code
Ask about the CRC
Get cited, plain-English answers on the California Residential Code for your project — any code section, any scenario.
Start Free Trial