CRC · California Residential Code
Fuel‑Gas Systems
Fuel‑gas requirements for dwellings are governed by the California Mechanical and Plumbing Codes (not Part VI of the CRC); see §1301.1, §1303.1 (CMC) and §1201.1, §1213.6.2.1 (CPC) for scope, inspection, and purging.
Last reviewed: July 6, 2026
Overview
The California Residential Code does not adopt its own Fuel‑Gas (Part VI); fuel‑gas design, installation, testing, and inspection for dwellings are enforced through the California Mechanical Code and California Plumbing Code instead, so users must consult those Parts for binding requirements . The CMC establishes the scope and coverage for fuel‑gas piping (see §1301.1 and §1302.1) and sets procedures for inspection and testing (§1303.1) applicable to typical residential systems .
Key safety and performance topics — material and sizing rules, purging and gas‑leak detection, required gas supply, combustion air and venting — are found in the CPC and CMC. Examples include the CPC provisions for fuel‑gas piping scope and inspection (§1201.1, §1203.1), purging procedures and combustible‑gas detector requirements (§1213.6.2.1), and required gas‑supply sizing (§1214.0) . Both codes also reference national standards (NFPA 54, ANSI/CSA standards, etc.) that the codes incorporate for specific materials and appliances .
In this section
Code references
Grounded in the retrieved California Residential Code — click a citation to read the verbatim passage:
CRC § 1201.0 Medium relevance — show source text
1201.0 General.
1201.1 Applicability. The regulations of this chapter shall govern the installation of fuel gas piping in or in connection with a building, structure or within the property lines of premises up to 5 pounds-force per square inch (psi) (34 kPa) for natural gas and 10 psi (69 kPa) for undiluted propane, other than service pipe. Fuel oil piping systems connected to oil- burning equipment shall be installed in accordance with NFPA 31. Fuel oil piping systems connected to internal com- bustion engines and gas turbines shall be installed in accor- dance with NFPA 37.
1202.0 Coverage of Piping System. 1202.1 General. Coverage of piping systems shall extend from the point of delivery to the appliance connections. For other than undiluted liquefied petroleum gas (LP-Gas) systems, the point of delivery shall be the outlet of the service meter assembly or the outlet of the service regulator or service shutoff valve where no meter is provided. For undiluted LP-Gas systems, the point of delivery shall be considered to be the outlet of the final pressure regulator, exclusive of line gas regulators where no meter is installed. Where a meter is installed, the point of delivery shall be the outlet of the meter.
[NFPA 54:1.1.1.1(A)] 1202.2 Piping System Requirements. Requirements for piping systems shall include design, materials, components, fabrication, assembly, installation, testing, inspection, operation, and maintenance. [NFPA 54:1.1.1.1(E)] 1202.3 Applications. This chapter shall not apply to the following items:
(1) Portable LP-Gas appliances and equipment of all types that are not connected to a fixed fuel piping system.
(2) Installation of appliances such as brooders, dehydrators, dryers, and irrigation equipment used for agricultural
purposes.
(3) Raw material (feedstock) applications except for piping to special atmosphere generators.
(4) Oxygen-fuel gas cutting and welding systems.
(5) Industrial gas applications using such gases as acetylene and acetylenic compounds, hydrogen, ammonia, carbon monoxide, oxygen, and nitrogen.
(6) Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms, and natural gas processing plants.
(7) Large integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced by chemical reactions or used in chemical reactions.
(8) LP-Gas installations at utility gas plants.
(9) Liquefied natural gas (LNG) installations.
(10)Fuel gas piping in electric utility power plants.
(11)Proprietary items of equipment, apparatus, or instruments such as gas-generating sets, compressors, and calorimeters.
(12)LP-Gas equipment for vaporization, gas mixing, and gas manufacturing.
(13)LP-Gas piping for buildings under construction or renovations that is not to become part of the permanent building piping system—that is, temporary fixed piping for building heat.
(14)Installation of LP-Gas systems for railroad switch heating.
(15)Installation of LP-Gas and compressed natural gas (CNG) systems on vehicles.
(16)Gas piping, meters, gas pressure regulators, and other appurtenances used by the serving gas supplier in distribution of gas, other than undiluted LP-Gas.
CRC § 1.11.0. Medium relevance — show source text
This state agency does not adopt sections identified with the following symbol: † The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2025 CALIFORNIA MECHANICAL CODE 273
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
274 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 13
FUEL GAS PIPING
1301.0 Scope of Gas Piping.
1301.1 Applicability. The regulations of this chapter shall govern the installation of fuel gas piping in or in connection with a building, structure or within the property lines of premises up to 5 pounds-force per square inch (psi) (34 kPa) for natural gas and 10 psi (69 kPa) for undiluted propane, other than service pipe.
1302.0 Coverage of Piping System.
1302.1 General. Coverage of piping systems shall extend from the point of delivery to the appliance connections. For other than undiluted liquefied petroleum gas (LP-Gas) systems, the point of delivery shall be the outlet of the service meter assembly or the outlet of the service regulator or service shutoff valve where no meter is provided. For undiluted LP-Gas systems, the point of delivery shall be considered to be the outlet of the final pressure regulator, exclusive of line gas regulators where no meter is installed. Where a meter is installed, the point of delivery shall be the outlet of the meter.
[NFPA 54:1.1.1.1(A)]
1302.2 Piping System Requirements. Requirements for piping systems shall include design, materials, components, fabrication, assembly, installation, testing, inspection, operation, and maintenance. [NFPA 54:1.1.1.1(E)]
1302.3 Applications. This chapter shall not apply to the following items:
(1) Portable LP-Gas appliances and equipment of all types that are not connected to a fixed fuel piping system.
(2) Installation of appliances such as brooders, dehydrators, dryers, and irrigation equipment used for agricultural
purposes.
(3) Raw material (feedstock) applications except for piping to special atmosphere generators.
(4) Oxygen-fuel gas cutting and welding systems.
(5) Industrial gas applications using such gases as acetylene and acetylenic compounds, hydrogen, ammonia, carbon monoxide, oxygen, and nitrogen.
(6) Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms, and natural gas processing plants.
(7) Large integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced by chemical reactions or used in chemical reactions.
(8) LP-Gas installations at utility gas plants.
(9) Liquefied natural gas (LNG) installations.
(10)Fuel gas piping in electric utility power plants.
(11)Proprietary items of equipment, apparatus, or instruments such as gas-generating sets, compressors, and calorime ters.
(12)LP-Gas equipment for vaporization, gas mixing, and gas manufacturing.
CRC § 1.1.1.2 Medium relevance — show source text
(17)Building design and construction, except as specified herein.
(18)Fuel gas systems on recreational vehicles manufactured in accordance with NFPA 1192.
(19)Fuel gas systems using hydrogen as a fuel.
(20)Construction of appliances. {NFPA 54:1.1.1.2}
1203.0 Inspection.
1203.1 Inspection Notification. Upon completion of the installation, alteration, or repair of gas piping, and prior to the use thereof, the Authority Having Jurisdiction shall be notified that such gas piping is ready for inspection.
1203.2 Excavation. Excavations required for the installation of underground piping shall be kept open until the piping has been inspected and approved. Where such piping is covered or concealed before such approval, it shall be exposed upon the direction of the Authority Having Jurisdiction.
1203.3 Type of Inspections. The Authority Having Jurisdiction shall make the following inspections and either shall approve that portion of the work as completed or shall notify the permit holder wherein the same fails to be in accordance with this code.
1203.3.1 Rough Piping Inspection. This inspection shall be made after gas piping authorized by the permit has been installed and before such piping has been covered or concealed or fixture or appliance has been attached thereto. This inspection shall include a determination that the gas piping size, material, and installation meet the requirements of this code.
1203.3.2 Final Piping Inspection. This inspection shall be made after piping authorized by the permit has been installed, and after portions, thereof that are to be covered or concealed are so concealed, and before fixture, appliance, or shutoff valve has been attached thereto.
2025 CALIFORNIA PLUMBING CODE 215
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
This inspection shall comply with Section 1213.1. Test gauges used in conducting tests shall be in accordance with Section 318.0.
1203.4 Inspection Waived. In cases where the work authorized by the permit consists of a minor installation of additional piping to piping already connected to a gas meter, the preceding inspections shall be permitted to be waived at the discretion of the Authority Having Jurisdiction. In this event, the Authority Having Jurisdiction shall make such inspection as deemed advisable to be assured that the work has been performed in accordance with the intent of this code.
1204.0 Certificate of Inspection.
1204.1 Issuance. Whereupon final piping inspection, the installation is found to be in accordance with the provisions of this code, a certificate of inspection shall be permitted to be issued by the Authority Having Jurisdiction. 1204.2 Gas Supplier. A copy of the certificate of such final piping inspection shall be issued to the serving gas supplier supplying gas to the premises. 1204.3 Unlawful. It shall be unlawful for a serving gas supplier, or person is furnishing gas, to turn on or cause to be turned on, a fuel gas or a gas meter or meters, until such certificate of final inspection, as herein provided, has been issued.
1205.0 Authority to Render Gas Service.
CRC § 1.11.0. Medium relevance — show source text
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting Agency BSC BSC-
CGSFM HCD Col6 Col7 DSA Col9 Col10 OSHPD Col12 Col13 Col14 Col15 Col16 Col17 BSCC DPH AGR DWR CEC CA SL SLC Adopting Agency BSC BSC-
CGSFM 1 2 1-AC AC ** SS** ** SS/CC** 1 1R 2 3 4 5 6 6 6 6 6 6 6 6 6 Adopt Entire Chapter X X X X X X X X X X X X Adopt Entire Chapter as
amended (amended sections
listed below)Adopt only those sections
that are listed belowChapter/Section This state agency does not adopt sections identified with the following symbol: † The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2025 CALIFORNIA MECHANICAL CODE 273
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
274 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 13
FUEL GAS PIPING
1301.0 Scope of Gas Piping.
1301.1 Applicability. The regulations of this chapter shall govern the installation of fuel gas piping in or in connection with a building, structure or within the property lines of premises up to 5 pounds-force per square inch (psi) (34 kPa) for natural gas and 10 psi (69 kPa) for undiluted propane, other than service pipe.
1302.0 Coverage of Piping System.
CRC § 3.4.2 Medium relevance — show source text
Add 5 gpm to the flow rate required by Section_R309.3.4.2_ where the water service pipe supplies more than one dwelling.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section_R309.3.4.2_ where the water service pipe supplies more than one dwelling.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section_R309.3.4.2_ where the water service pipe supplies more than one dwelling.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section_R309.3.4.2_ where the water service pipe supplies more than one dwelling.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2.CRC § 1213.6.2.1 Medium relevance — show source text
1213.6.2.1 Purging Procedure. The piping system shall be purged in accordance with one or more of the following:
(1) The piping shall be purged with fuel gas and shall discharge to the outdoors.
(2) The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through an appliance burner not located in a combustion chamber. Such burner shall be provided with a continuous source of ignition.
(3) The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through a burner that has a continuous source of ignition and that is designed for such pur pose.
(4) The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Section 1213.6.2.2. Purging shall be stopped when fuel gas is detected.
(5) The piping shall be purged by the gas supplier in accordance with written procedures. [NFPA 54:8.3.2.1]
1213.6.2.2 Combustible Gas Detector. Com bustible gas detectors shall be listed and calibrated or tested in accordance with the manufacturer’s
instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas.
[NFPA 54:8.3.2.2]
1213.6.3 Purging Appliances and Equipment. After the piping system has been placed in operation, appliances and equipment shall be purged before being placed into operation. [NFPA 54:8.3.3]
1214.0 Required Gas Supply.
1214.1 General. The following regulations shall comply with this section and Section 1215.0, shall be the standard for the installation of gas piping. Natural gas regulations and tables are based on the use of a gas having a specific gravity of 0.60 and for undiluted liquefied petroleum gas, having a specific gravity of 1.50. Where gas of a different specific gravity is to be delivered, the specific gravity conversion factors provided by the serving gas supplier shall be used in sizing piping systems from the pipe sizing tables in this chapter.
1214.2 Volume. The hourly volume of gas required at each piping outlet shall be taken as not less than the maximum hourly rating as specified by the manufacturer of the appliance or appliances to be connected to each such outlet.
1214.3 Gas Appliances. Where the gas appliances to be installed have not been specified, Table 1208.3.1 shall be permitted to be used as a reference to estimate requirements of typical appliances. To obtain the cubic feet per hour (m [3] /h) of gas required, divide the input of the appliances by the average Btu (kW•h) heating value per cubic foot (m [3] ) of the gas. The average Btu (kW•h) per cubic foot (m [3] ) of the gas in the area of the installation shall be permitted to be obtained from the serving gas supplier.
1214.4 Size of Piping Outlets. The size of the supply piping outlet for a gas appliance shall be not less than [1] ⁄ 2 of an inch in diameter (15 mm).
The size of a piping outlet for a mobile home shall be not less than [3] ⁄ 4 of an inch in diameter (20 mm).
CRC § 17.4 Medium relevance — show source text
8|17.4|1.5|2.5|3.4|5.1|0.6|1.0|1.3|1.9| |10|7.7|13.1|17.8|26.3|2.3|3.8|5.2|7.7|0.8|1.4|2.0|2.9| |12|10.8|18.4|24.9|NP|3.2|5.4|7.3|10.7|1.2|2.0|2.7|4.0| |14|14.4|24.5|NP|NP|4.2|7.1|9.6|14.3|1.6|2.7|3.6|5.4| |16|18.4|NP|NP|NP|5.4|9.1|12.4|18.3|2.0|3.4|4.7|6.9| |18|22.9|NP|NP|NP|6.7|11.4|15.4|22.7|2.5|4.3|5.8|8.6| |20|27.8|NP|NP|NP|8.1|13.8|18.7|27.6|3.1|5.2|7.0|10.4| |22|NP|NP|NP|NP|9.7|16.5|22.3|NP|3.7|6.2|8.4|12.4| |24|NP|NP|NP|NP|11.4|19.3|26.2|NP|4.3|7.3|9.9|14.6| |26|NP|NP|NP|NP|13.2|22.4|NP|NP|5.0|8.5|11.4|16.9| |28|NP|NP|NP|NP|15.1|25.7|NP|NP|5.7|9.7|13.1|19.4| |30|NP|NP|NP|NP|17.2|NP|NP|NP|6.5|11.0|14.9|22.0| |32|NP|NP|NP|NP|19.4|NP|NP|NP|7.3|12.4|16.8|24.8| |34|NP|NP|NP|NP|21.7|NP|NP|NP|8.2|13.9|18.8|NP| |36|NP|NP|NP|NP|24.1|NP|NP|NP|9.1|15.4|20.9|NP| |For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2.CRC § 8.3.2.1 Medium relevance — show source text
(5) The piping shall be purged by the gas supplier in accordance with written procedures. [NFPA 54:8.3.2.1] 1313.6.2.2 Combustible Gas Detector. Combustible gas detectors shall be listed and calibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. [NFPA 54:8.3.2.2] 1313.6.3 Purging Appliances and Equipment. After the piping system has been placed in operation, appliances and equipment shall be purged before being placed into operation. [NFPA 54:8.3.3]
1314.0 Required Gas Supply. 1314.1 General. The following regulations, shall comply with this section and Section 1315.0, shall be the standard for the installation of gas piping. Natural gas regulations and tables are based on the use of gas having a specific gravity of 0.60 and for undiluted liquefied petroleum gas having a specific gravity of 1.50. Where gas of a different specific gravity is to be delivered, the serving gas supplier shall be permitted to be contacted for specific gravity conversion factors to use in sizing piping systems from the pipe sizing tables in this chapter. 1314.2 Volume. The hourly volume of gas required at each piping outlet shall be taken as not less than the maximum hourly rating as specified by the manufacturer of the appliance or appliances to be connected to each such outlet.
2025 CALIFORNIA MECHANICAL CODE 293
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
1314.3 Gas Appliances. Where the gas appliances to be installed have not been definitely specified, Table 1308.3.1 shall be permitted to be used as a reference to estimate requirements of typical appliances. To obtain the cubic feet per hour (m [3] /h) of gas required, divide the input of the appliances by the average Btu (kW•h) heating value per cubic foot (m [3] ) of the gas. The average Btu (kW•h) per cubic foot (m [3] ) of the gas in the area of the installation shall be permitted to be obtained from the serving gas supplier. 1314.4 Size of Piping Outlets. The size of the supply piping outlet for a gas appliance shall be not less than [1] ⁄ 2 of an inch (15 mm). The size of a piping outlet for a mobile home shall be not less than [3] ⁄ 4 of an inch (20 mm).
CRC § 605.11.1 Medium relevance — show source text
1,
605.11.1| |CSA B137.18-2020|Polyethylene of Raised Temperature Resistance (PE-RT)
Tubing Systems for Pressure Applications|Piping, Fittings|Table 604.1| |CSA B181.3-2021|Polyolefin and Polyvinylidene Fluoride (PVDF) Laboratory
Drainage Systems|Piping|811.2| |CSA B242-2005 (R2021)|Groove- and Shoulder-Type Mechanical Pipe Couplings|Fittings|Table 604.1| |CSA B481-2012 (R2017)|Grease Interceptors|Fixtures|Table 1009.1, 1014.1| |CSA/ANSI LC 1-2019/CSA
6.26-2019|Fuel Gas Piping Systems Using Corrugated Stainless Steel
Tubing|Fuel Gas|1208.5.3.5,
1210.4.1(4), 1211.3| |ANSI LC 4-2022/CSA 6.32-
2022|Press-Connect Metallic Fittings and Valves for Use in Fuel Gas
Distribution Systems|Fuel Gas|1208.4(2), 1208.5.9.1,
1208.5.9.2,
1208.5.9.3, Table
1208.13, 1210.4.1(3)| |CSA/ANSI Z21.10.1-
2019/CSA 4.1-2019|Gas Water Heaters, Volume I, Storage Water Heaters with Input
Ratings of 75,000 Btu Per Hour or Less|Fuel Gas, Appliances|Table 501.1(1)| |CSA/ANSI Z21.10.3-
2019/CSA 4.3-2019|Gas-Fired Water Heaters, Volume III, Storage Water Heaters
with Input Ratings Above 75,000 Btu Per Hour, Circulating
and Instantaneous|Fuel Gas, Appliances|Table 501.1(1)| |CSA/ANSI Z21.15-
2021/CSA 9.1-2021|Manually Operated Gas Valves for Appliances, Appliance
Connector Valves, and Hose End Valves|Fuel Gas|Table 1208.13| |CSA/ANSI Z21.18-
2019/CSA 6.3-2019|Gas Appliance Pressure Regulators|Gas Pressure
Regulators|507.20| |ANSI Z21.22-2015/CSA
4.4-2015 (R2020)|Relief Valves for Hot Water Supply Systems|Valves|607.6, 608.7| |ANSI Z21.24-2015/CSA
6.10-2015 (R2020)|Connectors for Gas Appliances|Fuel Gas|1212.1(3), 1212.2| |ANSI Z21.41-2014/CSA
6.9-2014 (R2019)|Quick Disconnect Devices for Use with Gas Fuel Appliances|Fuel Gas|1212.7| |CSA/ANSI Z21.54-
2019/CSA 8.4-2019|Gas Hose Connectors for Portable Outdoor Gas-Fired Appliances|Fuel Gas|1212.3.2| |ANSI Z21.69-2015/CSA
6.CRC § 7.3 Medium relevance — show source text
3|7.3|9.9|14.6| |26|NP|NP|NP|NP|13.2|22.4|NP|NP|5.0|8.5|11.4|16.9| |28|NP|NP|NP|NP|15.1|25.7|NP|NP|5.7|9.7|13.1|19.4| |30|NP|NP|NP|NP|17.2|NP|NP|NP|6.5|11.0|14.9|22.0| |32|NP|NP|NP|NP|19.4|NP|NP|NP|7.3|12.4|16.8|24.8| |34|NP|NP|NP|NP|21.7|NP|NP|NP|8.2|13.9|18.8|NP| |36|NP|NP|NP|NP|24.1|NP|NP|NP|9.1|15.4|20.9|NP| |For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section_R309.3.4.2_ where the water service pipe supplies more than one dwelling.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2. Add 5 gpm to the flow rate required by Section_R309.3.4.2_ where the water service pipe supplies more than one dwelling.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 0.063 L/s, 1 pound per square inch = 6.895 kPa.
NP = Not Permitted. Pressure loss exceeds reasonable limits.
a. Values are applicable for underground piping materials listed in_ the California Plumbing Code_ and are based on an SDR of 11 and a Hazen Williams C Factor of 150.
b. Values include the following length allowances for fittings: 25-percent length increase for actual lengths up to 100 feet and 15-percent length increase for actual lengths over
100 feet.
c. Flow rate from Section P2904.4.2.CRC § 1313.6.2 Medium relevance — show source text
1313.6.2 Piping Systems Allowed to be Purged Indoors or Outdoors. The purging of piping systems shall be in accordance with the provisions of Section 1313.6.2.1 where the piping system meets both of the following: (1) The design operating pressure is 2 psig (14 kPag) or less.
(2) The piping being purged is constructed entirely from pipe or tubing not meeting the size and length criteria of Table 1313.6.1. [NFPA 54:8.3.2] 1313.6.2.1 Purging Procedure. The piping system shall be purged in accordance with one or more of the following: (1) The piping shall be purged with fuel gas and shall discharge to the outdoors. (2) The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through an appliance burner not located in a combustion chamber. Such burner shall be provided with a continuous source of ignition. (3) The piping shall be purged with fuel gas and shall discharge to the indoors or outdoors through a burner that has a continuous source of ignition and that is designed for such purpose. (4) The piping shall be purged with fuel gas that is discharged to the indoors or outdoors, and the point of discharge shall be monitored with a listed combustible gas detector in accordance with Section 1313.6.2.2. Purging shall be stopped when fuel gas is detected. (5) The piping shall be purged by the gas supplier in accordance with written procedures. [NFPA 54:8.3.2.1] 1313.6.2.2 Combustible Gas Detector. Combustible gas detectors shall be listed and calibrated or tested in accordance with the manufacturer’s instructions. Combustible gas detectors shall be capable of indicating the presence of fuel gas. [NFPA 54:8.3.2.2] 1313.6.3 Purging Appliances and Equipment. After the piping system has been placed in operation, appliances and equipment shall be purged before being placed into operation. [NFPA 54:8.3.3]
1314.0 Required Gas Supply. 1314.1 General. The following regulations, shall comply with this section and Section 1315.0, shall be the standard for the installation of gas piping. Natural gas regulations and tables are based on the use of gas having a specific gravity of 0.60 and for undiluted liquefied petroleum gas having a specific gravity of 1.50. Where gas of a different specific gravity is to be delivered, the serving gas supplier shall be permitted to be contacted for specific gravity conversion factors to use in sizing piping systems from the pipe sizing tables in this chapter. 1314.2 Volume. The hourly volume of gas required at each piping outlet shall be taken as not less than the maximum hourly rating as specified by the manufacturer of the appliance or appliances to be connected to each such outlet.
2025 CALIFORNIA MECHANICAL CODE 293
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FUEL GAS PIPING
CRC § 10-13 Medium relevance — show source text
R1006.5 Outlet. The exterior air outlet shall be located in the back or side of the firebox chamber or shall be located outside of the firebox, at the level of the hearth and not greater than 24 inches (610 mm) from the firebox opening. The outlet shall be closable and designed to prevent burning material from dropping into concealed combustible spaces.
2025 CALIFORNIA RESIDENTIAL CODE 10-13
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
10-14 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Part IV—Energy Conservation
(Note: Part IV is not adopted. See California Energy Code, Title 24, Part 6.)
2025 CALIFORNIA RESIDENTIAL CODE 11-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
11-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Part V—Mechanical
(Note: Part V is not adopted. See California Mechanical Code, Title 24, Part 4.)
2025 CALIFORNIA RESIDENTIAL CODE 12-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Part VI—Fuel Gas
(Note: Part VI is not adopted. See California Mechanical Code and California Plumbing Code, Title 24, Parts 4 and 5.)
2025 CALIFORNIA RESIDENTIAL CODE 24-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
24-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Part VII—Plumbing
(Note: Part VII is not adopted. See California Plumbing Code, Title 24, Part 5.)
2025 CALIFORNIA RESIDENTIAL CODE 25-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
25-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Part VIII—Electrical
(Note: Part VIII is not adopted. See California Electrical Code, Title 24, Part 3.)
2025 CALIFORNIA RESIDENTIAL CODE 34-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
34-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA RESIDENTIAL CODE – MATRIX ADOPTION TABLE
CHAPTER 44 – REFERENCED STANDARDS
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
|Adopting
Frequently asked questions
Where are fuel‑gas requirements for residences located if Part VI of the CRC is not adopted?
The CRC directs users to the California Mechanical Code for fuel‑gas piping and the California Plumbing Code for fuel‑gas piping and appliance connections; Part VI of the CRC itself is not adopted, so consult the CMC and CPC for the operative rules .
Which sections cover inspection, testing and purging of gas piping?
Inspection and testing procedures appear in the CMC (§1303.1) and CPC (rough and final piping inspections, §1203.1), and purging/combustible‑gas detection procedures are set out in CPC §1213.6.2.1 (and parallel CMC provisions) .
Where do I find rules about combustion air and venting for gas appliances?
Combustion air and venting requirements are covered in the Mechanical Code chapters that address combustion air (Chapter 7) and chimneys/vents (Chapter 8) and are part of the CMC guidance for appliance installation and vent system design .
More in California Residential Code
Ask about the CRC
Get cited, plain-English answers on the California Residential Code for your project — any code section, any scenario.
Start Free Trial