CRC · California Residential Code

What is a 'Guard' (or 'Guardrail')?

A guard (or guardrail) is the barrier required at open edges of elevated walking surfaces to prevent falls. Under the California Residential Code a guard is required where the surface is more than 30 inches above the level below (checked within 36 inches horizontally), must normally be 42 inches high, must not allow a 4‑inch sphere to pass through openings, and must be attached and sized to meet the code’s load and deck‑support requirements.

Last reviewed: July 6, 2026

What the code requires — 2–4 sentences

A Guard (or Guardrail) is the building component placed at the open edges of elevated walking surfaces to minimize the possibility of a fall. That definition appears in § R202. Required guards are described in § R321.1 — generally a guard is required where an open‑sided walking surface is located more than 30 inches above the level below (with the 30‑inch trigger measured vertically and checked within 36 inches horizontally to the edge) and required guards must meet the height, opening and load rules in § R321.1 and related provisions.

A guard is the barrier required at the open side of a deck, balcony, porch, ramp, landing or stair that is high enough and strong enough to prevent people (and small children) from falling off an elevated walking surface.

Requirements in detail

Definition (what a guard is)

  • Guard / GuardrailA building component or a system of building components located near the open sides of elevated walking surfaces that minimizes the possibility of a fall from the walking surface to the lower level. See § R202.

When a guard is required (trigger)

  • Guards are required for open‑sided walking surfaces (floors, stairs, ramps, landings, porches, balconies, etc.) that are located more than 30 inches (762 mm) measured vertically to the floor or grade below at any point within 36 inches (914 mm) horizontally to the open edge. Insect screening is not a guard. See § R321.1.1.

Minimum heights and measurement points

  • Required guards at open‑sided walking surfaces: not less than 42 inches (1067 mm) measured vertically above the adjacent walking surface (or the line connecting the nosings on stairs). See § R321.1.2.
  • Exception (stair open sides in most detached dwellings / dwelling units): stair guards may be 34 inches (864 mm) (measured from the line connecting nosings); when the top of the guard also serves as a handrail on open sides of stairs, the height is 34–38 inches (864–965 mm). See § R321.1.2 Exception(s).

Opening (infill) limitations

  • Guards shall not have openings from the walking surface to the required guard height that allow passage of a sphere 4 inches (102 mm) in diameter. See § R321.1.3.
  • Exceptions: triangular openings at the open side of stairs (formed by riser, tread and bottom rail) may not allow passage of a 6‑inch (153 mm) sphere; open‑side stairs have a slightly larger stair‑opening exception of 4 3/8 inches (111 mm) in some stair locations. See § R321.1.3 Exception(s).

Structural strength and loads

  • Guard systems and components must be constructed to the live‑load and concentrated‑load rules in the code. The CRC live‑load table identifies the concentrated and uniform loads that apply to guards, handrails and guard in‑fill components: e.g., Guards — concentrated load 200 lb and Guard in‑fill components — concentrated 50 lb (see Table in § R301.5 and its footnotes for the specific numbers and application rules). See § R301.5.
  • Exterior guards (decks) must be constructed to meet § R301.5 and § R321, and must transfer guard loads to the deck framing with a continuous load path to the deck joists. See § R507.10 and § R507.10.1. Additional deck‑attachment details, 4×4 post rules (no notching where they support top-of-guard loads), and manufacturer/engineering directions are in § R507.10.2 and following.

Material & special guard types

  • Plastic composite guards and certain glass elements are specifically addressed (comply with referenced sections). See § R321.1.4 and the cross‑references in § R507.10.

Quick decision table (decision‑relevant dimensions / values)

Question / dimension Value(s) to use Code Reference
Vertical trigger to require a guard > 30 inches (762 mm) (measured vertically) within 36 inches (914 mm) horizontally to open edge § R321.1.1
Required guard height (general) 42 inches (1067 mm) (measured vertically above walking surface) § R321.1.2
Guard height exception — open side of stairs 34 inches (864 mm) (nosings line measurement) § R321.1.2 Exception
Guard height when top serves as handrail on stair 34–38 inches (864–965 mm) (from nosing line) § R321.1.2 Exception
Opening (infill) maximum sphere 4 inches (102 mm) (general) § R321.1.3
Opening exceptions (triangular at open‑side stairs) 6 inches (153 mm) triangular § R321.1.3 Exception
Load — concentrated on guard top (design) 200 lb concentrated (see table/footnotes) § R301.5 (Table/footnote)
Load — guard in‑fill components 50 lb concentrated on 1 sq ft area (design of balusters/panel fill) § R301.5 (Table/footnote)
Exterior / deck guard support requirement Guard loads transferred to deck framing with a continuous load path to adjacent joists; follow manufacturer or engineered details § R507.10 & § R507.10.1

Exceptions & special cases

  • Stairs: lower guard heights are allowed on open stair sides (see § R321.1.2 exceptions). Measure from the line connecting the nosings for stair height.
  • Insect screening is explicitly not a guard — screening does not satisfy the guard requirement. See § R321.1.1.
  • Balconies/portions of occupiable roofs less than 30 inches to an adjacent unoccupiable area may be treated differently where approved guards or barriers are provided at the perimeter — see the related CBC/CRC cross‑references for rooftop and assembly special cases. (See § R321.1 notes/related sections.)
  • Plastic composite guards and glazing used in guards have additional referenced requirements; follow the cited sections (e.g., § R321.1.4 and Table/footnotes in § R301.5).

If you have a nonstandard guard (glass panels, cable systems, engineered glass handrail assemblies, etc.) the code still requires the same height/opening/load performance — these systems must be demonstrated to meet the applicable load and opening limitations in the code or be engineered to accepted standards. See § R301.5, § R321 and § R507.10.

Common mistakes

  • Measuring guard height from the wrong reference point — on stairs the code requires measurement from the line connecting nosings, not the landing. See § R321.1.2.
  • Assuming insect screening is a guard (it is not). See § R321.1.1.
  • Allowing openings (baluster spacing, horizontal rails, cable rail systems) that permit a 4‑inch sphere to pass — common with modern horizontal cable rails. See § R321.1.3.
  • Failing to design balusters/panel infill to resist the required concentrated 50‑lb component load (baluster infill load). See § R301.5 footnote.
  • Connecting guards to a single joist with end‑grain fasteners only (risk of rotation) — deck guards must transfer loads to framing with a continuous load path; do not rely on withdrawal from end grain. See § R507.10.1 and § R507.10.1.1.
  • Not following the specific 4×4 post rule for deck guards — posts that are 4"×4" carrying top‑of‑guard loads must not be notched at their supporting connection. See § R507.10.2.

Worked example — balcony at second floor

Scenario: A homeowner has a second‑floor balcony whose finished walking surface is 10 feet (120 inches) above grade. The balcony edge is open to the yard, no screens.

Step 1 — Is a guard required?

  • Yes. The vertical distance (120") is > 30 inches, and the open edge is the walking surface edge; § R321.1.1 applies so a guard is required.

Step 2 — What height is required?

  • General rule: 42 inches measured vertically above the balcony walking surface. So install a guard whose top is 42" above the finished walking surface. If this were an open side of a stair instead, the permitted stair height could be 34". See § R321.1.2.

Step 3 — What about baluster spacing / openings?

  • Any opening from the walking surface to the required guard height must not allow a 4‑inch diameter sphere to pass. Design baluster spacing or panel infill accordingly (use spacing and profiles that block a 4" sphere). See § R321.1.3.

Step 4 — Strength & connections for a deck guard

  • The guard top and handrail should be capable of the code required concentrated load (see § R301.5 — concentrated guard load 200 lb; guard infill components 50 lb). For a deck, make sure the guard loads are transferred to the deck framing (continuous load path to joists), and follow the R507.10 connection rules (no relying on end grain withdrawal; 4×4 posts supporting loads must not be notched). See § R301.5 and § R507.10.

Related provisions (CRC sections)

  • § R202 — Definitions (Guard / Guardrail).
  • § R321.1.1 — Where guards are required (trigger).
  • § R321.1.2 — Guard height and stair exceptions.
  • § R321.1.3 — Opening limitations (4‑inch sphere rule and exceptions).
  • § R321.1.4 — Plastic composite and referenced requirements.
  • § R301.5 — Live loads / concentrated loads table (guard and guard in‑fill loads).
  • § R507.10 — Exterior guards on decks: construction, support and connection requirements.

If you want, I can: (a) review a photo or dimensioned sketch of your existing guard and say whether it meets the CRC criteria above; or (b) produce a simple detail drawing checklist for a deck guard post and connection that satisfies § R507.10 and the load requirements in § R301.5.

Code references

Grounded in the retrieved California Residential Code — click a citation to read the verbatim passage:

  • CRC § 1030.17.2. High relevance — show source text

    Exceptions: Guards are not required for the following locations:

    1. On the loading side of loading docks or piers.
    2. On the audience side of stages and raised platforms, including stairs leading up to the stage and raised platforms.
    3. On raised stage and platform floor areas, such as runways, ramps and side stages used for entertainment or presentations.
    4. At vertical openings in the performance area of stages and platforms.
    5. At elevated walking surfaces appurtenant to stages and platforms for access to and utilization of special lighting or equipment.
    6. Along vehicle service pits not accessible to the public.
    7. In assembly seating areas at cross aisles in accordance with Section 1030.17.2.
    8. On the loading side of station platforms on fixed guideway transit or passenger rail systems.

    2025 CALIFORNIA BUILDING CODE 10-37

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    1. Portions of an occupiable roof located less than 30 inches (762 mm) measured vertically to adjacent unoccupiable roof areas where approved guards are present at the perimeter of the roof.
    2. At portions of an occupiable roof where an approved barrier is provided. 11. Elevated facility observation station access hatches at detention facilities.

    1015.2.1 Glazing. Where glass is used to provide a guard or as a portion of the guard system, the guard shall comply with Section 2407. Where the glazing provided does not meet the strength and attachment requirements of Section 1607.9, complying guards shall be located along glazed sides of open-sided walking surfaces.

    1015.3 Height. Required guards shall be not less than 42 inches (1067 mm) high, measured vertically as follows:

    1. From the adjacent walking surfaces.
    2. On stairways and stepped aisles, from the line connecting the nosings.
    3. On ramps and ramped aisles, from the ramp surface at the guard.

    Exceptions:

    1 . For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R-2, guards on the open sides of stairs shall have a height not less than 34 inches (864 mm) measured vertically from a line connecting the nosings. 2 . For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R-2, where the top of the guard serves as a handrail on the open sides of stairs, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from a line connecting the nosings. 3 . The guard height in assembly seating areas shall comply with Section 1030.17 as applicable. 4 . Along alternating tread devices and ships ladders, guards where the top rail serves as a handrail shall have height not less than 30 inches (762 mm) and not more than 34 inches (864 mm), measured vertically from a line connecting the leading edge of the treads. 5 . In Group F occupancies where exit access stairways serve fewer than three stories and such stairways are not open to the public, and where the top of the guard also serves as a handrail, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from a line connecting the nosings.

  • CRC § 0.01 Medium relevance — show source text
    1. Type II. Handrails with a perimeter greater than 6 [1] / 4 inches (160 mm) shall have a graspable finger recess area on both sides of the profile. The finger recess shall begin within [3] / 4 inch (19 mm) measured vertically from the tallest portion of the profile and have a depth of not less than [5] / 16 inch (8 mm) within [7] / 8 inch (22 mm) below the widest portion of the profile. This required depth shall continue for not less than [3] / 8 inch (10 mm) to a level that is not less than 1 [3] / 4 inches (45 mm) below the tallest portion of the profile. The width of the handrail above the recess shall be not less than 1 [1] / 4 inches (32 mm) and not more than 2 [3] / 4 inches (70 mm). Edges shall have a radius of not less than 0.01 inch (0.25 mm).

    R320.7 Exterior plastic composite handrails. Plastic composite exterior handrails shall also comply with the requirements of Section R507.2.2.

    SECTION R321—GUARDS AND WINDOW FALL PROTECTION

    R321.1 Guards. Guards shall be provided in accordance with Sections R321.1.1 through R321.1.4.

    R321.1.1 Where required. Guards shall be provided for those portions of open-sided walking surfaces, including floors, stairs, ramps and landings that are located more than 30 inches (762 mm) measured vertically to the floor or grade below at any point within 36 inches (914 mm) horizontally to the edge of the open side. Insect screening shall not be considered as a guard.

    R321.1.2 Height. Required guards at open-sided walking surfaces, including stairs, porches, balconies or landings, shall be not less than 42 inches (1067 mm) in height as measured vertically above the adjacent walking surface or the line connecting the nosings.

    Exceptions:

    1. Guards on the open sides of stairs shall have a height of not less than 34 inches (864 mm) measured vertically from a line connecting the nosings.

    2025 CALIFORNIA RESIDENTIAL CODE 3-67

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    BUILDING PLANNING

    1. Where the top of the guard serves as a handrail on the open sides of stairs, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) as measured vertically from a line connecting the nosings.

    R321.1.3 Opening limitations. Required guards shall not have openings from the walking surface to the required guard height that allow passage of a sphere 4 inches (102 mm) in diameter.

    Exceptions:

    1. The triangular openings at the open side of stair, formed by the riser, tread and bottom rail of a guard, shall not allow passage of a sphere 6 inches (153 mm) in diameter.
    2. Guards on the open side of stairs shall not have openings that allow passage of a sphere 4 [3] / 8 inches (111 mm) in diameter.

    R321.1.4 Exterior plastic composite guards. Plastic composite exterior guards shall comply with the requirements of Section R507.2.2.

  • CRC § 2-14 Medium relevance — show source text

    [MP] GRAYWATER. Waste discharged from lavatories, bathtubs, showers, clothes washers and laundry trays.

    [MP] GRIDDED WATER DISTRIBUTION SYSTEM. A water distribution system where every water distribution pipe is interconnected so as to provide two or more paths to each fixture supply pipe.

    [RB] GROSS AREA OF EXTERIOR WALLS. The normal projection of all exterior walls, including the area of all windows and doors installed therein.

    [MP] GROUND-SOURCE HEAT PUMP LOOP SYSTEM. Piping buried in horizontal or vertical excavations or placed in a body of water for the purpose of transporting heat transfer liquid to and from a heat pump. Included in this definition are closed loop systems in which the liquid is recirculated and open loop systems in which the liquid is drawn from a well or other source.

    [RB] GUARD OR GUARDRAIL . A building component or a system of building components located near the open sides of elevated walking surfaces that minimizes the possibility of a fall from the walking surface to the lower level.

    [RB] GUESTROOM. Any room or rooms used or intended to be used by one or more guests for living or sleeping purposes.

    [RB] GYPSUM BOARD. A type of gypsum panel product consisting of a noncombustible core primarily of gypsum with paper surfacing.

    [RB] GYPSUM PANEL PRODUCT. The general name for a family of sheet products consisting essentially of gypsum complying with the standards specified in Section R702.3 and Chapter 44 of this code.

    [RB] GYPSUM SHEATHING. Gypsum panel products specifically manufactured with enhanced water resistance for use as a substrate for exterior surface materials.

    [RB] GYPSUM WALLBOARD. A gypsum board used primarily as interior surfacing for building structures.

    [RB] HABITABLE SPACE. A space in a building for living, sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not considered habitable spaces.

    2-14 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    DEFINITIONS

    [RB] HANDRAIL. A horizontal or sloping rail intended for grasping by the hand for guidance or support.

    [MP] HANGERS. See “Supports.”

    [MP] HAZARDOUS LOCATION. Any location considered to be a fire hazard for flammable vapors, dust, combustible fibers or other highly combustible substances.

    [MP] HEAT PUMP. A refrigeration system or factory-made appliance that utilizes refrigerant to transfer heat into a space or substance.

    [RB] HEIGHT, BUILDING. The vertical distance from grade plane to the average height of the highest roof surface.

    [RB] HEIGHT, STORY. The vertical distance from top to top of two successive tiers of beams or finished floor surfaces; and, for the topmost story, from the top of the floor finish to the top of the ceiling joists or, where there is not a ceiling, to the top of the roof rafters.

    [MP] HIGH-TEMPERATURE (H.T.) CHIMNEY. A high-temperature chimney complying with the requirements of UL 103. A Type H.T. chimney is identifiable by the markings “Type H.T.” on each chimney pipe section.

  • CRC § 5-42 Medium relevance — show source text

    5-42 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FLOORS

    FIGURE R507.9.2(1)—DECK ATTACHMENT FOR LATERAL LOADS

    WATER-PROTECTIVE BARRIER

    LAPPED OVER FLASHING

    "Z" FLASHING (SHOWN) OR "L" FLASHING (OPTIONAL)

    HOLD-DOWN OR SIMILAR DEVICE

    ATTACHED TO ADJACENT JOISTS

    PER MANUFACTURER

    LAG SCREWS OR BOLTS STAGGARED

    APPROVED JOIST HANGER

    For SI: 1 inch = 25.4 mm.

    FIGURE R507.9.2(2)—DECK ATTACHMENT FOR LATERAL LOADS

    WATER-RESISTING BARRIER

    LAPPED OVER FLASHING

    "L" FLASHING (SHOWN) OR "Z" FLASHING (OPTIONAL)

    APPROVED JOIST HANGERS

    LAG SCREWS OR BOLTS STAGGERED

    HOLD-DOWN DEVICE MIN 750 LB. CAPACITY AT 4 LOCATIONS, EVENLY DISTRIBUTED ALONG DECK AND ONE WITHIN 24" OF EACH

    END OF THE LEDGER. HOLD-DOWN DEVICES

    SHALL FULLY ENGAGE DECK JOIST PER

    HOLD-DOWN MANUFACTURER. ATTACHED TO

    TOP PLATE STUDS OR HEADER WITH A FULLY

    THREADED 3/8" DIAMETER LAG SCREW

    PREDRILLED W/ MIN. 3" PENETRATION

    For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

    2025 CALIFORNIA RESIDENTIAL CODE 5-43

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FLOORS

    R507.10 Exterior guards. Guards shall be constructed to meet the requirements of Sections R301.5 and R321, and this section.

    R507.10.1 Support of guards. Where guards are supported on deck framing, guard loads shall be transferred to the deck framing with a continuous load path to the deck joists.

    R507.10.1.1 Guards supported by side of deck framing. Where guards are connected to the interior or exterior side of a deck joist or beam, the joist or beam shall be connected to the adjacent joists to prevent rotation of the joist or beam. Connections relying only on fasteners in end grain withdrawal are not permitted.

    R507.10.1.2 Guards supported on top of deck framing. Where guards are mounted on top of the decking, the guards shall be connected to the deck framing or blocking and installed in accordance with manufacturer’s instructions to transfer the guard loads to the adjacent joists.

    R507.10.2 Wood posts at deck guards. Where 4-inch by 4-inch (102 mm by 102 mm) wood posts support guard loads applied to the top of the guard, such posts shall not be notched at the connection to the supporting structure.

    R507.10.3 Plastic composite guards. Plastic composite guards shall comply with the provisions of Section R507.2.2.

    R507.10.4 Other guards. Other guards shall be in accordance with either manufacturer’s instructions or accepted engineering principles.

    5-44 2025 CALIFORNIA RESIDENTIAL CODE

  • CRC § 1030.17.1 Medium relevance — show source text

    1030.17.1 Perimeter guards. Perimeter guards shall be provided where the footboards or walking surface of seating facilities are more than 30 inches (762 mm) above the floor or grade below. Where the seatboards are adjacent to the perimeter, guard height shall be 42 inches (1067 mm) high minimum, measured from the seatboard. Where the seats are self-rising, guard height shall be 42 inches (1067 mm) high minimum, measured from the floor surface. Where there is an aisle between the seating and the perimeter, the guard height shall be measured in accordance with Section 1015.3.

    Exceptions:

    1. Guards that impact sightlines shall be permitted to comply with Section 1030.17.3.
    2. Bleachers, grandstands and folding and telescopic seating shall not be required to have perimeter guards where the seating is located adjacent to a wall and the space between the wall and the seating is less than 4 inches (102 mm).

    1030.17.2 Cross aisles. Cross aisles located more than 30 inches (762 mm) above the floor or grade below shall have guards in accordance with Section 1015.

    Where an elevation change of 30 inches (762 mm) or less occurs between a cross aisle and the adjacent floor or grade below, guards not less than 26 inches (660 mm) above the aisle floor shall be provided.

    Exception: Where the backs of seats on the front of the cross aisle project 24 inches (610 mm) or more above the adjacent floor of the aisle, a guard need not be provided.

    1030.17.3 Sightline-constrained guard heights. Unless subject to the requirements of Section 1030.17.4, a fascia or railing system in accordance with the guard requirements of Section 1015 and having a minimum height of 26 inches (660 mm) shall be provided where the floor or footboard elevation is more than 30 inches (762 mm) above the floor or grade below and the fascia or railing would otherwise interfere with the sightlines of immediately adjacent seating.

    1030.17.4 Guards at the end of aisles. A fascia or railing system complying with the guard requirements of Section 1015 shall be provided for the full width of the aisle where the foot of the aisle is more than 30 inches (762 mm) above the floor or grade below. The fascia or railing shall be not less than 36 inches (914 mm) high and shall provide not less than 42 inches (1067 mm) measured diagonally between the top of the rail and the nosing of the nearest tread.

    SECTION 1031—EMERGENCY ESCAPE AND RESCUE

    1031.1 General. Emergency escape and rescue openings shall comply with the requirements of this section.

    1031.2 Where required. In addition to the means of egress required by this chapter, emergency escape and rescue openings shall be provided in Group R occupancies .

    Basements and sleeping rooms below the fourth story above grade plane shall have not fewer than one emergency escape and rescue opening in accordance with this section. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room, but shall not be required in adjoining areas of the basement. Such open

    2025 CALIFORNIA BUILDING CODE 10-59

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

  • CRC § 1030.17.2. Medium relevance — show source text

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    1. In assembly seating areas at cross aisles in accordance with Section 1030.17.2.
    2. On the loading side of station platforms on fixed guideway transit or passenger rail systems.
    3. Portions of an occupiable roof located less than 30 inches (762 mm) measured vertically to adjacent unoccupiable roof areas where approved guards are present at the perimeter of the roof.
    4. At portions of an occupiable roof where an approved barrier is provided. 11. Elevated facility observation station access hatches at detention facilities.

    [BE] 1015.2.1 Glazing. Where glass is used to provide a guard or as a portion of the guard system, the guard shall comply with Section 2407 of the California Building Code . Where the glazing provided does not meet the strength and attachment requirements of Section 1607.9 of the California Building Code, complying guards shall be located along glazed sides of open-sided walking surfaces.

    [BE] 1015.3 Height. Required guards shall be not less than 42 inches (1067 mm) high, measured vertically as follows:

    1. From the adjacent walking surfaces.
    2. On stairways and stepped aisles, from the line connecting the nosings.
    3. On ramps and ramped aisles, from the ramp surface at the guard.

    Exceptions:

    1. For occupancies in Group R-3 not more than three stories above grade in height and within individual dwelling units in occupancies in Group R-2 not more than three stories above grade in height with separate means of egress, required guards shall be not less than 36 inches (914 mm) in height measured vertically above the adjacent walking surfaces.
    2. For occupancies in Groups R-2 and R-3, within the interior conditioned space of individual dwelling units, where the open-sided walking surface is located not more than 25 feet (7.62 meters) measured vertically to the floor or walking surface below, required guards shall not be less than 36 inches (914 mm) in height measured vertically above the adjacent walking surface. 3. For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R-2, where the top of the guard serves as a handrail on the open sides of stairs, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from a line connecting the nosings. 4. The guard height in assembly seating areas shall comply with Section 1030.17 as applicable. 5. Along alternating tread devices and ship’s ladders, guards where the top rail serves as a handrail shall have height not less than 30 inches (762 mm) and not more than 34 inches (864 mm), measured vertically from a line connecting the leading edge of the treads. 6. In Group F occupancies where exit access stairways serve fewer than three stories and such stairways are not open to the public, and where the top of the guard also serves as a handrail, the top of the guard shall be not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from a line connecting the nosings.

    [BE] 1015.4 Opening limitations. Required guards shall not have openings that allow passage of a sphere 4 inches (102 mm) in diameter from the walking surface to the required guard height.

    Exceptions: 1.

  • CRC § 8.1 Medium relevance — show source text

    Garbage Disposal (see Food-Waste Disposers) Garages R317, R330.8.1 Electric vehicle charging infrastructure R317.6 Protection of Energy Storage Systems R330.8

    Generators R331

    Girders R502.5 Glazing Aggregate area R325.1 Greenhouses R324.6.6 Protection of openings R301.2.1.2 Safety glazing at hazardous locations R324

    Site-built R324.5 Skylights and sloped glazing R324.6 Grade

    Of lumber R502.1.1, R602.1.1, R802.1.1 Grade Plane R101.2, R301.2.2.7, R316.3 Ground Floors (on ground) R504, R506 Guards or Guardrail R321, R324.4.4 Exterior R507.10 Guestroom (see Lodging House) Gypsum Board and Gypsum Panel Products R702.3

    Hallways R318.6 Hand Shower (see Shower) Handrails R318.7.8, R318.8.3, R320, R324.4.4 Alternating tread devices R318.7.12.2 Ship’s ladders R318.7.13.2 Hazardous Location R324

    Headers

    SIP R610.8

    Steel R603.6

    Wood R602.7

    Hearth R1001.9

    Extension R1001.10, R1001.9

    Heaters

    Masonry R1002 Heating Required R325.8 Height Ceiling R313 Mezzanines R314.2 Sleeping lofts R315.3 Hollow-Unit Masonry (see Masonry)

    INDEX-2 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    INDEX

    Roof shingles R905.4 Methods Water distribution pipe sizing Appendix CF Mezzanines (see also Sleeping Lofts) R314, R321 Modifications R104.2.3 Moisture Content, Building Materials R109.1.4.1

    Moisture Control R702.7

    Mortar

    Joints R606.3.1 Multiple Flues R1003.13

    Natural Light (see Light) Natural Ventilation (see Ventilation) Notching Steel joists R505.2.5, R505.3.5, R804.2.5, R804.3.3 Steel studs R603.2.6, R603.3.4 Wood joists R502.8, R802.7.1 Wood studs R602.6 Wood top plates R602.6.1

    Opening Protection R302.5

    Parapets R302.2.2, R606.4.4 Particleboard

    Floor R503.3

  • California Residential Code Medium relevance — show source text

    [MP] FULLWAY VALVE. A valve that in the full open position has an opening cross-sectional area that is not less than 85 percent of the cross-sectional area of the connecting pipe.

    [MP] FURNACE. A vented heating appliance designed or arranged to discharge heated air into a conditioned space or through a duct or ducts.

    [RB] GLASS MAT GYPSUM PANEL. A gypsum panel consisting of a noncombustible core primarily of gypsum, surfaced with glass mat partially or completely embedded in the core.

    [RB] GLAZING AREA. The interior surface area of all glazed fenestration, including the area of sash, curbing or other framing elements, that enclose conditioned space. Includes the area of glazed fenestration assemblies in walls bounding conditioned basements.

    [RB] GRADE. The finished ground level adjoining the building at all exterior walls.

    [MP] GRADE, PIPING. See “Slope.”

    [RB] GRADE FLOOR EMERGENCY ESCAPE AND RESCUE OPENING. An emergency escape and rescue opening located such that the bottom of the clear opening is not more than 44 inches (1118 mm) above or below the finished ground level adjacent to the opening. (See also “Emergency escape and rescue opening.”)

    [RB] GRADE PLANE. A reference plane representing the average of the finished ground level adjoining the building at all exterior walls. Where the finished ground level slopes away from the exterior walls, the reference plane shall be established by the lowest points within the area between the building and the lot line or, where the lot line is more than 6 feet (1829 mm) from the building between the structure and a point 6 feet (1829 mm) from the building.

    [MP] GRAYWATER. Waste discharged from lavatories, bathtubs, showers, clothes washers and laundry trays.

    [MP] GRIDDED WATER DISTRIBUTION SYSTEM. A water distribution system where every water distribution pipe is interconnected so as to provide two or more paths to each fixture supply pipe.

    [RB] GROSS AREA OF EXTERIOR WALLS. The normal projection of all exterior walls, including the area of all windows and doors installed therein.

    [MP] GROUND-SOURCE HEAT PUMP LOOP SYSTEM. Piping buried in horizontal or vertical excavations or placed in a body of water for the purpose of transporting heat transfer liquid to and from a heat pump. Included in this definition are closed loop systems in which the liquid is recirculated and open loop systems in which the liquid is drawn from a well or other source.

    [RB] GUARD OR GUARDRAIL . A building component or a system of building components located near the open sides of elevated walking surfaces that minimizes the possibility of a fall from the walking surface to the lower level.

    [RB] GUESTROOM. Any room or rooms used or intended to be used by one or more guests for living or sleeping purposes.

    [RB] GYPSUM BOARD. A type of gypsum panel product consisting of a noncombustible core primarily of gypsum with paper surfacing.

    [RB] GYPSUM PANEL PRODUCT. The general name for a family of sheet products consisting essentially of gypsum complying with the standards specified in Section R702.3 and Chapter 44 of this code.

    [RB] GYPSUM SHEATHING. Gypsum panel products specifically manufactured with enhanced water resistance for use as a substrate for exterior surface materials.

  • CRC § 1.90 Medium relevance — show source text

    RC.L|1.90 ×TDA + 7.08|1.90 ×TDA + 7.08| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Vertical Closed
    Transparent (VCT)|38 (M)|≥32|VCT.SC.M|0.10 ×V + 0.86|0.10 ×V + 0.86| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Vertical Closed
    Transparent (VCT)|0 (L)|<32|VCT.SC.L|0.29 ×V + 2.95|0.29 ×V + 2.95| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Vertical Closed
    Solid (VCS)|38 (M)|≥32|VCS.SC.M|0.05 ×V + 1.36|0.05 ×V + 1.36| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Vertical Closed
    Solid (VCS)|0 (L)|<32|VCS.SC.L|0.22 ×V + 1.38|0.22 ×V + 1.38| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Horizontal Closed
    Transparent (HCT)|38 (M)|≥32|HCT.SC.M|0.06 ×V + 0.37|0.06 ×V + 0.37| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Horizontal Closed
    Transparent (HCT)|0 (L)|<32|HCT.SC.L|0.08 ×V + 1.23|0.08 ×V + 1.23| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Horizontal Closed
    Solid (HCS)|38 (M)|≥32|HCS.SC.M|0.05 ×V + 0.91|0.05 ×V + 0.91| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Horizontal Closed
    Solid (HCS)|0 (L)|<32|HCS.SC.L|0.06 ×V + 1.12|0.06 ×V + 1.12| |Self-contained
    commercial
    refrigerators and
    commercial
    freezers with and
    with outdoors|
    Self-contained
    (SC)|Service Over
    Counter (SOC)|38 (M)|≥32|SOC.SC.M|0.52 ×TDA + 1.00|0.52 ×TDA + 1.

  • CRC § 2022-1.0 Medium relevance — show source text

    GROUND LEVEL PLAY COMPONENT. [DSA-AC] A play component that is approached and exited at the ground level.

    [BS] GROUND SNOW LOAD, p g . Design ground snow loads.

    [BS] GROUND SNOW LOAD, p g(asd) . Allowable stress design ground snow loads

    [BS] GROUND SNOW LOAD GEODATABASE. The ASCE database (version 2022-1.0) of geocoded values of risk-targeted design ground snow load values.

    [BG] GROUP HOME. Group Home means a facility which provides 24-hour care and supervision to children, provides services specified in this chapter to a specific client group, and maintains a structured environment, with such services provided at least in part by staff employed by the licensee. The care and supervision provided by a group home shall be nonmedical except as permitted by Welfare and Institutions Code Section 17736(b). Since small family and foster family homes, by definition, care for six or fewer children only, any facility providing 24-hour care for seven or more children must be licensed as a group home.

    [BE] GUARD [DSA-AC, HCD 1, HCD 2 & HCD 1-AC] OR GUARDRAIL . A building component or a system of building components located at or near the open sides of elevated walking surfaces that minimizes the possibility of a fall from the walking surface to a lower level.

    [BG] GUESTROOM. A room used or intended to be used by one or more guests for living or sleeping purposes.

    [BS] GYPSUM BOARD. A type of gypsum panel product consisting of a noncombustible core primarily of gypsum with paper surfacing.

    [BS] GYPSUM PANEL PRODUCT. The general name for a family of sheet products consisting essentially of gypsum complying with the standards specified in Table 2506.2, Table 2507.2 and Chapter 35.

    [BS] GYPSUM PLASTER. A mixture of calcined gypsum or calcined gypsum and lime and aggregate and other approved materials as specified in this code.

    [BS] GYPSUM SHEATHING. Gypsum panel products specifically manufactured with enhanced water resistance for use as a substrate for exterior surface materials.

    [BS] GYPSUM VENEER PLASTER. Gypsum plaster applied to an approved base in one or more coats normally not exceeding [1] / 4 inch (6.4 mm) in total thickness.

    [BS] GYPSUM WALLBOARD. A gypsum board used primarily as an interior surfacing for building structures.

    [BG] HABITABLE SPACE. A space in a building for living, sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not considered habitable spaces.

    HALL CALL CONSOLE. [DSA-AC] An elevator call user interface exclusive to a destination-oriented elevator system that requires the user to select a destination floor prior to entering the elevator car.

    [F] HALOGENATED EXTINGUISHING SYSTEM. A fire-extinguishing system using one or more atoms of an element from the halogen chemical series: fluorine, chlorine, bromine and iodine.

    [F] HANDLING. The deliberate transport by any means to a point of storage or use .

    2025 CALIFORNIA BUILDING CODE 2-35

  • CRC § 2025 Medium relevance — show source text

    It is important to understand that the IRC contains coverage for what is conventional and common in residential construction practice. While the IRC will provide all of the needed coverage for most residential construction, it might not address construction practices and systems that are atypical or rarely encountered in the industry. Therefore, the IRC contains several references to other codes either as an alternative to the provisions of the IRC or where the IRC lacks coverage for a particular type of structure, design, system, appliance or method of construction. In other words, the IRC is meant to be all inclusive for typical residential construction and it relies on other codes only where alternatives are desired or where the code lacks coverage for the uncommon aspect of residential construction. Of course, the IRC constantly evolves to address new technologies and construction practices that were once uncommon, but are now common.

    The IRC is unique in that much of it, including Chapters 3 through 9 and Chapters 34 through 43, is presented in an ordered format that is consistent with the normal progression of construction, starting with the design phase and continuing through the final trimout phase. This is consistent with the “cookbook” philosophy of the IRC.

    2025 CALIFORNIA RESIDENTIAL CODE xiii

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    xiv 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    Arrangement and Format of the 2025 CRC

    The CRC is divided into nine main parts, specifically: Part I—Administrative, Part II—Definitions, Part III—Building Planning and Construction, Part IV—Energy Conservation, Part V—Mechanical, Part VI—Fuel Gas, Part VII—Plumbing, Part VIII—Electrical and Part IX—Referenced Standards. Parts IV through VIII of IRC are not adopted in California and replaced with references to appropriate parts of Title 24. The following provides a brief description of the content of each chapter and appendix of the CRC:

    Chapter 1 Scope and Administration.

    Chapter 1 establishes the limits of applicability of the code and describes how the code is to be applied and enforced. The provisions of Chapter 1 establish the authority and duties of the code official appointed by the authority having jurisdiction and also establish the rights and privileges of the design professional, contractor and property owner.

    Chapter 2 Definitions.

    Chapter 2 is the repository of the definitions of terms used in the body of the code. The user of the code should be familiar with and consult this chapter because the definitions are essential to the correct interpretation of the code and because the user may not be aware that a term is defined.

    Chapter 3 Building Planning.

    Chapter 3 provides guidelines for a minimum level of structural integrity, life safety, fire safety and livability for inhabitants of dwelling units regulated by this code. Chapter 3 is a compilation of the code requirements specific to the building planning sector of the design and construction process. This chapter sets forth code requirements dealing with light, ventilation, sanitation, minimum room size, ceiling height and environmental comfort. Chapter 3 establishes life-safety provisions including limitations on glazing used in hazardous areas, specifications on stairways, use of guards at elevated surfaces, window and fall protection, and rules for means of egress. Snow, wind and seismic design live and dead loads and flood-resistant construction, as well as solar energy systems are addressed in this chapter.

    Chapter 4 Foundations.

  • CRC § 6.1 Medium relevance — show source text

    d
    (pcf)|MINIMUM COMPRES-
    SIVE STRENGTH PER
    SECTION BK106.6.1
    (psi)|WALL-TYPE
    REINFORCEMENT
    PER TABLE
    BK105.3|MINIMUM
    THICKNESSc, e, f AT
    TOP OF WALL
    (inches)|MINIMUM
    THICKNESSc, e, f AT
    BOTTOM OF WALL
    (inches)**| |1,200|100|85|E|9|12| |475|≥ 50 pcf: less than
    40 inches from top of wall|40b|E or F|8|12| |475|≥ 70 pcf: from 40 inches to 80
    inches from top of wall|55b|55b|55b|55b| |475|≥ 90 pcf: more than 80 inches
    from top of wall|85|85|85|85| |Nonload bearing|50 to 100|≥ 60 psi
    < 60 psib|E or F|9|9| |For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.45 kg, 1 pound per cubic foot = 16.02 kg/m3.
    a.
    Density is to be measured at equilibrium moisture content. Average wall density shall be within ±5 pcf of the tabulated value.
    b.
    Requires an approved engineered design per Section BK106.6.
    c.
    Cob thickness only. The interior and exterior cob faces shall be permitted to be unfinished or receive any plaster finish allowed by this appendix.
    d.
    Cob walls with more than one density shall be built with heavier densities below lighter densities.
    e.
    Minimum cob wall thickness shall be whichever is greater in Tables BK105.3, BK106.11(1) and BK108.1.
    f.
    Wall thicknesses less than 10 inches require an engineered design.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.45 kg, 1 pound per cubic foot = 16.02 kg/m3.
    a.
    Density is to be measured at equilibrium moisture content. Average wall density shall be within ±5 pcf of the tabulated value.
    b.
    Requires an approved engineered design per Section BK106.6.
    c.
    Cob thickness only. The interior and exterior cob faces shall be permitted to be unfinished or receive any plaster finish allowed by this appendix.
    d.
    Cob walls with more than one density shall be built with heavier densities below lighter densities.
    e.
    Minimum cob wall thickness shall be whichever is greater in Tables BK105.3, BK106.11(1) and BK108.1.
    f.
    Wall thicknesses less than 10 inches require an engineered design.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.45 kg, 1 pound per cubic foot = 16.02 kg/m3.
    a.
    Density is to be measured at equilibrium moisture content.

  • CRC § 25.4 Medium relevance — show source text

    Where the top of a guard is also serving as the handrail, a single concentrated load shall be applied in any
    direction at any point along the top. Concentrated loads shall not be applied concurrently.|For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1 pound = 4.45 N.
    a. Elevated garage floors shall be capable of supporting the uniformly distributed live load or a 2,000-pound concentrated load applied on an area of 41/2 inches by 41/2 inches,
    whichever produces the greater stresses.
    b. Uninhabitable attics without storage are those where the clear height between joists and rafters is not more than 42 inches, or where there are not two or more adjacent
    trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This
    live load need not be assumed to act concurrently with any other live load requirements.
    c. Individual stair treads shall be capable of supporting the uniformly distributed live load or a 300-pound concentrated load applied on an area of 2 inches by 2 inches, which-
    ever produces the greater stresses.
    d. A single concentrated load applied in any direction at any point along the top. For a guard not required to serve as a handrail, the load need not be applied to the top element
    of the guard in a direction parallel to such element.
    e. See Section R507.1 for decks attached to exterior walls.
    f. Guard in-fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area
    equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement.
    g. Uninhabitable attics with limited storage are those where the clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses
    with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
    The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met:
    1.
    The attic area is accessed from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is not less than 30 inches.
    2.
    The slopes of the joists or truss bottom chords are not greater than 2 units vertical in 12 units horizontal.
    3.
    Required insulation depth is less than the joist or truss bottom chord member depth.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
    h. Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated
    loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to
    occur with any other live load.
    i.

  • California Residential Code Medium relevance — show source text

    Elevated garage floors shall be capable of supporting the uniformly distributed live load or a 2,000-pound concentrated load applied on an area of 41/2 inches by 41/2 inches,
    whichever produces the greater stresses.
    b. Uninhabitable attics without storage are those where the clear height between joists and rafters is not more than 42 inches, or where there are not two or more adjacent
    trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This
    live load need not be assumed to act concurrently with any other live load requirements.
    c. Individual stair treads shall be capable of supporting the uniformly distributed live load or a 300-pound concentrated load applied on an area of 2 inches by 2 inches, which-
    ever produces the greater stresses.
    d. A single concentrated load applied in any direction at any point along the top. For a guard not required to serve as a handrail, the load need not be applied to the top element
    of the guard in a direction parallel to such element.
    e. See Section R507.1 for decks attached to exterior walls.
    f. Guard in-fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area
    equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement.
    g. Uninhabitable attics with limited storage are those where the clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses
    with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
    The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met:
    1.
    The attic area is accessed from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is not less than 30 inches.
    2.
    The slopes of the joists or truss bottom chords are not greater than 2 units vertical in 12 units horizontal.
    3.
    Required insulation depth is less than the joist or truss bottom chord member depth.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
    h. Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated
    loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to
    occur with any other live load.
    i. Where the top of a guard system is not required to serve as a handrail, the single concentrated load shall be applied at any point along the top, in the vertical downward direc-
    tion and in the horizontal direction away from the walking surface. Where the top of a guard is also serving as the handrail, a single concentrated load shall be applied in any
    direction at any point along the top.

  • CRC § 16A-15 Medium relevance — show source text

    2025 CALIFORNIA BUILDING CODE 16A-15

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    STRUCTURAL DESIGN

    1. For roofs not intended for occupancy, only the single concentrated load required by Section 1607 A .9.1 shall be applied.

    1607 A .9.1.2 Guard component loads. Balusters, panel fillers and guard infill components, including all rails except the handrail and the top rail, shall be designed to resist a concentrated load of 50 pounds (0.22 kN) in accordance with Section 4.5.1.2 of ASCE 7.

    1607 A .9.2 Grab bars, shower seats and accessible benches. Grab bars, shower seats and accessible benches shall be designed to resist a single concentrated load of 250 pounds (1.11 kN) applied in any direction at any point on the grab bar, shower seat, or seat of the accessible bench so as to produce the maximum load effects. [DSA-AC & HCD 1-AC] See Chapter 11A, Section 1127A.4 and Chapter 11B, Sections 11B-609.8, 11B-610.4 and 11B-903.6 for grab bars, shower seats and dressing room bench seats, as applicable.

    1607 A .10 Fixed ladders. Fixed ladders with rungs shall be designed to resist a single concentrated load of 300 pounds (1.33 kN) in accordance with Section 4.5.4 of ASCE 7. Where rails of fixed ladders extend above a floor or platform at the top of the ladder, each side rail extension shall be designed to resist a single concentrated load of 100 pounds (0.445 kN) in accordance with Section 4.5.4 of ASCE 7. Ship’s ladders shall be designed to resist the stair loads given in Table 1607 A .1.

    1607 A .11 Vehicle barriers. Vehicle barriers for passenger vehicles shall be designed to resist a concentrated load of 6,000 pounds (26.70 kN) in accordance with Section 4.5.3 of ASCE 7. Garages accommodating trucks and buses shall be designed in accordance with an approved method that contains provisions for traffic railings.

    1607 A .12 Impact loads. The live loads specified in Sections 1607 A .3 through 1607 A .11 shall be assumed to include adequate allowance for ordinary impact conditions. Provisions shall be made in the structural design for uses and loads that involve unusual vibration and impact forces.

    1607 A .12.1 Elevators. Members, elements and components subject to dynamic loads from elevators shall be designed for impact loads and deflection limits prescribed by ASME A17.1/CSA B44.

    1607 A .12.2 Machinery. For the purpose of design, the weight of machinery and moving loads shall be increased as follows to allow for impact:

    1. Light machinery, shaft- or motor-driven, 20 percent.
    2. Reciprocating machinery or power-driven units, 50 percent.

    Percentages shall be increased where specified by the manufacturer.

  • CRC § 25.4 Medium relevance — show source text

    Concentrated loads shall not be applied concurrently.|For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1 pound = 4.45 N.
    a. Elevated garage floors shall be capable of supporting the uniformly distributed live load or a 2,000-pound concentrated load applied on an area of 41/2 inches by 41/2 inches,
    whichever produces the greater stresses.
    b. Uninhabitable attics without storage are those where the clear height between joists and rafters is not more than 42 inches, or where there are not two or more adjacent
    trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This
    live load need not be assumed to act concurrently with any other live load requirements.
    c. Individual stair treads shall be capable of supporting the uniformly distributed live load or a 300-pound concentrated load applied on an area of 2 inches by 2 inches, which-
    ever produces the greater stresses.
    d. A single concentrated load applied in any direction at any point along the top. For a guard not required to serve as a handrail, the load need not be applied to the top element
    of the guard in a direction parallel to such element.
    e. See Section R507.1 for decks attached to exterior walls.
    f. Guard in-fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area
    equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement.
    g. Uninhabitable attics with limited storage are those where the clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses
    with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
    The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met:
    1.
    The attic area is accessed from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is not less than 30 inches.
    2.
    The slopes of the joists or truss bottom chords are not greater than 2 units vertical in 12 units horizontal.
    3.
    Required insulation depth is less than the joist or truss bottom chord member depth.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
    h. Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated
    loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to
    occur with any other live load.
    i. Where the top of a guard system is not required to serve as a handrail, the single concentrated load shall be applied at any point along the top, in the vertical downward direc-
    tion and in the horizontal direction away from the walking surface.

  • CRC § 3-22 Medium relevance — show source text

    Guard in-fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area
    equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement.
    g. Uninhabitable attics with limited storage are those where the clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses
    with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
    The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met:
    1.
    The attic area is accessed from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is not less than 30 inches.
    2.
    The slopes of the joists or truss bottom chords are not greater than 2 units vertical in 12 units horizontal.
    3.
    Required insulation depth is less than the joist or truss bottom chord member depth.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
    h. Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated
    loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to
    occur with any other live load.
    i. Where the top of a guard system is not required to serve as a handrail, the single concentrated load shall be applied at any point along the top, in the vertical downward direc-
    tion and in the horizontal direction away from the walking surface. Where the top of a guard is also serving as the handrail, a single concentrated load shall be applied in any
    direction at any point along the top. Concentrated loads shall not be applied concurrently.|

    3-22 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    BUILDING PLANNING

    R301.6 Roof load. The roof shall be designed for the live load indicated in Table R301.6 or the ground snow load indicated in Table R301.2, whichever is greater.

    |TABLE R301.

  • CRC § 25.4 Medium relevance — show source text

    This load need not be assumed to act concurrently with any other live load requirement.
    g. Uninhabitable attics with limited storage are those where the clear height between joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses
    with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
    The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met:
    1.
    The attic area is accessed from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is not less than 30 inches.
    2.
    The slopes of the joists or truss bottom chords are not greater than 2 units vertical in 12 units horizontal.
    3.
    Required insulation depth is less than the joist or truss bottom chord member depth.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
    h. Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated
    loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to
    occur with any other live load.
    i. Where the top of a guard system is not required to serve as a handrail, the single concentrated load shall be applied at any point along the top, in the vertical downward direc-
    tion and in the horizontal direction away from the walking surface. Where the top of a guard is also serving as the handrail, a single concentrated load shall be applied in any
    direction at any point along the top. Concentrated loads shall not be applied concurrently.|For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1 pound = 4.45 N.
    a. Elevated garage floors shall be capable of supporting the uniformly distributed live load or a 2,000-pound concentrated load applied on an area of 41/2 inches by 41/2 inches,
    whichever produces the greater stresses.
    b. Uninhabitable attics without storage are those where the clear height between joists and rafters is not more than 42 inches, or where there are not two or more adjacent
    trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This
    live load need not be assumed to act concurrently with any other live load requirements.
    c. Individual stair treads shall be capable of supporting the uniformly distributed live load or a 300-pound concentrated load applied on an area of 2 inches by 2 inches, which-
    ever produces the greater stresses.
    d. A single concentrated load applied in any direction at any point along the top. For a guard not required to serve as a handrail, the load need not be applied to the top element
    of the guard in a direction parallel to such element.
    e. See Section R507.1 for decks attached to exterior walls.
    f.

  • CRC § 25.4 Medium relevance — show source text

    or where there are two or more adjacent trusses
    with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.
    The live load need only be applied to those portions of the joists or truss bottom chords where all of the following conditions are met:
    1.
    The attic area is accessed from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is not less than 30 inches.
    2.
    The slopes of the joists or truss bottom chords are not greater than 2 units vertical in 12 units horizontal.
    3.
    Required insulation depth is less than the joist or truss bottom chord member depth.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
    h. Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated
    loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to
    occur with any other live load.
    i. Where the top of a guard system is not required to serve as a handrail, the single concentrated load shall be applied at any point along the top, in the vertical downward direc-
    tion and in the horizontal direction away from the walking surface. Where the top of a guard is also serving as the handrail, a single concentrated load shall be applied in any
    direction at any point along the top. Concentrated loads shall not be applied concurrently.|For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 square inch = 645 mm2, 1 pound = 4.45 N.
    a. Elevated garage floors shall be capable of supporting the uniformly distributed live load or a 2,000-pound concentrated load applied on an area of 41/2 inches by 41/2 inches,
    whichever produces the greater stresses.
    b. Uninhabitable attics without storage are those where the clear height between joists and rafters is not more than 42 inches, or where there are not two or more adjacent
    trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This
    live load need not be assumed to act concurrently with any other live load requirements.
    c. Individual stair treads shall be capable of supporting the uniformly distributed live load or a 300-pound concentrated load applied on an area of 2 inches by 2 inches, which-
    ever produces the greater stresses.
    d. A single concentrated load applied in any direction at any point along the top. For a guard not required to serve as a handrail, the load need not be applied to the top element
    of the guard in a direction parallel to such element.
    e. See Section R507.1 for decks attached to exterior walls.
    f. Guard in-fill components (all those except the handrail), balusters and panel fillers shall be designed to withstand a horizontally applied normal load of 50 pounds on an area
    equal to 1 square foot. This load need not be assumed to act concurrently with any other live load requirement.
    g.

  • CRC § 8.4.1 Medium relevance — show source text

    1607 A .8.4.1 Impact and fatigue. Impact loads and fatigue loading shall be considered in the design of the supporting structure. For the purposes of design, the vehicle and wheel loads shall be increased by 30 percent to account for impact.

    1607 A .8.5 Posting. The maximum weight of vehicles allowed into or on a garage or other structure shall be posted by the owner or the owner’s authorized agent in accordance with Section 106.1.

    1607 A .9 Loads on handrails, guards, grab bars and seats. Handrails and guards shall be designed and constructed for the structural loading conditions set forth in Section 1607 A .9.1. Grab bars, shower seats and accessible benches shall be designed and constructed for the structural loading conditions set forth in Section 1607 A .9.2.

    1607 A .9.1 Concentrated load. Handrails and guards shall be designed to resist a concentrated load of 200 pounds (0.89 kN) in accordance with Section 4.5.1 of ASCE 7. Glass handrail assemblies and guards shall comply with Section 2407.

    1607 A .9.1.1 Uniform load. Handrails and guards shall be designed to resist a linear load of 50 pounds per linear foot (plf) (0.73 kN/m) in accordance with Section 4.5.1.1 of ASCE 7. This load need not be assumed to act concurrently with the concentrated load specified in Section 1607 A .9.1.

    Exceptions:

    1. For one- and two-family dwellings, only the single concentrated load required by Section 1607 A .9.1 shall be applied.
    2. In Group I-3, F, H and S occupancies, for areas that are not accessible to the general public and that have an occupant load less than 50, the minimum load shall be 20 pounds per foot (0.29 kN/m).

    2025 CALIFORNIA BUILDING CODE 16A-15

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    STRUCTURAL DESIGN

    1. For roofs not intended for occupancy, only the single concentrated load required by Section 1607 A .9.1 shall be applied.

    1607 A .9.1.2 Guard component loads. Balusters, panel fillers and guard infill components, including all rails except the handrail and the top rail, shall be designed to resist a concentrated load of 50 pounds (0.22 kN) in accordance with Section 4.5.1.2 of ASCE 7.

    1607 A .9.2 Grab bars, shower seats and accessible benches. Grab bars, shower seats and accessible benches shall be designed to resist a single concentrated load of 250 pounds (1.11 kN) applied in any direction at any point on the grab bar, shower seat, or seat of the accessible bench so as to produce the maximum load effects. [DSA-AC & HCD 1-AC] See Chapter 11A, Section 1127A.4 and Chapter 11B, Sections 11B-609.8, 11B-610.4 and 11B-903.6 for grab bars, shower seats and dressing room bench seats, as applicable.

  • CRC § 1607.8.4.1 Medium relevance — show source text

    1607.8.4.1 Impact and fatigue. Impact loads and fatigue loading shall be considered in the design of the supporting structure. For the purposes of design, the vehicle and wheel loads shall be increased by 30 percent to account for impact.

    1607.8.5 Posting. The maximum weight of vehicles allowed into or on a garage or other structure shall be posted by the owner or the owner’s authorized agent in accordance with Section 106.1.

    2025 CALIFORNIA BUILDING CODE 16-13

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    **

    STRUCTURAL DESIGN

    1607.9 Loads on handrails, guards, grab bars , shower seats, dressing room bench and seats. Handrails and guards shall be designed and constructed for the structural loading conditions set forth in Section 1607.9.1. Grab bars, shower seats and accessible benches shall be designed and constructed for the structural loading conditions set forth in Section 1607.9.2.

    1607.9.1 Concentrated load. Handrails and guards shall be designed to resist a concentrated load of 200 pounds (0.89 kN) in accordance with Section 4.5.1 of ASCE 7. Glass handrail assemblies and guards shall comply with Section 2407.

    1607.9.1.1 Uniform load. Handrails and guards shall be designed to resist a linear load of 50 pounds per linear foot (plf) (0.73 kN/m) in accordance with Section 4.5.1.1 of ASCE 7. This load need not be assumed to act concurrently with the concentrated load specified in Section 1607.9.1.

    Exceptions:

    1. For one- and two-family dwellings, only the single concentrated load required by Section 1607.9.1 shall be applied.
    2. In Group I-3, F, H and S occupancies, for areas that are not accessible to the general public and that have an occupant load less than 50, the minimum load shall be 20 pounds per foot (0.29 kN/m).
    3. For roofs not intended for occupancy, only the single concentrated load required by Section 1607.9.1 shall be applied.

    1607.9.1.2 Guard component loads. Balusters, panel fillers and guard infill components, including all rails except the handrail and the top rail, shall be designed to resist a concentrated load of 50 pounds (0.22 kN) in accordance with Section 4.5.1.2 of ASCE 7.

    1607.9.2 Grab bars, shower seats and accessible benches. Grab bars, shower seats and accessible benches shall be designed to resist a single concentrated load of 250 pounds (1.11 kN) applied in any direction at any point on the grab bar, shower seat, or seat of the accessible bench so as to produce the maximum load effects. [DSA-AC & HCD 1-AC] See Chapter 11A, Section 1127A.4 and Chapter 11B, Sections 11B-609.8, 11B-610.4 and 11B-903.6 for grab bars, shower seats and dressing room bench seats, as applicable.

  • CRC § 0.5 Medium relevance — show source text

    0_|1.0|1.0|1.0|0.6| |Wind on Structure (W)|1.0|1.0|0.75||| |Current on Structure (C)|1.0|1.0|1.0||| |Earth Pressure on the Structure (H)|1.0|1.0|1.0|1.0|1.0| |Mooring/Breasting Load (M)||1.0|||| |Berthing Load (Be)|||1.0||| |Earthquake Load (E)||||0.7|0.7| |% Allowable Stress|100|100|100|1002|1002| |1. k = 0.5 (PGA)
    2. Increase in allowable stress shall not be used with these load combinations unless it can be demonstrated that such increase is justified by structural behavior caused by rate or
    duration of load. See ASCE/SEI 7 [3.21]|1. k = 0.5 (PGA)
    2. Increase in allowable stress shall not be used with these load combinations unless it can be demonstrated that such increase is justified by structural behavior caused by rate or
    duration of load. See ASCE/SEI 7 [3.21]|1. k = 0.5 (PGA)
    2. Increase in allowable stress shall not be used with these load combinations unless it can be demonstrated that such increase is justified by structural behavior caused by rate or
    duration of load. See ASCE/SEI 7 [3.21]|1. k = 0.5 (PGA)
    2. Increase in allowable stress shall not be used with these load combinations unless it can be demonstrated that such increase is justified by structural behavior caused by rate or
    duration of load. See ASCE/SEI 7 [3.21]|1. k = 0.5 (PGA)
    2. Increase in allowable stress shall not be used with these load combinations unless it can be demonstrated that such increase is justified by structural behavior caused by rate or
    duration of load. See ASCE/SEI 7 [3.21]|1. k = 0.5 (PGA)
    2. Increase in allowable stress shall not be used with these load combinations unless it can be demonstrated that such increase is justified by structural behavior caused by rate or
    duration of load. See ASCE/SEI 7 [3.21]|

    2025 CALIFORNIA BUILDING CODE 31F-31

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MARINE OIL TERMINALS

    3103F.9 Miscellaneous loads. Handrails and guardrails shall be designed for 25 plf with a 200-pound minimum concentrated load in any location or direction.

    3103F.10 Symbols.

    a = Distance between the vessel’s center of gravity and the point of contact on the vessel’s side, projected onto the vessel’s longitudi- nal axis [ft]

  • CRC § 5-43 Medium relevance — show source text

    2025 CALIFORNIA RESIDENTIAL CODE 5-43

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FLOORS

    R507.10 Exterior guards. Guards shall be constructed to meet the requirements of Sections R301.5 and R321, and this section.

    R507.10.1 Support of guards. Where guards are supported on deck framing, guard loads shall be transferred to the deck framing with a continuous load path to the deck joists.

    R507.10.1.1 Guards supported by side of deck framing. Where guards are connected to the interior or exterior side of a deck joist or beam, the joist or beam shall be connected to the adjacent joists to prevent rotation of the joist or beam. Connections relying only on fasteners in end grain withdrawal are not permitted.

    R507.10.1.2 Guards supported on top of deck framing. Where guards are mounted on top of the decking, the guards shall be connected to the deck framing or blocking and installed in accordance with manufacturer’s instructions to transfer the guard loads to the adjacent joists.

    R507.10.2 Wood posts at deck guards. Where 4-inch by 4-inch (102 mm by 102 mm) wood posts support guard loads applied to the top of the guard, such posts shall not be notched at the connection to the supporting structure.

    R507.10.3 Plastic composite guards. Plastic composite guards shall comply with the provisions of Section R507.2.2.

    R507.10.4 Other guards. Other guards shall be in accordance with either manufacturer’s instructions or accepted engineering principles.

    5-44 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA RESIDENTIAL CODE – MATRIX ADOPTION TABLE

    CHAPTER 6 – WALL CONSTRUCTION

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting agency BSC BSC-
    CG
    SFM HCD Col6 Col7 DSA Col9 Col10 OSHPD Col12 Col13 Col14 Col15 Col16 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting agency BSC BSC-
    CG
    SFM 1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt entire chapter
    Adopt entire chapter as
    amended (amended
    sections listed below)
    X X
    Adopt only those sections
    that are listed below
    Chapter / Section
    R602.1.
  • CRC § 3-22 Medium relevance — show source text


    2.
    The slopes of the joists or truss bottom chords are not greater than 2 units vertical in 12 units horizontal.
    3.
    Required insulation depth is less than the joist or truss bottom chord member depth.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 pounds per square foot.
    h. Glazing used in handrail assemblies and guards shall be designed with a load adjustment factor of 4. The load adjustment factor shall be applied to each of the concentrated
    loads applied to the top of the rail, and to the load on the in-fill components. These loads shall be determined independent of one another, and loads are assumed not to
    occur with any other live load.
    i. Where the top of a guard system is not required to serve as a handrail, the single concentrated load shall be applied at any point along the top, in the vertical downward direc-
    tion and in the horizontal direction away from the walking surface. Where the top of a guard is also serving as the handrail, a single concentrated load shall be applied in any
    direction at any point along the top. Concentrated loads shall not be applied concurrently.|

    3-22 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    BUILDING PLANNING

    R301.6 Roof load. The roof shall be designed for the live load indicated in Table R301.6 or the ground snow load indicated in Table R301.2, whichever is greater.

    TABLE R301.6—MINIMUM ROOF LIVE LOADS IN POUNDS-FORCE PER SQUARE FOOT OF HORIZONTAL PROJECTION Col2 Col3 Col4
    ** ROOF SLOPE** ** TRIBUTARY LOADED AREA IN SQUARE FEET FOR ANY STRUCTURAL MEMBER** ** TRIBUTARY LOADED AREA IN SQUARE FEET FOR ANY STRUCTURAL MEMBER** ** TRIBUTARY LOADED AREA IN SQUARE FEET FOR ANY STRUCTURAL MEMBER**
    ** ROOF SLOPE** ** 0 to 200** ** 201 to 600** ** Over 600**
    Flat or rise less than 4 inches per foot (1:3) 20 16 12
    Rise 4 inches per foot (1:3) to less than 12 inches per foot (1:1) 16 14 12
    Rise 12 inches per foot (1:1) and greater 12 12 12
    For SI: 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa, 1 inch per foot = 83.3 mm/m. For SI: 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa, 1 inch per foot = 83.3 mm/m. For SI: 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa, 1 inch per foot = 83.3 mm/m. For SI: 1 square foot = 0.0929 m2, 1 pound per square foot = 0.0479 kPa, 1 inch per foot = 83.3 mm/m.

Frequently asked questions

Do I need a guard on a porch that is 28 inches above grade?

No. Guards are required where the vertical distance is more than 30 inches measured vertically within 36 inches horizontal to the open edge. At 28 inches the CRC guard trigger in § R321.1.1 is not met.

Can I use insect screen or lattice as the guard?

No. Insect screening is not considered a guard under § R321.1.1; the screening does not meet height, opening or load requirements. Use a code‑compliant railing/guard system.

How high must a guard be for a second‑floor balcony?

Generally 42 inches above the walking surface per § R321.1.2 (measured vertically). Stair exceptions apply only on open stair sides.

What is the 4‑inch sphere rule?

A guard’s openings (from walking surface up to the required guard height) must not admit a 4‑inch diameter sphere — i.e., any opening large enough to let that sphere pass is noncompliant — per § R321.1.3. There are limited stair and triangular opening exceptions.

Do balusters and panels need to be engineered?

Balusters and panel fillers must be designed to resist the guard in‑fill concentrated load (the code calls out 50 lb on an area equal to 1 sq ft in the CRC live‑load table / footnotes in § R301.5). This can be satisfied by common prescriptive details or by engineered details for nonstandard systems.

More in California Residential Code

Ask about the CRC

Get cited, plain-English answers on the California Residential Code for your project — any code section, any scenario.

Start Free Trial

Related in the CRC