CMC · California Mechanical Code
How must factory-made and flexible ducts be constructed and labeled?
Factory-made ducts (metal or nonmetallic) and flexible ducts must be listed and labeled to the appropriate UL standard (commonly UL 181), installed per the CMC’s flexible‑duct rules (supports, length limits), and sealed with UL‑listed closure systems marked as required by the code.
Last reviewed: July 6, 2026
What the code requires — plain English
Factory-made metal ducts must meet recognized metal-duct construction standards and flexible metallic ducts must be listed to UL 181. Nonmetallic factory-made ducts (including flexible and rigid nonmetallic materials) are permitted only when listed and labeled to UL 181. Closure systems (tapes, mastics, etc.) used with ducts must be the types listed for the duct material and marked per the CMC closure-marking table. See § 602.4 and § 602.5.5 for the material/listing rules and § 603.9.1 for closure/label markings.
The single most important rule: use factory-made ducts and closure systems that are listed and labeled to the appropriate UL standard (commonly UL 181), and follow the CMC installation and marking rules.
Requirements in detail
Materials and listing
- Metal ducts (ducts, plenums, fittings)
- Must comply with SMACNA HVAC Duct Construction Standards – Metal and Flexible. Flexible metallic ducts must be listed to UL 181. (See § 602.4)
- Nonmetallic ducts (factory-made)
- Flexible and rigid nonmetallic ducts, plenums, or fittings are permitted only if listed and labeled to UL 181. (See § 602.5.5)
- Exception: plastic ducts are treated separately and must comply with § 603.5 (see Exceptions & special cases).
Closure systems, sealing, and markings
- Closure systems (tapes, mastics and other closure products) used on ducts and plenums must be listed/labeled per UL 181A or UL 181B as appropriate, and must be marked in accordance with the CMC closure-marking table. The table in § 603.9.1 assigns markings (e.g., 181A‑P, 181B‑FX, 181B‑M, etc.) depending on duct type and closure type. Mechanical fasteners used with flexible ducts must be used with a listed pressure-sensitive tape or mastic and—if nonmetallic—must be listed/labeled to UL 181B (marked “181B‑C”).
Installation-related construction rules that affect factory-made/flexible ducts
- Flexible air ducts must be listed to UL 181, installed per the manufacturer's instructions and SMACNA, supported at specified intervals, and meet length and sag limits (for example, support spacing and maximum permitted length rules appear in § 603.4). Flexible ducts are also limited in some applications (vertical risers, fire‑rated penetrations).
- All ducts shall be sealed to Seal Class A and joints and seams made substantially airtight using listed closure systems (see § 603.1.1 and § 603.9).
Decision‑relevant dimensions / values (quick reference table)
| Item | Value / Limit | Code Reference |
|---|---|---|
| Flexible metallic ducts: listing | Must be listed to UL 181 | § 602.4 |
| Nonmetallic factory-made ducts: listing | Must be listed and labeled to UL 181 | § 602.5.5 |
| Seal requirement | All ducts sealed to Seal Class A | § 603.1.1 / § 603.9 |
| Closure markings | Marked per table (examples: 181A‑P, 181B‑FX, 181B‑M, 181B‑C) | § 603.9.1 (Table 603.9.1) |
| Flexible duct support spacing (horizontal) | Support at not more than 4 ft (1219 mm) | § 603.4 (Flexible Air Ducts) |
| Flexible duct maximum length (general) | Not more than 5 ft (1524 mm) in many installations (see exceptions for residential/healthcare) | § 603.4.1 |
(Use this table as a checklist when selecting factory-made duct products or acceptance‑testing installation work.)
Exceptions & special cases
- Plastic ducts: although § 602.5.5 permits other nonmetallic materials listed to UL 181, plastic ducts are excluded from this allowance and instead must comply with § 603.5. Do not assume every plastic duct is covered by § 602.5.5 — check § 603.5.
- Vertical risers & fire-rated assemblies: ducts listed to UL 181 are not permitted as vertical risers serving more than two stories, nor may UL 181 ducts penetrate fire‑resistance‑rated assemblies — see § 603.1.4 and § 603.1.5. For tall or multi‑story runs, use appropriate rigid construction or design by a registered professional.
- Flexible duct length: CMC limits flexible duct length to 5 ft in many applications (with exceptions in residential occupancies and special allowances for healthcare) — check § 603.4.1 for the application-specific rule.
Common mistakes
- Installing unlisted flexible duct or closure products — the code requires listing/labeling to UL 181 (or UL 181A/B for closures). Don’t rely on generic “flexible duct” packaging without a UL marking.
- Using the wrong closure product or failing to use the listed closure marking — tapes/mastics must be listed to the correct UL standard and marked as prescribed in § 603.9.1 (e.g., using a tape not marked for flexible ducts).
- Exceeding flexible duct length or improper support spacing — long, unsupported flex ducts increase pressure drop and risk collapse; follow § 603.4 support and length limits.
- Assuming nonmetallic always OK — only nonmetallic ducts listed to UL 181 are permitted by § 602.5.5; plastic ducts must be checked against § 603.5.
- Not sealing to Seal Class A — every duct must meet Seal Class A sealing per § 603.1.1/§ 603.9; cloth‑back rubber adhesive tape alone is not acceptable unless used with mastic and drawbands (see related sealing rules).
Worked example
Scenario: You specify a factory-made nonmetallic flexible duct to connect an air handler to a short run of rigid duct in a small commercial tenant space.
Step 1 — Product selection:
- Choose a flexible duct product that is listed and labeled to UL 181 (manufacturer’s label on the product or documentation). This complies with § 602.5.5.
Step 2 — Closures and fasteners:
- Use closure materials listed for flexible ducts (UL 181B) and labeled per § 603.9.1 (for example, a pressure‑sensitive tape listed as 181B‑FX and/or mastic 181B‑M). Use mechanical fasteners in combination with the listed tape/mastic; nonmetallic mechanical fasteners must be listed per UL 181B and marked 181B‑C.
Step 3 — Installation limits:
- Keep the flexible duct run short — the CMC generally limits flexible runs to 5 ft except where exceptions apply — confirm whether this installation is treated as residential or nonresidential per § 603.4.1. Support horizontal runs at not more than 4 ft intervals and keep sag within the allowed limits per § 603.4.
Step 4 — Sealing:
- Seal joints to Seal Class A using the listed closure system (combined mastic + tape if required). Verify the closure marking on the tape/mastic matches the UL marking called out in the table § 603.9.1.
If each of the above is met and the product documentation shows the UL listing, the run will meet the CMC material, closure and installation rules in the cited sections.
Related provisions (CMC sections)
- § 602.4 — Metallic ducts and flexible metallic ducts (SMACNA, UL 181 requirements).
- § 602.5.5 — Other nonmetallic materials: flexible and rigid ducts/plenums/fittings listed to UL 181.
- § 603.4 — Flexible air duct installation rules (support spacing, sag, length limits, fittings).
- § 603.9 / § 603.9.1 — Joints, seams, closure systems and the closure-marking table.
- § 603.1.4 / § 603.1.5 — Restrictions for vertical risers and penetrations of fire‑resistance‑rated assemblies.
Code references
Grounded in the retrieved California Mechanical Code — click a citation to read the verbatim passage:
CMC § 4.2 High relevance — show source text
2025 CALIFORNIA ENERGY CODE 77
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space.
(b) Duct and plenum materials.
- Factory-fabricated duct systems. A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. B. All pressure-sensitive tapes, heat-activated tapes, and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. D. All ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
Exception to Section 120.4(b)1D: Ductwork located in occupied space and exposed to view is not required to meet Seal Class A.
- Field-fabricated duct systems. A. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
B. Mastic sealants and mesh.
i. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
ii. Sealants for interior applications shall pass ASTM C731 (extrudability after aging) and D2202 (slump test on vertical surfaces), incorporated herein by reference. iii. Sealants for exterior applications shall pass ASTM tests C731, C732 (artificial weathering test), and D2202, incorporated herein by reference.
iv. Sealants and meshes shall be rated for exterior use.
C. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
D. All ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
Exception to Section 120.4(b)2D: Ductwork located in occupied space and exposed to view is not required to meet Seal Class A.
E. Drawbands used with flexible duct.
i. Drawbands shall be either stainless-steel worm-drive hose clamps or UV-resistant nylon duct ties. ii. Drawbands shall have a minimum tensile strength rating of 150 pounds. iii. Drawbands shall be tightened as recommended by the manufacturer with an adjustable tensioning tool.
F. Aerosol-sealant closures.
CMC § 150.0 High relevance — show source text
If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. E. Building cavities, support platforms for air handlers and plenums designed or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Exception to Section 150.0(m)1: Ducts and fans integral to a wood heater or fireplace. 2. Factory-fabricated duct systems. A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. B. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. D. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. 3. Field-fabricated duct systems. A. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
B. Mastic sealants and mesh.
i. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 18IB, and be nontoxic and water resistant.
ii. Sealants for interior applications shall be tested in accordance with ASTM C731 and D2202 incorporated herein by reference. iii. Sealants for exterior applications shall be tested in accordance with ASTM C731, C732 and D2202, incorporated herein by reference.
iv. Sealants and meshes shall be rated for exterior use.
C. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
D. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
164 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SINGLE-FAMILY RESIDENTIAL BUILDINGS— MANDATORY FEATURES AND DEVICES
E. Drawbands used with flexible duct.
i. Drawbands shall be either stainless-steel worm- drive hose clamps or UV-resistant nylon duct ties. ii. Drawbands shall have a minimum tensile strength rating of 150 pounds. iii. Drawbands shall be tightened as recommended by the manufacturer with an adjustable tensioning tool.
F. Aerosol-sealant closures.
CMC § 110.8. High relevance — show source text
B. Factory-fabricated duct systems . i. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. ii. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. iii. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. iv. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. C. Field-fabricated duct systems. i. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
ii. Mastic sealants and mesh.
a. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
b. Sealants for interior applications shall be tested in accordance with ASTM C731 and D2202, incorporated herein by reference.
2025 CALIFORNIA ENERGY CODE 215
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
c. Sealants for exterior applications shall be tested in accordance with ASTM C731, C732 and D2202, incorporated herein by reference.
d. Sealants and meshes shall be rated for exterior use.
iii. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
iv. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
v. Drawbands used with flexible duct.
a. Drawbands shall be either stainless-steel worm-drive hose clamps or UV-resistant nylon duct ties. b. Drawbands shall have a minimum tensile strength rating of 150 pounds. c. Drawbands shall be tightened as recommended by the manufacturer with an adjustable tensioning tool.
vi. Aerosol-sealant closures.
a. Aerosol sealants shall meet the requirements of UL 723 and be applied according to manufacturer specifications. b. Tapes or mastics used in combination with aerosol sealing shall meet the requirements of this section. D. Duct insulation R- value ratings. All duct insulation product R- values shall be based on insulation only (excluding air films, vapor retarder or other duct components) and tested C-values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
E. Duct insulation thickness. The installed thickness of duct insulation used to determine its R- value shall be deter mined as follows:
i. For duct board, duct liner and factory-made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used .
CMC § 4.2 High relevance — show source text
If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. B. Portions of supply-air and return-air ducts conveying heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:
i. Outdoors; or ii. In a space between the roof and an insulated ceiling; or iii. In a space directly under a roof with fixed vents or openings to the outside or unconditioned spaces; or iv. In an unconditioned crawl space; or v. In other unconditioned spaces. Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space. C. Duct and plenum materials. i. Factory-fabricated duct systems. a. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. b. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. c. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. d. Ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. Exception to Section 160.3(c)2Cid: Ductwork located in occupied space and exposed to view. ii. Field-fabricated duct systems. a. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
b. Mastic sealants and mesh.
I. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
II. Sealants for interior applications shall pass ASTM C731 (extrudability after aging) and D2202 (slump test on vertical surfaces), incorporated herein by reference. III. Sealants for exterior applications shall pass ASTM C731, C732 (artificial weathering test) and D2202, incorporated herein by reference.
IV. Sealants and meshes shall be rated for exterior use.
2025 CALIFORNIA ENERGY CODE 219
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
c. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
d. Ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
e. Drawbands used with flexible duct.
CMC § 703.1 High relevance — show source text
a. The noninsulated portion of the duct system is located entirely inside the building’s thermal envelope as confirmed by visual inspection. b. At all locations where noninsulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection. Exception 2 to Section 150.0(m)1Bi : Ducts located in an unvented attic shall have a minimum insulation value of R-4.2, verified by visual inspection where:
a. The attic has at least R-30 insulation between the roof rafters in contact with the roof deck.
b. The gable ends meet the wall insulation requirements of Section 150.1(c)1B. c. The dwelling unit achieves a whole building leakage rate of 3.0 ACH50 or less, as confirmed by field verification and diagnostic testing in accordance with Reference Residential Appendix RA3.8. ii. Ducts do not require insulation when the duct system is located entirely within conditioned space, as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. For dwelling units with attics, the duct system shall be located below the ceiling separating the occupiable space from the attic. C. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. D. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL181A or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. E. Building cavities, support platforms for air handlers and plenums designed or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Exception to Section 150.0(m)1: Ducts and fans integral to a wood heater or fireplace. 2. Factory-fabricated duct systems. A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. B. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. D. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. 3. Field-fabricated duct systems. A. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181.
CMC § 603.7.2 High relevance — show source text
603.7.2 Flexible Air Ducts. Flexible air ducts shall be supported in accordance with Section 603.4. 603.7.3 Other Ducts. Other approved ducts shall be supported in accordance with the manufacturer’s installation instructions.
603.8 Protection Against Flood Damage. In flood hazard areas, ducts shall be located above the elevation required by the building code for utilities and attendant equipment or the elevation of the lowest floor, whichever is higher, or shall be designed and constructed to prevent water from entering or accumulating within the ducts during floods up to such elevation. Where the ducts are located below that elevation, the ducts shall be capable of resisting hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to such elevation.
603.9 Joints and Seams of Ducts. Joints and seams for duct systems shall comply with SMACNA HVAC Duct Construction Standards – Metal and Flexible, SMACNA Round Industrial Duct Construction Standards, or SMACNA Rectangular Industrial Duct Construction Standards, as applicable. Joints of duct systems shall be made substantially airtight by means of tapes, mastics, gasketing, or other means. All ducts shall be sealed to Seal Class A. Crimp joints for round ducts shall have a contact lap of not less than 1 [1] ⁄ 2 inches (38 mm) and shall be mechanically fastened by means of not less than three sheet-metal screws equally spaced around the joint, or an equivalent fastening method.
2025 CALIFORNIA MECHANICAL CODE 139
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
DUCT SYSTEMS
603.9.1 Closure Systems. Joints and seams and reinforcements for air ducts and plenums listed and labeled to UL 181, shall be in accordance with the manufacturer’s installation instructions. Closure systems for sealing air ducts and plenums shall be listed and labeled in accordance with UL 181A or UL 181B, and marked in accordance with Table 603.9.1.
TABLE 603.9.1
CLOSURE MARKINGS
TYPE OF DUCTWORK STANDARD TYPE OF CLO-
SURE SYSTEMMARKING
Rigid Metallic or
Rigid FiberglassUL 181A Pressure
Sensitive Tape181A-P
Rigid Metallic or
Rigid FiberglassUL 181A Mastic Tape 181A-M
Rigid Metallic or
Rigid FiberglassUL 181A Heat
Sensitive Tape181A–H
Flexible Air DuctsUL 181B Pressure
Sensitive Tape*181B-FX*
Flexible Air DuctsUL 181B Mastic* 181B-M* - Mechanical fasteners shall be used in conjunction with a listed pressure sensitive tape or mastic in accordance with UL 181. Nonmetallic mechanical fasteners shall be listed and labeled in accordance with UL 181B and
labeled “181B-C.”
603.9.2 Duct Leakage Tests. [Not adopted by HCD] Ductwork shall be leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual.
CMC § 703.1 High relevance — show source text
ii. At all locations where noninsulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection. b. Ducts do not require insulation when the duct system is located entirely in conditioned space. For buildings with three or fewer habitable stories, duct systems located entirely in conditioned space shall be confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. iii. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. iv. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. v. Building cavities, support platforms for air handlers, and plenums designed or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. Exception to Section 160.3(b)5A: Ducts and fans integral to a wood heater or fireplace. B. Factory-fabricated duct systems . i. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. ii. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. iii. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. iv. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. C. Field-fabricated duct systems. i. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
ii. Mastic sealants and mesh.
a. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
b. Sealants for interior applications shall be tested in accordance with ASTM C731 and D2202, incorporated herein by reference.
2025 CALIFORNIA ENERGY CODE 215
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
CMC § 110.8. High relevance — show source text
** A. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
B. Mastic sealants and mesh.
i. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 18IB, and be nontoxic and water resistant.
ii. Sealants for interior applications shall be tested in accordance with ASTM C731 and D2202 incorporated herein by reference. iii. Sealants for exterior applications shall be tested in accordance with ASTM C731, C732 and D2202, incorporated herein by reference.
iv. Sealants and meshes shall be rated for exterior use.
C. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
D. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
164 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SINGLE-FAMILY RESIDENTIAL BUILDINGS— MANDATORY FEATURES AND DEVICES
E. Drawbands used with flexible duct.
i. Drawbands shall be either stainless-steel worm- drive hose clamps or UV-resistant nylon duct ties. ii. Drawbands shall have a minimum tensile strength rating of 150 pounds. iii. Drawbands shall be tightened as recommended by the manufacturer with an adjustable tensioning tool.
F. Aerosol-sealant closures.
i. Aerosol sealants shall meet the requirements of UL 723, and be applied according to manufacturer specifications. ii. Tapes or mastics used in combination with aerosol sealing shall meet the requirements of this section. 4. Duct insulation R -value ratings. All duct insulation product R -values shall be based on insulation only (excluding air films, vapor retarder or other duct components) and tested C -values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
- Duct insulation thickness. The installed thickness of duct insulation used to determine its R -value shall be determined as
follows:
A. For duct board, duct liner and factory-made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used.
B. For duct wrap, installed thickness shall be assumed to be 75 percent (25 percent compression) of nominal thickness. C. For factory-made flexible air ducts, the installed thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two. 6. Duct labeling. Insulated flexible duct products installed to meet this requirement shall include labels, in maximum intervals of 3 feet, showing the thermal performance R -value for the duct insulation itself (excluding air films, vapor retarders or other duct components), based on the tests in Section 150.0(m)4 and the installed thickness determined by Section 150.0(m)5C. 7. **Backdraft dampers.
CMC § 120.4 High relevance — show source text
Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 120.4(a) through 120.4(g).
Exception to Section 120.4: Systems serving healthcare facilities shall comply with the applicable requirements of the California Mechanical Code.
(a) CMC compliance. All air distribution system ducts and plenums, including but not limited to building cavities, mechanical closets, air-handler boxes and support platforms used as ducts or plenums, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0, and 605.0, and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible, 3rd Edition incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used.
Portions of supply-air and return-air ducts conveying heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:
Outdoors; or
In a space between the roof and an insulated ceiling; or
In a space directly under a roof with fixed vents or openings to the outside or unconditioned spaces; or
In an unconditioned crawlspace; or
In other unconditioned spaces.
2025 CALIFORNIA ENERGY CODE 77
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space.
(b) Duct and plenum materials.
- Factory-fabricated duct systems. A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. B. All pressure-sensitive tapes, heat-activated tapes, and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. D. All ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
Exception to Section 120.4(b)1D: Ductwork located in occupied space and exposed to view is not required to meet Seal Class A.
CMC § 160.3 High relevance — show source text
Exception 2 to Section 160.3(c)1: Piping that conveys fluids with a design operating temperature range between 60°F and 105°F.
Exception 3 to Section 160.3(c)1: Where the heat gain or heat loss to or from piping without insulation will not increase building source energy use. Exception 4 to Section 160.3(c)1: Piping that penetrates framing members shall not be required to have pipe insulation for the distance of the framing penetration. Metal piping that penetrates metal framing shall use grommets, plugs, wrapping or other insulating material to ensure that no contact is made with the metal framing. 2. Requirements for air distribution system, ducts and plenum. Multifamily common areas shall comply with the applicable requirements of Sections 160.3(c)2A through 160.3(c)2F. A. CMC compliance. All air distribution system ducts and plenums, including, but not limited to, building cavities, mechanical closets, air-handler boxes and support platforms used as ducts or plenums shall meet the requirements of CMC Sections 601.0, 602.0, 603.0, 604.0 and 605.0, and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition, incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. B. Portions of supply-air and return-air ducts conveying heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:
i. Outdoors; or ii. In a space between the roof and an insulated ceiling; or iii. In a space directly under a roof with fixed vents or openings to the outside or unconditioned spaces; or iv. In an unconditioned crawl space; or v. In other unconditioned spaces. Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space. C. Duct and plenum materials. i. Factory-fabricated duct systems. a. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. b. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. c. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. d. Ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
CMC § 110.8. High relevance — show source text
(c) All duct insulation product R -values shall be based on insulation only (excluding air films, vapor retarders or other duct components) and tested C -values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
(d) The installed thickness of duct insulation used to determine its R -value shall be determined as follows:
For duct board, duct liner and factory-made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used.
For duct wrap, installed thickness shall be assumed to be 75 percent (25 percent compression) of nominal thickness.
For factory-made flexible air ducts, the installed thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two.
(e) Insulated flexible duct products installed to meet this requirement must include labels, in maximum intervals of 3 feet, showing the thermal performance R -value for the duct insulation itself (excluding air films, vapor retarder or other duct components), based on the tests in Section 120.4(c) and the installed thickness determined by Section 120.4(d)3.
(f) Protection of insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance and wind, but not limited to the following:
78 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet metal, painted canvas or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material.
(g) Duct sealing. Duct systems shall comply with Subsection 1 or 2 below:
- New duct systems that meet the criteria in Subsections A, B, C and D below shall be sealed to a leakage rate not to exceed 6 percent of the nominal air handler airflow rate as confirmed through acceptance testing, in accordance with Reference Nonresidential Appendix NA7.5.3; A. The duct system does not serve a healthcare facility; and B. The duct system provides conditioned air to an occupiable space for a constant volume, single zone, space-conditioning system; and C. The space-conditioning system serves less than 5,000 square feet of conditioned floor area; and D. The combined surface area of the ducts located outdoors or in unconditioned space is more than 25 percent of the total surface area of the entire duct system.
- New duct systems that are not subject to testing under Section 120.4(g)1 shall instead meet the duct leakage testing requirements of CMC Section 603.9.2.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.
SECTION 120.5—REQUIRED NONRESIDENTIAL MECHANICAL SYSTEM ACCEPTANCE
CMC § 110.8. High relevance — show source text
F. Aerosol-sealant closures.
i. Aerosol sealants shall meet the requirements of UL 723, and be applied according to manufacturer specifications. ii. Tapes or mastics used in combination with aerosol sealing shall meet the requirements of this section. 4. Duct insulation R -value ratings. All duct insulation product R -values shall be based on insulation only (excluding air films, vapor retarder or other duct components) and tested C -values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
- Duct insulation thickness. The installed thickness of duct insulation used to determine its R -value shall be determined as
follows:
A. For duct board, duct liner and factory-made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used.
B. For duct wrap, installed thickness shall be assumed to be 75 percent (25 percent compression) of nominal thickness. C. For factory-made flexible air ducts, the installed thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two. 6. Duct labeling. Insulated flexible duct products installed to meet this requirement shall include labels, in maximum intervals of 3 feet, showing the thermal performance R -value for the duct insulation itself (excluding air films, vapor retarders or other duct components), based on the tests in Section 150.0(m)4 and the installed thickness determined by Section 150.0(m)5C. 7. Backdraft dampers. All fan systems, regardless of volumetric capacity, that exchange air between the building conditioned space and the outside of the building shall be provided with backdraft or automatic dampers to prevent unintended air leakage through the fan system when the fan system is not operating. 8. Gravity ventilation dampers. All gravity ventilating systems that serve conditioned space shall be provided with either automatic or readily accessible, manually operated dampers in all openings to the outside except combustion inlet and outlet air openings and elevator shaft vents. 9. Protection of insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance and wind, but not limited to the following: Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet metal, painted canvas or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material.
- Porous inner core flex duct. Flexible ducts having porous inner cores shall have a non-porous layer or air barrier between the inner core and the outer vapor barrier.
- Duct system sealing and leakage testing. When space-conditioning systems utilize forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be sealed as confirmed through field verification and diagnostic testing in accordance with all applicable procedures specified in Reference Residential Appendix RA3.1, and conforming to one of the following Subsections A, B or C as applicable. Air handler airflow for calculation of duct leakage rate compliance targets shall be determined according to methods specified in Reference Residential Appendix RA3.1.4.2.
CMC § 0.50 High relevance — show source text
(8) Materials in a hazardous fabrication area including the areas above and below the fabrication area sharing a common air recirculation path with the fabrication area.
(9) Plastic water distribution piping listed and labeled for use in plenums in accordance with UL 2846 as having a peak optical density not greater than 0.50, an average optical density not greater than 0.15, and a flame spread distance not greater than 5 feet (1524 mm), and installed in accordance with its listing, shall be permitted.
602.2.1 Electrical. Electrical wiring in plenums shall comply with the California Electrical Code . Electrical wires and cables and optical fiber cables shall be listed and labeled for use in plenums and shall have a flame spread distance not exceeding 5 feet (1524 mm), an average optical density not exceeding 0.15, and a peak optical density not exceeding 0.5, where tested in accordance with NFPA 262.
602.2.2 Fire Sprinkler Piping. Nonmetallic fire sprinkler piping in plenums shall be listed and labeled for use in plenums and shall have a flame spread distance not exceeding 5 feet (1524 mm), an average optical density not exceeding 0.15 and, a peak optical density not exceeding 0.5, where tested in accordance with UL 1887.
602.2.3 Pneumatic Tubing. Nonmetallic pneumatic tubing in plenums shall be listed and labeled for use in plenums and shall have a flame spread distance not exceeding 5 feet (1524 mm), an average optical density not exceeding 0.15, and a peak optical density not exceeding 0.5, where tested in accordance with UL 1820.
602.2.4 Discrete Products in Plenums. Discrete plumbing, mechanical, and electrical products that are located in a plenum and have exposed combustible material shall be listed and labeled in accordance with UL
602.3 Tall Wood (Mass Timber) Buildings. Duct systems installed in tall wood (mass timber) buildings shall comply with the following:
(1) Be designed by a registered design professional in accordance with this code and the building code.
(2) Be designed to accommodate expansion, contraction, and differential movement between parts of a tall wood (mass timber) building in accordance with Section 316.2.
2025 CALIFORNIA MECHANICAL CODE 137
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
DUCT SYSTEMS
»
»
»
»
»
»
»
»
602.4 Metallic. Ducts, plenums, or fittings of metal shall comply with SMACNA HVAC Duct Construction Standards – Metal and Flexible. Flexible metallic ducts shall comply with UL 181.
602.5 Nonmetallic Ducts. Nonmetallic ducts shall comply with Section 602.5.1, Section 602.5.2, Section 602.5.3, Section 602.5.4, or Section 602.5.5.
602.5.1 Phenolic. Phenolic duct, plenum, or fitting material shall comply with UL 181. Ducts, plenums, or fittings of phenolic shall be constructed in accordance with SMACNA Phenolic Duct Construction Standards or the conditions of its listing.
CMC § 160.3 High relevance — show source text
Exception to Section 160.3(c)2Cid: Ductwork located in occupied space and exposed to view. ii. Field-fabricated duct systems. a. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
b. Mastic sealants and mesh.
I. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
II. Sealants for interior applications shall pass ASTM C731 (extrudability after aging) and D2202 (slump test on vertical surfaces), incorporated herein by reference. III. Sealants for exterior applications shall pass ASTM C731, C732 (artificial weathering test) and D2202, incorporated herein by reference.
IV. Sealants and meshes shall be rated for exterior use.
2025 CALIFORNIA ENERGY CODE 219
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
c. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
d. Ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
e. Drawbands used with flexible duct.
I. Drawbands shall be either stainless-steel worm-drive hose clamps or UV-resistant nylon duct ties. II. Drawbands shall have a minimum tensile strength rating of 150 pounds. III. Drawbands shall be tightened as recommended by the manufacturer with an adjustable tensioning tool.
f. Aerosol-sealant closures.
I. Aerosol sealants shall meet the requirements of UL 723 and be applied according to manufacturer specifications. II. Tapes or mastics used in combination with aerosol sealing shall meet the requirements of this section.
D. All duct insulation product R- values shall be based on insulation only (excluding air films, vapor retarders or other duct components) and tested C-values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
E. The installed thickness of duct insulation used to determine its R- value shall be determined as follows:
i. For duct board, duct liner and factory-made rigid ducts not normally subjected to compression, the nominal insulation thickness shall be used.
ii. For duct wrap, installed thickness shall be assumed to be 75 percent (25 percent compression) of nominal thickness.
iii. For factory-made flexible air ducts, the installed thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two. F. Insulated flexible duct products installed to meet this requirement must include labels, in maximum intervals of 3 feet, showing the thermal performance R- value for the duct insulation itself (excluding air films, vapor retarder or other duct components), based on the tests in Section 160.3(c)2D and the installed thickness determined by Section 160.3(c)2Eiii.
Frequently asked questions
What is the single test/listing I should look for on factory-made flexible duct?
Look for the UL 181 listing on the product label or manufacturer documentation; flexible ducts must be listed and labeled to UL 181 per § 602.5.5.
Do closure tapes need a special marking?
Yes — closure tapes and mastics must be listed and labeled per UL 181A/181B and be marked as required by the closure marking table in § 603.9.1 (e.g., 181B‑FX, 181B‑M).
Can I use flexible ducts anywhere?
No — flexible ducts are permitted but are limited by length, support, and location rules (see § 603.4 and § 603.4.1). Also, UL‑listed ducts cannot be used as vertical risers serving more than two stories or to penetrate fire‑rated assemblies.
Are nonmetallic factory-made ducts allowed?
Yes — but only if they are listed and labeled to UL 181 (see § 602.5.5). Plastic ducts are a special case and must follow § 603.5.
What does “Seal Class A” mean for my ductwork?
It means the duct system must be sealed to the higher airtightness classification required by the code; all ducts are required to be sealed to Seal Class A per § 603.1.1 and § 603.9.
More in California Mechanical Code
Ask about the CMC
Get cited, plain-English answers on the California Mechanical Code for your project — any code section, any scenario.
Start Free Trial