CMC · California Mechanical Code

What materials are permitted for ducts, plenums and fittings?

The CMC allows metal ducts (built to SMACNA) and certain nonmetallic ducts only when they meet the Code’s specific sub‑sections or are UL‑listed — phenolic requires UL 181 + SMACNA phenolic standards, fibrous glass must follow SMACNA or NAIMA standards, and other nonmetallic products must be UL 181 listed; plastic ducts are handled separately. Always use listed products and follow the referenced standards to be code‑compliant.

Last reviewed: July 6, 2026

What the code requires — 2–4 sentences

The California Mechanical Code requires that ducts, plenums, and fittings be made of materials and assemblies that meet the construction standards or listings referenced in the Code. In particular, metallic systems must follow SMACNA standards (and flexible metallic ducts must meet UL 181) (see § 602.4). Nonmetallic systems are allowed only where they comply with the specific nonmetallic sub‑sections or are listed to UL 181 (see § 602.5, § 602.5.1, § 602.5.4) .

The single most important rule: use the material or assembly specifically required or listed by the CMC (SMACNA standards or the applicable UL listing) — you cannot substitute an unlisted or unstandardized material and still be in compliance.

Requirements in detail

Metallic materials

  • Allowed material: metal for ducts, plenums, or fittings.
  • Required standards: constructed in accordance with SMACNA HVAC Duct Construction Standards – Metal and Flexible. Flexible metallic ducts must comply with UL 181. See § 602.4.

Nonmetallic materials — overview

  • Nonmetallic ducts are permitted only if they meet one of the specific nonmetallic subsections or are listed to UL 181. See § 602.5.

Phenolic

  • Phenolic duct, plenum or fitting material must comply with UL 181 and be constructed per SMACNA Phenolic Duct Construction Standards or the conditions of its listing. See § 602.5.1.

Fibrous glass

  • Fibrous glass ducts, plenums, or fittings must be constructed in accordance with SMACNA Fibrous Glass Duct Construction Standards or NAIMA Fibrous Glass Duct Construction Standards. See § 602.5.4.

Other nonmetallic materials

  • Flexible and rigid ducts, plenums or fittings made of other nonmetallic materials are permitted only if they are listed and labeled to UL 181. See § 602.5.5 (within § 602.5). Note: plastic ducts are specifically addressed elsewhere and must comply with § 603.5 per the CMC exception. See § 602.5 and the exception.

Decision-relevant dimensions, thresholds and listings (quick reference)

Topic / value What it means for the designer/installer Code Reference
Material for metal ducts Must comply with SMACNA HVAC Duct Construction Standards – Metal and Flexible; flexible metallic ducts must meet UL 181 § 602.4
Phenolic ducts/fittings Must comply with UL 181 and be constructed per SMACNA Phenolic Standards or listed conditions § 602.5.1
Fibrous glass ducts/fittings Must be built to SMACNA Fibrous Glass or NAIMA Fibrous Glass standards § 602.5.4
Other nonmetallic materials Only permitted if listed & labeled to UL 181 § 602.5 / § 602.5.5
Plastic ducts (special) Plastic ducts are governed by § 603.5 (see exception in § 602.5) Exception to § 602.5
Gypsum exposed in plenums (temperature) If gypsum products are exposed in ducts/plenums, air temp must be 50°F (10°C) to 125°F (52°C) and moisture controlled; gypsum not allowed in supply ducts § 602.5.2

(Where a UL listing is required, use the listed product and follow manufacturer/listing conditions. The Code references UL and SMACNA standards by section — follow both the Code and the referenced standard.)

Exceptions & special cases

  • The § 602.5 text permits “other nonmetallic materials” only when listed and labeled to UL 181; plastic ducts are excluded from general § 602.5 and must comply with § 603.5 instead (the Code explicitly notes this exception). See § 602.5 and its exception .
  • The Code separately addresses discrete products in plenums and requires those with exposed combustible material to be listed per UL 2043 (see related plenum listing requirements in § 602.2.4) — important when you put non‑duct equipment into a plenum space .
  • For underground installations the Code permits ducts, plenums and fittings of concrete, clay or ceramics where installed in the ground or in a concrete slab, provided joints are sealed and duct is secured per SMACNA standards; metal ducts in or under a slab must be encased in at least 2 inches (51 mm) of concrete. See § 603.11 for these special provisions .

Common mistakes

  • Assuming “any plastic” is allowed in plenums: the Code requires specific listing/ratings (UL 181 or other plenum listings) and separates plastic ducts to § 603.5. Don’t install unlisted plastic in a plenum and assume compliance. See § 602.5 and its exception .
  • Using nonlisted rigid fiberglass or sealants that don’t meet UL requirements. Factory or field-fabricated fibrous glass ducts and their tapes/mastics must meet UL 181/UL 181A/UL 181B as applicable and SMACNA/NAIMA standards — check both the Code section and the referenced standards. See § 602.5.4 and related UL references in the Code .
  • Installing ductboard / building cavities as plenums or primary air paths when they are not constructed and sealed per the Code and referenced SMACNA/UL standards. The Energy Code and CMC prohibit using building cavities or non‑sealed platforms to convey conditioned air unless they meet CMC materials/assembly requirements .
  • Using ducts listed to UL 181 as vertical risers serving more than two stories — the Code limits UL 181‑listed ducts for vertical risers in multi‑story applications. See § 603.1.4 for this specific restriction .

Worked example — choosing a duct material for a return plenum

Scenario: You need to construct a return plenum inside a commercial tenant space. The owner prefers a factory‑made ductboard alternative.

Step 1 — Verify application: The space is an interior return plenum (not underground) and will not be used as a vertical riser. The owner wants nonmetallic material with good thermal properties.

Step 2 — Check allowable materials: Nonmetallic ducts are allowed only per § 602.5. If you choose phenolic, that material must be listed to UL 181 and constructed per SMACNA Phenolic Duct Construction Standards per § 602.5.1. If you choose fibrous glass, the assembly must follow SMACNA Fibrous Glass or NAIMA standards per § 602.5.4 .

Step 3 — Choose product and documentation: Select a phenolic duct product that is labeled to UL 181 and obtain the manufacturer’s listing and SMACNA construction instructions. Record the UL labeling and the SMACNA/UL compliance documentation in the project submittal (the Code requires listed materials and construction to the referenced standard) (§ 602.5.1; § 602.5) .

Step 4 — Install per listing and referenced standard: Install the phenolic duct per the manufacturer’s listing conditions and SMACNA phenolic standards; use compatible UL‑listed closure systems (UL 181 tapes/mastics) for joints. Confirm the installation documentation at inspection to demonstrate compliance with § 602.5.1 and § 602.5 .

Related provisions

  • § 602.2.4 — Discrete products in plenums (UL 2043 listing for products located in plenums) .
  • § 602.5.2 — Gypsum products exposed in ducts/plenums (temperature 50°F to 125°F; gypsum not allowed in supply ducts) .
  • § 602.5.5 — Other nonmetallic materials permitted if listed to UL 181 (see § 602.5) .
  • § 603.1.4 — Ducts listed to UL 181 shall not be used for vertical risers serving more than two stories .
  • § 603.11 — Underground installations may use concrete, clay, or ceramics for ducts/plenums where installed in the ground or slab; metal ducts under slab require 2 inches (51 mm) of concrete encasement .

Code references

Grounded in the retrieved California Mechanical Code — click a citation to read the verbatim passage:

  • CMC § 0.50 High relevance — show source text

    (8) Materials in a hazardous fabrication area including the areas above and below the fabrication area sharing a common air recirculation path with the fabrication area.

    (9) Plastic water distribution piping listed and labeled for use in plenums in accordance with UL 2846 as having a peak optical density not greater than 0.50, an average optical density not greater than 0.15, and a flame spread distance not greater than 5 feet (1524 mm), and installed in accordance with its listing, shall be permitted.

    602.2.1 Electrical. Electrical wiring in plenums shall comply with the California Electrical Code . Electrical wires and cables and optical fiber cables shall be listed and labeled for use in plenums and shall have a flame spread distance not exceeding 5 feet (1524 mm), an average optical density not exceeding 0.15, and a peak optical density not exceeding 0.5, where tested in accordance with NFPA 262.

    602.2.2 Fire Sprinkler Piping. Nonmetallic fire sprinkler piping in plenums shall be listed and labeled for use in plenums and shall have a flame spread distance not exceeding 5 feet (1524 mm), an average optical density not exceeding 0.15 and, a peak optical density not exceeding 0.5, where tested in accordance with UL 1887.

    602.2.3 Pneumatic Tubing. Nonmetallic pneumatic tubing in plenums shall be listed and labeled for use in plenums and shall have a flame spread distance not exceeding 5 feet (1524 mm), an average optical density not exceeding 0.15, and a peak optical density not exceeding 0.5, where tested in accordance with UL 1820.

    602.2.4 Discrete Products in Plenums. Discrete plumbing, mechanical, and electrical products that are located in a plenum and have exposed combustible material shall be listed and labeled in accordance with UL

    602.3 Tall Wood (Mass Timber) Buildings. Duct systems installed in tall wood (mass timber) buildings shall comply with the following:

    (1) Be designed by a registered design professional in accordance with this code and the building code.

    (2) Be designed to accommodate expansion, contraction, and differential movement between parts of a tall wood (mass timber) building in accordance with Section 316.2.

    2025 CALIFORNIA MECHANICAL CODE 137

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    DUCT SYSTEMS

    »

    »

    »

    »

    »

    »

    »

    »

    602.4 Metallic. Ducts, plenums, or fittings of metal shall comply with SMACNA HVAC Duct Construction Standards – Metal and Flexible. Flexible metallic ducts shall comply with UL 181.

    602.5 Nonmetallic Ducts. Nonmetallic ducts shall comply with Section 602.5.1, Section 602.5.2, Section 602.5.3, Section 602.5.4, or Section 602.5.5.

    602.5.1 Phenolic. Phenolic duct, plenum, or fitting material shall comply with UL 181. Ducts, plenums, or fittings of phenolic shall be constructed in accordance with SMACNA Phenolic Duct Construction Standards or the conditions of its listing.

  • CMC § 602.2.4 High relevance — show source text

    602.2.4 Discrete Products in Plenums. Discrete plumbing, mechanical, and electrical products that are located in a plenum and have exposed combustible material shall be listed and labeled in accordance with UL

    602.3 Tall Wood (Mass Timber) Buildings. Duct systems installed in tall wood (mass timber) buildings shall comply with the following:

    (1) Be designed by a registered design professional in accordance with this code and the building code.

    (2) Be designed to accommodate expansion, contraction, and differential movement between parts of a tall wood (mass timber) building in accordance with Section 316.2.

    2025 CALIFORNIA MECHANICAL CODE 137

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    DUCT SYSTEMS

    »

    »

    »

    »

    »

    »

    »

    »

    602.4 Metallic. Ducts, plenums, or fittings of metal shall comply with SMACNA HVAC Duct Construction Standards – Metal and Flexible. Flexible metallic ducts shall comply with UL 181.

    602.5 Nonmetallic Ducts. Nonmetallic ducts shall comply with Section 602.5.1, Section 602.5.2, Section 602.5.3, Section 602.5.4, or Section 602.5.5.

    602.5.1 Phenolic. Phenolic duct, plenum, or fitting material shall comply with UL 181. Ducts, plenums, or fittings of phenolic shall be constructed in accordance with SMACNA Phenolic Duct Construction Standards or the conditions of its listing.

    602.5.2 Gypsum. Where gypsum products are exposed in ducts or plenums, the air temperature shall be restricted to a range from 50°F (10°C) to 125°F (52°C), and moisture content shall be controlled so that the material is not adversely affected. All gypsum products shall have a mold or mildew resistant surface. For the purpose of this section, gypsum products shall not be exposed in supply ducts.

    602.5.3 Air Dispersion Systems. Air dispersion systems shall be listed and labeled in accordance with UL

    602.5.4 Fibrous Glass Duct. Fibrous glass ducts, plenums, or fittings shall be constructed in accordance with SMACNA Fibrous Glass Duct Construction Stan dards or NAIMA Fibrous Glass Duct Construction Stan dards.

    602.5.5 Other Materials. Flexible and rigid ducts, plenums, or fittings for use in heating, ventilation, and air conditioning systems of other nonmetallic materials listed and labeled to UL 181 shall be permitted.

    Exception: Plastic ducts shall comply with Section 603.5.

    602.6 Vibration Isolators. Vibration isolation connectors installed between mechanical equipment and metal ducts (or casings) shall be made of an approved material and shall not exceed 10 inches (254 mm) in length.

    602.7 Corridors. Corridors shall not be used to convey air to or from rooms where the corridor is required to be of fire-resistive construction in accordance with the building code except where permitted by the building code. Corridors shall not serve as supply, return, exhaust, relief, or ventilation air ducts.

    603.0 Installation of Ducts.

  • CMC § 602.5.2 High relevance — show source text

    602.5.2 Gypsum. Where gypsum products are exposed in ducts or plenums, the air temperature shall be restricted to a range from 50°F (10°C) to 125°F (52°C), and moisture content shall be controlled so that the material is not adversely affected. All gypsum products shall have a mold or mildew resistant surface. For the purpose of this section, gypsum products shall not be exposed in supply ducts.

    602.5.3 Air Dispersion Systems. Air dispersion systems shall be listed and labeled in accordance with UL

    602.5.4 Fibrous Glass Duct. Fibrous glass ducts, plenums, or fittings shall be constructed in accordance with SMACNA Fibrous Glass Duct Construction Stan dards or NAIMA Fibrous Glass Duct Construction Stan dards.

    602.5.5 Other Materials. Flexible and rigid ducts, plenums, or fittings for use in heating, ventilation, and air conditioning systems of other nonmetallic materials listed and labeled to UL 181 shall be permitted.

    Exception: Plastic ducts shall comply with Section 603.5.

    602.6 Vibration Isolators. Vibration isolation connectors installed between mechanical equipment and metal ducts (or casings) shall be made of an approved material and shall not exceed 10 inches (254 mm) in length.

    602.7 Corridors. Corridors shall not be used to convey air to or from rooms where the corridor is required to be of fire-resistive construction in accordance with the building code except where permitted by the building code. Corridors shall not serve as supply, return, exhaust, relief, or ventilation air ducts.

    603.0 Installation of Ducts.

    603.1 General. Air ducts shall be installed in accordance with this chapter and the installation instructions.

    603.1.1 Pressure Classification. The pressure classification of ducts shall be not less than the design operating pressure of the air distribution in which the duct is utilized. All ducts regardless of pressure classification(s) shall be sealed to Seal Class A.

    603.1.2 Air Temperature. The temperature of the air to be conveyed in a duct shall not exceed 250°F (121°C).

    603.1.3 Protection. Air ducts, other than plastic ducts, shall be installed with not less than 4 inches (102 mm) of

    separation from earth, except where installed as a liner inside of concrete, tile, or metal pipe and shall be protected from physical damage.

    603.1.4 Vertical Risers. Ducts listed and labeled to UL 181 shall not be used for vertical risers in air-duct systems serving more than two stories.

    603.1.5 Penetrations. Ducts listed and labeled to UL 181 shall not penetrate a fire-resistance-rated assembly or construction.

    603.1.6 Earthquake Loads. Ducts located in structures that are installed in areas classified as seismic design categories shall be restrained to resist displacement due to earthquake motion.

    603.2 Under-Floor or Crawl Space. Air ducts installed under a floor in a crawl space shall be installed in accordance with the following:

    (1) Shall not prevent access to an area of the crawl space.

    (2) Where it is required to move under ducts for access to areas of the crawl space, a vertical clearance of not less than 18 inches (457 mm) shall be provided.

  • CMC § 1.0 High relevance — show source text

    D. The outdoor design temperatures for cooling shall be no greater than the 1.0 percent Cooling Dry Bulb and Mean Coincident Wet Bulb values.

    214 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS

    1. Outdoor condensing units . A. Clearances. Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least 5 feet (1.5 meters) from the outlet of any dryer vent. B. Liquid line drier. Installed air conditioner and heat pump systems shall be equipped with liquid line filter driers if required, as specified by manufacturer’s instructions.
    2. Central forced-air heating furnaces . A. Temperature rise . Central forced-air heating furnace installations shall be configured to operate in conformance with the furnace manufacturer's maximum inlet-to-outlet temperature rise specifications.
    3. Air-distribution and ventilation system ducts, plenums and fans. A. CMC compliance.

    i. All air-distribution system ducts and plenums, including, but not limited to, mechanical closets and air-handler boxes, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0 and 605.0 and ANSI/SMACNA006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition, incorporated herein by reference. ii. Portions of supply-air and return-air ducts and plenums of a space heating or cooling system shall be insulated in accordance with either Subsection a or b below:

    a. Ducts shall have a minimum installed level of R-6.0, or

    Exception to Section 160.3(b)5Aiia : Portions of the duct system located in conditioned space below the ceiling separating the occupiable space from the attic are not required to be insulated if all of the following conditions are met: i. The noninsulated portion of the duct system is located entirely inside the building’s thermal envelope as confirmed by visual inspection. ii. At all locations where noninsulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection. b. Ducts do not require insulation when the duct system is located entirely in conditioned space. For buildings with three or fewer habitable stories, duct systems located entirely in conditioned space shall be confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. iii. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. iv. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. v. Building cavities, support platforms for air handlers, and plenums designed or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air.

  • CMC § 0.65 High relevance — show source text

    Duct leakage tests shall be performed by a technician certified by the Associated Air Balance Council (AABC), the National Environmental Balancing Bureau (NEBB), the Testing, Adjusting and Balancing Bureau (TABB), or other equivalent approved agencies. Representative sections totaling not less than 10 percent of the total installed duct area shall be tested. Where the tested 10 percent fail to comply with the requirements of this section, then 40 percent of the total installed duct area shall be tested. Where the tested 40 percent fail to comply with the requirements of this section, then 100 percent of the total installed duct area shall be tested. Sections shall be selected by the building owner or designated representative of the building owner. Positive pressure leakage testing shall be permitted for negative pressure ductwork. The permitted duct leakage shall be not more than the following:

    Lmax = CLP [0.65 ] (Equation 603.9.2)

    Where:

    Lmax = maximum permitted leakage, (ft [3] /min)/100 square feet [0.0001 (m [3] /s)/m [2] ] duct surface

    area.

    CL = six, duct leakage class, (ft [3] /min)/100 square feet [0.0001 (m [3] /s)/m [2] ] duct surface area at 1 inch water column (0.2 kPa).

    P = test pressure, which shall be equal to the design duct pressure class rating, inch water column (kPa).

    Exception: Transfer air duct operating at less than 1 inch of water column (0.25 kPa). 603.9.2.1 Duct Leakage Tests for Buildings that Meet Air Distribution System Duct Leak- age Sealing Criteria in Title 24, Part 6. For duct leakage testing, see California Energy Code Sec- tions 150.0(m)(11) for single family buildings, Sec- tion 160.3(b) for multifamily buildings, and Section 120.4(g) for nonresidential and Hotel Motel build- ings. 603.10 Cross Contamination. Exhaust ducts that convey Class 4 air shall be negatively pressurized relative to ducts, plenums, or occupiable spaces through which the ducts pass. Exhaust ducts under positive pressure that convey Class 2 or Class 3 air shall not extend into or pass through ducts, plenums, or occupiable spaces other than the space from which the exhaust air is drawn.

    603.11 Underground Installation. Ducts installed underground shall be approved for the installation and shall have a slope of not less than [1] ⁄ 8 inch per foot (10.4 mm/m) back to the main riser. Ducts, plenums, and fittings shall be permitted to be constructed of concrete, clay, or ceramics where installed in the ground or in a concrete slab, provided the joints are sealed and duct is secured in accordance with SMACNA

    HVAC Duct Construction Standards – Metal and Flexible.

    Metal ducts where installed in or under a concrete slab shall be encased in not less than 2 inches (51 mm) of concrete, secured in accordance with SMACNA HVAC Duct Con struction Standards – Metal and Flexible.

  • CMC § 120.4 High relevance — show source text

    Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 120.4(a) through 120.4(g).

    Exception to Section 120.4: Systems serving healthcare facilities shall comply with the applicable requirements of the California Mechanical Code.

    (a) CMC compliance. All air distribution system ducts and plenums, including but not limited to building cavities, mechanical closets, air-handler boxes and support platforms used as ducts or plenums, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0, and 605.0, and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible, 3rd Edition incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used.

    Portions of supply-air and return-air ducts conveying heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:

    1. Outdoors; or

    2. In a space between the roof and an insulated ceiling; or

    3. In a space directly under a roof with fixed vents or openings to the outside or unconditioned spaces; or

    4. In an unconditioned crawlspace; or

    5. In other unconditioned spaces.

    2025 CALIFORNIA ENERGY CODE 77

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS

    Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space.

    (b) Duct and plenum materials.

    1. Factory-fabricated duct systems. A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. B. All pressure-sensitive tapes, heat-activated tapes, and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. D. All ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.

    Exception to Section 120.4(b)1D: Ductwork located in occupied space and exposed to view is not required to meet Seal Class A.

  • CMC § 160.3 High relevance — show source text

    Exception 2 to Section 160.3(c)1: Piping that conveys fluids with a design operating temperature range between 60°F and 105°F.

    Exception 3 to Section 160.3(c)1: Where the heat gain or heat loss to or from piping without insulation will not increase building source energy use. Exception 4 to Section 160.3(c)1: Piping that penetrates framing members shall not be required to have pipe insulation for the distance of the framing penetration. Metal piping that penetrates metal framing shall use grommets, plugs, wrapping or other insulating material to ensure that no contact is made with the metal framing. 2. Requirements for air distribution system, ducts and plenum. Multifamily common areas shall comply with the applicable requirements of Sections 160.3(c)2A through 160.3(c)2F. A. CMC compliance. All air distribution system ducts and plenums, including, but not limited to, building cavities, mechanical closets, air-handler boxes and support platforms used as ducts or plenums shall meet the requirements of CMC Sections 601.0, 602.0, 603.0, 604.0 and 605.0, and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition, incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. B. Portions of supply-air and return-air ducts conveying heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:

    i. Outdoors; or ii. In a space between the roof and an insulated ceiling; or iii. In a space directly under a roof with fixed vents or openings to the outside or unconditioned spaces; or iv. In an unconditioned crawl space; or v. In other unconditioned spaces. Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space. C. Duct and plenum materials. i. Factory-fabricated duct systems. a. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. b. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. c. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. d. Ductwork and plenums with pressure class ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.

  • CMC § 8.5 High relevance — show source text

    21_–0.27|75|0.75 inch|0.75 inch|1.0 inch|1.0 inch|1.0 inch| |Residential
    4060|0.210.27|75|R-6|R-5|R-7|R-6|R-5| |Nonresidential
    4060|0.210.27|75|0.5 inch|0.5 inch|1.0 inch|1.0 inch|1.0 inch| |Nonresidential
    4060|0.210.27|75|R-3|R-3|R-7|R-6|R-5| |Below 40|0.200.26|50|1.0 inch|1.5 inches|1.5 inches|1.5 inches|1.5 inches| |Below 40|0.200.26|50|R 8.5|R 14|R 12|R 10|R 9|

    Footnote to Table 120.3-A-1 and Table 120.3-A-2: These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders or additional insulation.

    SECTION 120.4—REQUIREMENTS FOR AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS

    Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 120.4(a) through 120.4(g).

    Exception to Section 120.4: Systems serving healthcare facilities shall comply with the applicable requirements of the California Mechanical Code.

    (a) CMC compliance. All air distribution system ducts and plenums, including but not limited to building cavities, mechanical closets, air-handler boxes and support platforms used as ducts or plenums, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0, and 605.0, and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible, 3rd Edition incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used.

    Portions of supply-air and return-air ducts conveying heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:

    1. Outdoors; or

    2. In a space between the roof and an insulated ceiling; or

    3. In a space directly under a roof with fixed vents or openings to the outside or unconditioned spaces; or

    4. In an unconditioned crawlspace; or

    5. In other unconditioned spaces.

    2025 CALIFORNIA ENERGY CODE 77

  • CMC § 140.8 High relevance — show source text

    C. An energy management control system (EMCS) or other controls that provides the specified lighting control functionality and complies with all requirements applicable to the specified controls may be used to meet these requirements. 4. Internally illuminated address signs. Internally illuminated address signs shall either: A. Comply with Section 140.8; or B. Consume no more than 5 watts of power. 5. Residential garages for eight or more vehicles. Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130.1, 130.4, 140.6 and 141.0.

    (l) Reserved.

    (m) Air-distribution and ventilation system ducts, plenums and fans.

    1. CMC compliance.

    A. All air-distribution system ducts and plenums, including but not limited to, mechanical closets and air-handler boxes, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0, 605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible, 3rd Edition, incorporated herein by reference.

    2025 CALIFORNIA ENERGY CODE 163

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    SINGLE-FAMILY RESIDENTIAL BUILDINGS— MANDATORY FEATURES AND DEVICES

    B. Portions of supply-air and return-air ducts and plenums of a space heating or cooling system shall be insulated in accordance with either Subsection i or ii below:

    i. Ducts shall have a minimum installed level of R-6.0, or Exception 1 to Section 150.0(m)1Bi: Portions of the duct system located in conditioned space below the ceiling separating the occupiable space from the attic are not required to be insulated if all of the following conditions are met:

    a. The noninsulated portion of the duct system is located entirely inside the building’s thermal envelope as confirmed by visual inspection. b. At all locations where noninsulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection. Exception 2 to Section 150.0(m)1Bi : Ducts located in an unvented attic shall have a minimum insulation value of R-4.2, verified by visual inspection where:

    a. The attic has at least R-30 insulation between the roof rafters in contact with the roof deck.

    b. The gable ends meet the wall insulation requirements of Section 150.1(c)1B. c. The dwelling unit achieves a whole building leakage rate of 3.0 ACH50 or less, as confirmed by field verification and diagnostic testing in accordance with Reference Residential Appendix RA3.8. ii. Ducts do not require insulation when the duct system is located entirely within conditioned space, as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. For dwelling units with attics, the duct system shall be located below the ceiling separating the occupiable space from the attic.

  • CMC § 703.1 High relevance — show source text

    ii. At all locations where noninsulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection. b. Ducts do not require insulation when the duct system is located entirely in conditioned space. For buildings with three or fewer habitable stories, duct systems located entirely in conditioned space shall be confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. iii. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. iv. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. v. Building cavities, support platforms for air handlers, and plenums designed or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. Exception to Section 160.3(b)5A: Ducts and fans integral to a wood heater or fireplace. B. Factory-fabricated duct systems . i. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. ii. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. iii. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. iv. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. C. Field-fabricated duct systems. i. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.

    ii. Mastic sealants and mesh.

    a. Sealants shall comply with the applicable requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.

    b. Sealants for interior applications shall be tested in accordance with ASTM C731 and D2202, incorporated herein by reference.

    2025 CALIFORNIA ENERGY CODE 215

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS

  • CMC § 0.35 High relevance — show source text

    Where the specific gravity of the wood species used for roof framing is greater than or equal to 0.35 but less than 0.42 in accordance with AWC NDS, fastening of roof
    sheathing shall be with RSRS-03 (21/2″ × 0.131″ × 0.281″ head) nails unless alternative fastening is designed in accordance with AWC NDS. Where the specific gravity of the wood
    species used for roof framing is less than 0.35, fastening of the roof sheathing shall be designed in accordance with AWC NDS.
    f. Fastening is only permitted where the basic wind speed,V, is less than or equal to 110 mph and where fastening is to wood framing of a species with specific gravity greater
    than or equal to 0.42 in accordance with AWC NDS.
    g. Nails and staples are carbon steel meeting the specifications of ASTM F1667. Connections using nails and staples of other materials, such as stainless steel, shall be designed
    by acceptable engineering practice or approved under Section 104.2.3.|For SI: 1 inch = 25.4 mm.
    a. Nails spaced at 6 inches at intermediate supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer
    to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.
    b. Spacing shall be 6 inches on center on the edges and 12 inches on center at intermediate supports for nonstructural applications. Panel supports at 16 inches (20 inches if
    strength axis in the long direction of the panel, unless otherwise marked).
    c. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule and the ceiling joist is fastened to the top plate in accordance with this schedule,
    the number of toenails in the rafter shall be permitted to be reduced by one nail.
    d. RSRS is a Roof Sheathing Ring Shank nail meeting the specifications in ASTM F1667.
    e. Tabulated fastener requirements apply where the basic wind speed,V, is less than 140 mph. For wood structural panel roof sheathing attached to gable-end roof framing and
    to intermediate supports within 48 inches of roof edges and ridges, nails shall be spaced at 4 inches on center where the basic wind speed,V, is greater than 130 mph in Expo-
    sure B or greater than 110 mph in Exposure C. Spacing exceeding 6 inches on center at intermediate supports shall be permitted where the fastening is designed per the AWC
    NDS. Where the specific gravity of the wood species used for roof framing is greater than or equal to 0.35 but less than 0.42 in accordance with AWC NDS, fastening of roof
    sheathing shall be with RSRS-03 (21/2″ × 0.131″ × 0.281″ head) nails unless alternative fastening is designed in accordance with AWC NDS. Where the specific gravity of the wood
    species used for roof framing is less than 0.35, fastening of the roof sheathing shall be designed in accordance with AWC NDS.
    f. Fastening is only permitted where the basic wind speed,V, is less than or equal to 110 mph and where fastening is to wood framing of a species with specific gravity greater
    than or equal to 0.42 in accordance with AWC NDS.
    g. Nails and staples are carbon steel meeting the specifications of ASTM F1667.

  • CMC § 703.1 High relevance — show source text

    a. The noninsulated portion of the duct system is located entirely inside the building’s thermal envelope as confirmed by visual inspection. b. At all locations where noninsulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection. Exception 2 to Section 150.0(m)1Bi : Ducts located in an unvented attic shall have a minimum insulation value of R-4.2, verified by visual inspection where:

    a. The attic has at least R-30 insulation between the roof rafters in contact with the roof deck.

    b. The gable ends meet the wall insulation requirements of Section 150.1(c)1B. c. The dwelling unit achieves a whole building leakage rate of 3.0 ACH50 or less, as confirmed by field verification and diagnostic testing in accordance with Reference Residential Appendix RA3.8. ii. Ducts do not require insulation when the duct system is located entirely within conditioned space, as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. For dwelling units with attics, the duct system shall be located below the ceiling separating the occupiable space from the attic. C. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. D. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL181A or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than [1] / 4 inch, the combination of mastic and either mesh or tape shall be used. E. Building cavities, support platforms for air handlers and plenums designed or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts.

    Exception to Section 150.0(m)1: Ducts and fans integral to a wood heater or fireplace. 2. Factory-fabricated duct systems. A. All factory-fabricated duct systems shall comply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director. B. All pressure-sensitive tapes, heat-activated tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A. C. All pressure-sensitive tapes and mastics used with flexible ducts shall comply with UL 181 and UL 181B. D. Joints and seams of duct systems and their components shall not be sealed with cloth-back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. 3. Field-fabricated duct systems. A. Factory-made rigid fiberglass and flexible ducts for field-fabricated duct systems shall comply with UL 181.

Frequently asked questions

Can I use any plastic duct material in a return plenum?

No. The CMC only permits plastic ducts where they comply with the specific plastic‑duct rules (see the exception to § 602.5 pointing to § 603.5) or where the product is listed and labeled for use in plenums per the applicable UL standard. See § 602.5 .

Do fibrous glass ducts need UL listings?

Factory‑fabricated fibrous glass ducts and their closure materials must comply with the referenced SMACNA/NAIMA construction standards and the applicable UL standards for tapes and mastics; fibrous glass assemblies themselves are required to be constructed per § 602.5.4 and the Code’s referenced UL requirements for closure systems .

Is phenolic allowed for plenums?

Yes — phenolic ducts, plenums and fittings are permitted if they comply with UL 181 and are constructed per SMACNA Phenolic Duct Construction Standards or the conditions of their listing (§ 602.5.1) .

What if my manufacturer’s product is “UL listed” but lacks a SMACNA instruction?

If the Code section requires both a UL listing and construction per a SMACNA standard (for example, phenolic per § 602.5.1), you must follow the listing conditions and the SMACNA construction standard or the listing’s specific conditions. Provide documentation during plan review/inspection showing compliance with the Code and the referenced standards .

Can building cavities be used as plenums or ducts?

Not unless the cavities or platforms are designed and constructed as ducts or plenums meeting the CMC and referenced standards. The Energy Code and CMC forbid using building cavities, support platforms or mechanical closets to convey conditioned air unless they meet the requirements of the CMC and referenced standards (see related Energy Code references incorporated by the CMC) .

More in California Mechanical Code

Ask about the CMC

Get cited, plain-English answers on the California Mechanical Code for your project — any code section, any scenario.

Start Free Trial

Related in the CMC