CHBC · California Historical Building Code
Can reconstructed or repaired walls reuse original historic masonry and what rules apply?
If you rebuild an entire historic masonry wall using the original bricks or stones, CHBC **§ 8-805.3** requires you to build it to the regular building code; if you are only repairing or doing a localized infill, the CHBC allows you to reconstruct that part using the original materials and traditional methods without meeting the regular code, though the building official can require testing or other measures for safety. file
Last reviewed: July 6, 2026
What the code requires — 2–4 sentences
Briefly: Totally reconstructed walls using original historic brick or masonry must be built to the regular code (the current California Building Code). Repairs or infills (partial repairs, patching, or small replaced areas) may be rebuilt in a similar manner to the original without conforming to the regular code. The controlling provision is § 8-805.3.
If you rebuild an entire historic masonry wall using the original bricks or stones, you must meet the regular (non‑CHBC) code; if you are only repairing or infilling portions, you may use original materials and historic methods under the CHBC. § 8-805.3
Requirements in detail
Short plain-English summary of § 8-805.3
- Totally reconstructed walls utilizing original brick or masonry, even if reusing original units, “shall be constructed in accordance with the regular code.” § 8-805.3
- Repairs or infills (i.e., partial rebuilding, patching, or limited replacement) “may be constructed in a similar manner to the original walls without conforming to the regular code.” § 8-805.3
Decision table — when you can reuse original masonry, and what standard applies
| Decision factor | What that means (practical test) | Code reference |
|---|---|---|
| Scope = Totally reconstructed wall | Entire wall rebuilt (full height/length), even using original bricks/stone — must meet the regular code (CBC/regular code) for materials, reinforcement, anchorage, seismic, etc. | § 8-805.3 |
| Scope = Repair or infill | Localized patching, repair, or infill may be done “in a similar manner to the original” and need not conform to the regular code | § 8-805.3 |
| Allowable shear for existing solid masonry (for evaluating repairs) | Existing solid unreinforced masonry may be assigned up to 9 pounds per square inch (9 psi) ultimate shear (when inspection shows mortar and brick are reasonably good) | § 8-805.1 |
| Height-to-thickness ratio limit (for unreinforced masonry evaluation) | Maximum unsupported height or length to thickness ratio 13 (used in applying the shear allowance above) | § 8-805.1 |
| Stone masonry special measures | Stone wythes that are independent require ties/anchors or testing; additional anchorage/near-top reinforcing element requirements apply | § 8-805.2 |
| Repairs generally (in-kind) | Repairs may be made in-kind with historical materials and original methods, subject to CHBC conditions | § 8-105.1 |
Practical implications for design, permitting and enforcement
- If the work is reconstruction of the whole wall, expect the enforcing authority to require compliance with the regular code: plan submittal, structural design to current code standards (seismic, anchorage, grouting, etc.), inspections and testing as required by the regular code. This follows directly from § 8-805.3.
- If the work is a repair/infill, you may use matching historic materials and original techniques; however, the enforcing agency still reviews safety and may require mitigation where a life‑safety hazard exists (see CHBC intent and enforcement provisions). See Sections on repairs and scope (for example § 8-105.1 and CHBC scope language). file
Exceptions & special cases
- Stone masonry with independent wythes: treating stone as “solid” requires testing/anchors; special anchoring spacing and a reinforcing element near the top may be required — see § 8-805.2. If those conditions are not met, additional reinforcement or treatments will be needed even for repairs.
- Adobe and other archaic materials: adobe has its own provisions; repair or reconstruction of adobe may be treated differently (see Section § 8-806, including § 8-806.6 for repair/reconstruction compatibility). If your wall is adobe, follow that section rather than the general masonry rule alone.
- Enforcement discretion and testing: the CHBC contemplates representative testing, structural survey, and the architect/engineer assigning allowable strengths; the enforcing agency can require testing, alternate measures, or accept equivalent methods consistent with CHBC intent (§ 8-802, § 8-804). file
Common mistakes
- Assuming reuse of original bricks always allows bypassing regular code. (Wrong — full wall reconstruction using original units triggers the regular code: § 8-805.3.)
- Calling a wholesale rebuild a “repair” to avoid regular-code requirements. The CHBC distinguishes totally reconstructed versus repairs/infill; scope and extent matter. Readily document whether work is partial repair or full reconstruction. § 8-805.3.
- Forgetting stone masonry specifics — independent stone wythes may require anchors or treatment even for repairs. See § 8-805.2.
- Overlooking required inspections, testing or the structural survey (CHBC requires documenting existing conditions to set allowable strengths). See § 8-804 (and the structural survey requirement referenced in § 8-703). file
Worked example — concrete scenario
Scenario: A historic brick exterior wall 16 ft high and full length is damaged. The owner wants to reuse the original bricks.
Step 1 — classify the scope:
- If you rebuild the entire 16‑ft wall (full height and length) using the reclaimed bricks, that is a totally reconstructed wall and “shall be constructed in accordance with the regular code.” You cannot treat it as an in‑kind CHBC repair. § 8-805.3.
Step 2 — practical consequences of “regular code” requirement:
- The project will generally need structural design per the regular code, including seismic detailing, anchorage, possible reinforcement/grouting, and material testing as required by the regular code (the CHBC explicitly sends totally reconstructed walls to the regular code). § 8-805.3.
Alternate case — localized damage (example: a 3 ft × 6 ft section at the base):
- Replacing just this localized area is a repair/infill. Per § 8-805.3, the owner may reconstruct that patch “in a similar manner to the original walls without conforming to the regular code.” Document the limited scope for the permitting authority and follow CHBC guidance for in‑kind repairs (§ 8-105.1). file
Using the CHBC’s evaluation metrics:
- If you plan to rely on the CHBC allowance for existing solid masonry strengths, remember the CHBC allows, without testing, a maximum ultimate shear of 9 psi for existing solid masonry when inspection verifies reasonable condition and mortar joints are filled — but that primarily applies when you are keeping/repairing existing masonry, not when you are fully reconstructing per regular code. § 8-805.1.
Related provisions (CHBC sections)
- § 8-805.3 — Reconstructed walls (controlling).
- § 8-805.1 — Existing solid masonry allowable shear and evaluation.
- § 8-805.2 — Stone masonry special provisions (anchors, testing).
- § 8-806 — Adobe provisions (including § 8-806.6 on repair/reconstruction compatibility).
- § 8-105.1 — Repairs: in‑kind repairs allowed under CHBC (conditions).
- § 8-804 — Structural survey and documentation used to set allowable conditions.
- § 8-802 — General engineering approaches, testing and enforcing agency concurrence.
Code references
Grounded in the retrieved California Historical Building Code — click a citation to read the verbatim passage:
CHBC § 8-805.3 High relevance — show source text
8-805.3 Reconstructed walls. Totally reconstructed walls utilizing original brick or masonry, constructed similar to original, shall be constructed in accordance with the regular code. Repairs or infills may be constructed in a similar manner to the original walls without conforming to the regular code.
SECTION 8-806 — ADOBE
8-806.1 General. Unburned clay masonry may be constructed, reconstructed, stabilized or rehabilitated subject to this chapter. Alternative approaches which provide an equivalent or greater level of safety may be used, subject to the concurrence of the enforcing agency.
8-806.2 Moisture protection. Provisions shall be in place to protect adobe structures from deterioration due to moisture penetration. Adobe shall be maintained in reasonably good condition. Particular attention shall be given to moisture content of adobe walls. Unmaintained walls or ruins shall be evaluated for safety based on their condition and stability. Additional protection measures may be appropriate subject to the concurrence of the enforcing agency.
8-806.3 Height to thickness ratio. Unreinforced new or existing adobe walls meeting these criteria need not be evaluated for out of plane failure. Where existing dimensions do not meet these conditions, additional strengthening measures, such as a bond beam, may be appropriate. Existing sod or rammed earth walls shall be considered similar to the extent these provisions apply.
- One-story adobe load-bearing walls shall not exceed a height-to-thickness ratio of 6.
- Two-story adobe buildings or structures’ height- to-thickness wall ratio shall not exceed 6 at the ground floor and 5 at the second floor, and shall be measured at floor-to-floor height when the second floor and attic ceiling/roof are connected to the wall as described below.
8-806.4 Nonload-bearing adobe. Nonload-bearing adobe partitions and gable end walls shall be evaluated for stability and anchored against out-of-plane failure if necessary.
8-806.5 Bond beam. Where provided, a bond beam or equivalent structural element shall be located at the top of all adobe walls, and at the second floor for two-story buildings or structures. The size and configuration of the structural element shall be sufficient to provide an effective brace for the wall, to tie the building together and to connect the wall to the floor or roof.
8-806.6 Repair or reconstruction. Repair or reconstruction of wall area may utilize unstabilized brick or adobe masonry designed to be compatible with the constituents of the existing adobe materials.
8-806.7 Shear values. Existing adobe may be allowed a maximum strength level of 12 pounds per square inch (82.7 kPa) for shear.
8-806.8 Mortar. Mortar may be of the same soil composition as that used in the existing wall, or in new walls as necessary to be compatible with the adobe brick.
SECTION 8-807 — WOOD
8-807.1 Existing wood diaphragms or walls. Existing wood diaphragms or walls of straight or diagonal sheathing shall be assigned shear resistance values appropriate with the fasteners and materials functioning in conjunction with the sheathing. The structural survey shall determine fastener details and spacings and verify a load path through floor construction. Shear values of Tables 8-8-A and 8-8-B.
8-807.2 Wood lath and plaster. Wood lath and plaster walls and ceilings may be utilized using the shear values referenced in Section 8-807.1.
CHBC § 8-805.2 High relevance — show source text
8-805.2 Stone masonry.
8-805.2.1 Solid-backed stone masonry. Stone masonry solidly backed with brick masonry shall be treated as solid brick masonry as described in Section 8-805.1 and in the 2009 International Existing Building Code [®] (IEBC [®] ), provided representative testing and inspection verifies solid collar joints between stone and brick and that a reasonable number of stones lap with the brick wythes as headers or that steel anchors are present. Solid stone masonry where the wythes of stone effectively overlap to provide the equivalent header courses may also be treated as solid brick masonry.
8-805.2.2 Independent wythe stone masonry. Stone masonry with independent face wythes may be treated as solid brick masonry as described in Section 8-805.1 and the CEBC, provided representative testing and inspection verify that the core is essentially solid in the masonry wall and that steel ties are epoxied in drilled holes between outer stone wythes at floors, roof and not to exceed 4 feet (1219 mm) on center in each direction, between floors and roof. A reinforcing element shall exist or be provided at or near the top of all stone masonry walls.
2025 CALIFORNIA HISTORICAL BUILDING CODE 15
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
8-805.2.3 Testing of stone masonry. Testing of stone masonry shall be similar to the 2010 CEBC requirements for brick masonry, except that representative stones which are not interlocked shall be pulled outward from the wall and shear area appropriately calculated after the test.
8-805.3 Reconstructed walls. Totally reconstructed walls utilizing original brick or masonry, constructed similar to original, shall be constructed in accordance with the regular code. Repairs or infills may be constructed in a similar manner to the original walls without conforming to the regular code.
SECTION 8-806 — ADOBE
8-806.1 General. Unburned clay masonry may be constructed, reconstructed, stabilized or rehabilitated subject to this chapter. Alternative approaches which provide an equivalent or greater level of safety may be used, subject to the concurrence of the enforcing agency.
8-806.2 Moisture protection. Provisions shall be in place to protect adobe structures from deterioration due to moisture penetration. Adobe shall be maintained in reasonably good condition. Particular attention shall be given to moisture content of adobe walls. Unmaintained walls or ruins shall be evaluated for safety based on their condition and stability. Additional protection measures may be appropriate subject to the concurrence of the enforcing agency.
8-806.3 Height to thickness ratio. Unreinforced new or existing adobe walls meeting these criteria need not be evaluated for out of plane failure. Where existing dimensions do not meet these conditions, additional strengthening measures, such as a bond beam, may be appropriate. Existing sod or rammed earth walls shall be considered similar to the extent these provisions apply.
- One-story adobe load-bearing walls shall not exceed a height-to-thickness ratio of 6.
- Two-story adobe buildings or structures’ height- to-thickness wall ratio shall not exceed 6 at the ground floor and 5 at the second floor, and shall be measured at floor-to-floor height when the second floor and attic ceiling/roof are connected to the wall as described below.
CHBC § 8-801 High relevance — show source text
SECTION 8-801 — PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regulations for the use of historical methods and materials of construction that are at variance with regular code requirements or are not otherwise codified, in buildings or structures designated as qualified historical buildings or properties. The CHBC require enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the use of historical methods and materials of construction that are at variance with specific code requirements or are not otherwise codified.
8-801.3 Scope. Any construction type or material that is, or was, part of the historical fabric of a structure is covered by this chapter. Archaic materials and methods of construction present in a historical structure may remain or be reinstalled or be installed with new materials of the same class to match existing conditions.
SECTION 8-802 — GENERAL ENGINEERING APPROACHES
Strength values for archaic materials shall be assigned based upon similar conventional codified materials, or on tests as hereinafter indicated. The archaic materials and methods of construction shall be thoroughly investigated for their details of construction in accordance with Section 8-703. Testing shall be performed when applicable to evaluate existing conditions. The architect or structural engineer in responsible charge of the project shall assign allowable stresses or strength levels to archaic materials. Such assigned strength values shall not be greater than those provided for in the following sections without adequate testing, and shall be subject to the concurrence of the enforcing agency.
SECTION 8-803 — NONSTRUCTURAL ARCHAIC MATERIALS
Where nonstructural historical materials exist in uses which do not meet the requirements of the regular code, their continued use is allowed by this code, provided that any public health and life safety hazards are mitigated subject to the concurrence of the enforcing agency.
SECTION 8-804 — ALLOWABLE CONDITIONS FOR SPECIFIC MATERIALS
Archaic materials which exist and are to remain in qualified historical buildings or structures shall be evaluated for their condition and for loads required by this code. The structural survey required in Section 8-703 of the CHBC shall document existing conditions, reinforcement, anchorage, deterioration and other factors pertinent to establishing allowable stresses, strength levels and adequacy of the archaic materials. The remaining portion of this chapter provides additional specific requirements for commonly encountered archaic materials.
SECTION 8-805 — MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls of any type, except adobe, may be allowed, without testing, a maximum ultimate strength of 9 pounds per square inch (62.1 kPa) in shear where there is a qualifying statement by the architect or engineer that an inspection has been made, that mortar joints are filled and that both brick and mortar are reasonably good. The shear stress above applies to unreinforced masonry, except adobe, where the maximum ratio of unsupported height or length to thickness does not exceed 13, and where minimum quality mortar is used or exists. Wall height or length is measured to supporting or resisting elements that are at least twice as stiff as the tributary wall. Stiffness is based on the gross section. Shear stress may be increased by the addition of 10 percent of the axial direct stress due to the weight of the wall directly above.
CHBC § 323-9843 High relevance — show source text
State Librarian [SL]
library.ca.gov csllaw@library.ca.gov (916) 323-9843 Public Library Construction & Renovation
2025 CALIFORNIA HISTORICAL BUILDING CODE v
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
HOW TO DETERMINE WHERE CHANGES HAVE BEEN MADE
Symbols in the margins indicate where changes have been made or language has been deleted.
This symbol indicates that a change has been made.
- This symbol indicates deletion of language.
vi 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
PART 8 CONTAINS ALTERNATIVE REGULATIONS
FOR QUALIFIED HISTORICAL BUILDINGS
The California Historical Building Code (CHBC) is unique among state regulations. The authoring of the original CHBC required state agencies promulgating regulations for building construction to work in harmony with representatives of other design and construction disciplines. The result was a totally new approach to building codes for historical structures, which maintains currently acceptable life safety standards. These regulations are also unique in that they are performance oriented rather than prescriptive. The provisions of the CHBC are to be applied by the enforcing authority of every city, county, city and county, or state agency in permitting repairs, alterations and additions necessary for the preservation, rehabilitation, relocation, related construction, change of use or continued use of a qualified historical building. The authority for use of the CHBC is vested in Sections 18950 through 18961 of the Health and Safety Code. Section 18954 states, “The building department of every city or county or other local agency that has jurisdiction over the enforcement of code within its legal authority shall apply the alternative standards and regulations adopted pursuant to Section 18959.5 in permitting repairs, alterations, and additions necessary for the preservation, restoration, rehabilitation, safety, moving, or continued use of a qualified historical building or structure. A state agency shall apply the alternative regulations adopted pursuant to Section 18959.5 in permitting repairs, alterations, and additions necessary for the preservation, restoration, rehabilitation, safety, moving, or continued use of a qualified historical building or structure.” However, be aware that in order to use the CHBC, the structure under consideration must be qualified by being designated as an historical building or structure. Section 18955 states, “For the purposes of this part, a qualified historical building or structure is any structure or property, collection of structures, and their related sites deemed of importance to the history, architecture, or culture of an area by an appropriate local or state governmental jurisdiction. This shall include historical buildings or structures on existing or future national, state or local historical registers or official inventories, such as the National Register of Historic Places, State Historical Landmarks, State Points of Historical Interest, and city or county registers or inventories of historical or architecturally significant sites, places, historic districts, or landmarks. This shall also include places, locations, or sites identified on these historical registers or official inventories and deemed of importance to the history, architecture, or culture of an area by an appropriate local or state governmental jurisdiction.” The regulations of the CHBC have the same authority as state law and are to be considered as such. Liability is the same as for prevailing law. The intent of the CHBC is to save California’s architectural heritage by recognizing the unique construction problems inherent in historical buildings and by providing a code to deal with these problems.
CHBC § 5.3 High relevance — show source text
- The type of interior wall and ceiling materials, and framing.
- The extent and type of existing wall anchorage to floors and roof where used in the design.
- The extent and type of parapet corrections that were previously performed, if any.
- Repair details, if any, of cracked or damaged unreinforced masonry walls required to resist forces specified in this chapter.
- All other plans, sections and details necessary to delineate required retrofit construction.
- The design procedure used shall be stated on both the plans and the permit application.
- Details of the anchor prequalification program required by Section A107.5.3, if used, including location and results of all tests.
- Quality assurance requirements of special inspection for all new construction materials and for retrofit construction including: anchor tests, pointing or repointing of mortar joints, installation of adhesive or mechanical anchors, and other elements as deemed necessary to ensure compliance with this chapter.
[BS] A105.4 Structural observation, testing and inspection. Structural observation, in accordance with Section 1704.6 of the Cali- fornia Building Code, shall be required for all structures in which seismic retrofit is being performed in accordance with this chapter. Structural observation shall include visual observation of work for compliance with the approved construction documents and confirmation of existing conditions assumed during design. Structural testing and inspection for new and existing construction materials shall be in accordance with the building code, except as modified by this chapter. Special inspection as described in Section A105.3, Item 10, shall be provided equivalent to Level 3 as prescribed in TMS 402, Table 3.1(2).
SECTION A106—MATERIALS REQUIREMENTS
[BS] A106.1 Condition of existing materials. Existing materials used as part of the required vertical load-carrying or seismic forceresisting system shall be evaluated by on-site investigation and: determined to be in good condition (free of degraded mortar, degraded masonry units or significant cracking); or shall be repaired, enhanced, retrofitted or removed and replaced with new materials. Mortar joint deterioration shall be patched by pointing or repointing of the eroded joint in accordance with Section A106.2.3.10. Existing significant cracks in solid unit unreinforced and solid grouted hollow unit masonry shall be repaired.
[BS] A106.2 Existing unreinforced masonry.
[BS] A106.2.1 General. Unreinforced masonry walls used to support vertical loads or seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this section. Masonry that does not meet the minimum requirements established by this chapter shall be repaired, enhanced, removed and replaced with new materials, or alternatively, shall have its structural functions replaced with new materials and shall be anchored to supporting elements.
[BS] A106.2.2 Lay-up of walls. Unreinforced masonry walls shall be laid in a running bond pattern.
[BS] A106.2.2.1 Header in multiple-wythe solid brick. The facing and backing wythes of multiple-wythe walls shall be bonded so that not less than 10 percent of the exposed face area is composed of solid headers extending not less than 4 inches (102 mm) into the backing wythes. The clear distance between adjacent header courses shall not exceed 24 inches (610 mm) vertically or horizontally.
CHBC § 8-804 High relevance — show source text
SECTION 8-804 — ALLOWABLE CONDITIONS FOR SPECIFIC MATERIALS
Archaic materials which exist and are to remain in qualified historical buildings or structures shall be evaluated for their condition and for loads required by this code. The structural survey required in Section 8-703 of the CHBC shall document existing conditions, reinforcement, anchorage, deterioration and other factors pertinent to establishing allowable stresses, strength levels and adequacy of the archaic materials. The remaining portion of this chapter provides additional specific requirements for commonly encountered archaic materials.
SECTION 8-805 — MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls of any type, except adobe, may be allowed, without testing, a maximum ultimate strength of 9 pounds per square inch (62.1 kPa) in shear where there is a qualifying statement by the architect or engineer that an inspection has been made, that mortar joints are filled and that both brick and mortar are reasonably good. The shear stress above applies to unreinforced masonry, except adobe, where the maximum ratio of unsupported height or length to thickness does not exceed 13, and where minimum quality mortar is used or exists. Wall height or length is measured to supporting or resisting elements that are at least twice as stiff as the tributary wall. Stiffness is based on the gross section. Shear stress may be increased by the addition of 10 percent of the axial direct stress due to the weight of the wall directly above. Higher-quality mortar may provide a greater shear value and shall be tested in accordance with Appendix A, Chapter A1 of the California Existing Building Code (CEBC) 2010 edition, and as modified by the CHBC.
8-805.2 Stone masonry.
8-805.2.1 Solid-backed stone masonry. Stone masonry solidly backed with brick masonry shall be treated as solid brick masonry as described in Section 8-805.1 and in the 2009 International Existing Building Code [®] (IEBC [®] ), provided representative testing and inspection verifies solid collar joints between stone and brick and that a reasonable number of stones lap with the brick wythes as headers or that steel anchors are present. Solid stone masonry where the wythes of stone effectively overlap to provide the equivalent header courses may also be treated as solid brick masonry.
8-805.2.2 Independent wythe stone masonry. Stone masonry with independent face wythes may be treated as solid brick masonry as described in Section 8-805.1 and the CEBC, provided representative testing and inspection verify that the core is essentially solid in the masonry wall and that steel ties are epoxied in drilled holes between outer stone wythes at floors, roof and not to exceed 4 feet (1219 mm) on center in each direction, between floors and roof. A reinforcing element shall exist or be provided at or near the top of all stone masonry walls.
2025 CALIFORNIA HISTORICAL BUILDING CODE 15
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
8-805.2.3 Testing of stone masonry. Testing of stone masonry shall be similar to the 2010 CEBC requirements for brick masonry, except that representative stones which are not interlocked shall be pulled outward from the wall and shear area appropriately calculated after the test.
CHBC § 8-104.4 High relevance — show source text
8-104.4 Local agency fees. Local agencies, when actively involved in the appeal, may also charge affected persons reasonable fees not to exceed the cost of obtaining reviews and appeals from the Board.
SECTION 8-105 — CONSTRUCTION METHODS AND MATERIALS
8-105.1 Repairs. Repairs to any portion of a qualified historical building or property may be made in-kind with historical materials and the use of original or existing historical methods of construction, subject to conditions of the CHBC. (See Chapter 8-8.)
8-105.2 Solutions to the California Historical Building Code . Solutions provided in the CHBC, or any other acceptable regulation or methodology of design or construction and used in whole or in part, with the regular code, or with any combination of the regular code and the CHBC, shall be allowed. The CHBC does not preclude the use of any proposed alternative or method of design or construction not specifically prescribed or otherwise allowed by these regulations. Any alternative may be submitted for evaluation to the appropriate enforcing agency for review and acceptance. The enforcing agency may request that sufficient evidence or proof be submitted to substantiate any claims that may be made regarding such solutions. Any alternative offered in lieu of that prescribed or allowed in the CHBC shall be reasonably equivalent in quality, strength, effectiveness, durability and safety to that of the CHBC.
SECTION 8-106 — SHBSB RULINGS
8-106.1 General. Rulings of the SHBSB (i.e., formal appeals, case decisions, code interpretations and administrative resolutions, etc.) that are issues of statewide application are required to be submitted to the California Building Standards Commission in printed form. These rulings may be used to provide guidance for similar cases or issues.
2 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-2 DEFINITIONS
SECTION 8-201 — DEFINITIONS
For the purpose of the CHBC, certain terms and phrases, words and their derivatives shall be construed as specified in this chapter. Additional definitions and/or terms may appear in the various other chapters relative to terms or phrases primarily applicable thereto. Any reference to “authority having jurisdiction” does not necessarily preclude the appellate process of Section 8-104.3.
ADDITION. A nonhistorical extension or increase in floor area or height of a building or property.
ALTERATION. A modification to a qualified historical building or property that affects the usability of the building or property, or part thereof. Alterations include, but are not limited to, remodeling, renovation, rehabilitation, reconstruction, historical restoration, changes or rearrangement of the structural parts or elements, and changes or rearrangements in the plan configuration of walls and full-height partitions.
BUILDING STANDARD. Any guideline, regulation or code that may be applied to a qualified historical building or property.
CHARACTER-DEFINING FEATURE. Those visual aspects and physical elements that comprise the appearance of a historical building or property, and that are significant to its historical, architectural and cultural values, including the overall shape of the historical building or property, its materials, craftsmanship, decorative details, interior spaces and features, as well as the various aspects of its site and environment.
CULTURAL RESOURCE. Building, site, property, object or district evaluated as having significance in prehistory or history.
CHBC § 304.8 High relevance — show source text
4 mm, 1 foot = 304.8 mm.
a. Mortar shall be Type M or S and masonry shall be laid in running bond. Ungrouted hollow masonry units are permitted except where otherwise indicated.
b. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R401.4.1(2).
c. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation
wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of
the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
d. Solid indicates solid masonry unit; grout indicates grouted hollow units.
e. Wall construction shall be in accordance with Table R404.1.2.1(2), R404.1.2.1(3) or R404.1.2.1(4), or a design shall be provided.
f. The use of this table shall be prohibited for soil classifications not shown.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Mortar shall be Type M or S and masonry shall be laid in running bond. Ungrouted hollow masonry units are permitted except where otherwise indicated.
b. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R401.4.1(2).
c. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation
wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of
the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
d. Solid indicates solid masonry unit; grout indicates grouted hollow units.
e. Wall construction shall be in accordance with Table R404.1.2.1(2), R404.1.2.1(3) or R404.1.2.1(4), or a design shall be provided.
f. The use of this table shall be prohibited for soil classifications not shown.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Mortar shall be Type M or S and masonry shall be laid in running bond. Ungrouted hollow masonry units are permitted except where otherwise indicated.
b. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R401.4.1(2).
c. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation
wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of
the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
d. Solid indicates solid masonry unit; grout indicates grouted hollow units.
e.CHBC § 3.5 High relevance — show source text
Grout pours not terminated at the top of constructed masonry shall comply with TMS 602, Articles 3.5 C.3.a through 3.5 C.3.c. 2. The top of the grout pour shall be in the top course of the constructed masonry. Grout pours not terminated within the top course of the constructed masonry shall comply with TMS 602, Articles 3.5 C.3.a through 3.5 C.3.c. 3. Grout pours in excess of 4 feet (1219 mm) or 5 feet 4 inches (1651 mm) for 10-inch (254 mm) nominal or wider for hollow unit masonry shall be subject to approval of the enforcement agency and the following: a. Grouting shall be done in a continuous pour in lifts not exceeding the requirements of TMS 602, Article 3.5 D. b. The grouting of any section of wall shall be completed in one day with no interruptions greater than one hour. c. Cleanout openings shall be provided at the bottom of each pour of grout.
TABLE 7—GROUT SPACE REQUIREMENTS Col2 Col3 Col4 GROUT TYPE1 MAXIMUM GROUT POUR
HEIGHT, FT (M)MINIMUM CLEAR WIDTH OF
GROUT SPACE,2,3 IN. (MM)MINIMUM CLEAR GROUT SPACE DIMENSIONS
**FOR GROUTING CELLS OF HOLLOW UNITS,3 **
IN. × IN. (MM × MM)Coarse 1 (0.3) 21/2 (63.5) 2 × 3(50.8× 76.2) Coarse 44 (1.22) 21/2 (63.5) 21/2 × 3 (63.5 × 76.2) Coarse 12.675 (3.86) 31/2 (88.9) 3 × 35 (76.2 × 76.2) 1. Coarse grout is defined in ASTM C476.
2. For grouting between masonry wythes.
3. Minimum clear width of grout space and minimum clear grout space dimension are the net dimension of the space determined by subtracting masonry protrusions and the
diameters of horizontal reinforcement from the as-built cross section of the grout space.
4. Maximum pour height can be increased to 5.33 feet for 10-inch nominal or wider hollow unit masonry.
5. Maximum pour height can be increased to 16 feet for hollow unit masonry walls with a nominal thickness of 12 inches or more and minimum clear grout space dimensions of 3 in.
x 4 in. (76.2 mm x 102 mm).1. Coarse grout is defined in ASTM C476.
2. For grouting between masonry wythes.
3. Minimum clear width of grout space and minimum clear grout space dimension are the net dimension of the space determined by subtracting masonry protrusions and the
diameters of horizontal reinforcement from the as-built cross section of the grout space.
4. Maximum pour height can be increased to 5.33 feet for 10-inch nominal or wider hollow unit masonry.
_5.CHBC § 8-102.1.1 High relevance — show source text
- State agencies. All state agencies shall apply the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, rehabilitation, safety, relocation, reconstruction or continued use of qualified historical buildings or properties.
8-102.1.1 Additions, alterations and repairs. It is the intent of the CHBC to allow nonhistorical expansion or addition to a qualified historical building or property, provided nonhistorical additions shall conform to the requirements of the regular code (as defined in Chapter 8-2).
8-102.1.2 Relocation. Relocated qualified historical buildings or properties shall be sited to comply with the regular code or with the solutions listed in the CHBC. Nonhistorical new construction related to relocation shall comply with the regular code. Reconstruction and restoration related to relocation is permitted to comply with the provisions in the CHBC.
8-102.1.3 Change of occupancy. For change of use or occupancy, see Chapter 8-3, Use and Occupancy.
8-102.1.4 Continued use. Qualified historical buildings or properties may have their existing use or occupancy continued if such use or occupancy conformed to the code or to the standards of construction in effect at the time of construction, and such use or occupancy does not constitute a distinct hazard to life safety as defined in the CHBC.
8-102.1.5 Unsafe buildings or properties. When a qualified historical building or property is determined to be unsafe as defined in the regular code, the requirements of the CHBC are applicable to the work necessary to correct the unsafe conditions. Work to remediate the buildings or properties need only address the correction of the unsafe conditions, and it shall not be required to bring the entire qualified historical building or property into compliance with regular code.
8-102.1.6 Additional work. Qualified historical buildings or properties shall not be subject to additional work required by the regular code, regulation or ordinance beyond that required to complete the work undertaken. Certain exceptions for accessibility and for distinct hazards exist by mandate and may require specific action, within the parameters of the CHBC.
SECTION 8-103 — ORGANIZATION AND ENFORCEMENT
8-103.1 Authority. The state or local enforcing agency, pursuant to authority provided under Section 18954 of the Health and Safety Code, shall administer and enforce the provisions of the CHBC in permitting repairs, alterations and additions necessary for the preservation, restoration, reconstruction, rehabilitation, relocation or continued use of a qualified historical building or property.
8-103.2 State enforcement. All state agencies pursuant to authority provided under Section 18954 and Section 18961 of the Health and Safety Code shall administer and enforce the CHBC with respect to qualified historical buildings or properties under their respective jurisdiction.
8-103.3 Liability. Prevailing law regarding immunity of building officials is unaffected by the use and enforcement of the CHBC.
2025 CALIFORNIA HISTORICAL BUILDING CODE 1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ADMINISTRATION
SECTION 8-104 — REVIEW AND APPEALS
8-104.1 State Historical Building Safety Board (SHBSB or Board). In order to provide for interpretation of the provisions of the CHBC and to hear appeals, the SHBSB shall act as an appeal and review body to state and local agencies or any affected party.
**8-104.2 SHBSB review.
CHBC § 8-303.6 Medium relevance — show source text
8-303.6 Light and ventilation. Windows in habitable rooms shall have an area of 6 percent of the floor area, or 6 square feet (0.56 m [2] ), whichever is greater. Windows in sleeping rooms shall be openable (see Section 8-503). Residential occupancies need not be provided with electrical lighting.
8-303.7 Alteration and repair. The alteration and repair of qualified historical buildings or properties may permit the replacement, retention and extension of original materials and the continued use of original methods of construction, provided a life safety hazard is not created or continued. Alterations and repairs shall be consistent with the CHBC.
The amount of alterations and repairs is not limited, provided there is no nonhistorical increase in floor area, volume or size of the building or property.
8-303.8 Exiting. See Chapter 8-5.
6 2025 CALIFORNIA HISTORICAL BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-4 FIRE PROTECTION
SECTION 8-401 — PURPOSE, INTENT AND SCOPE
8-401.1 Purpose. The purpose of this chapter is to provide regulations for fire protection of qualified historical buildings or properties. The CHBC requires enforcing agencies to accept any reasonably equivalent alternatives to the regular code when dealing with qualified historical buildings or properties.
8-401.2 Intent. The intent of the CHBC is to preserve the integrity of qualified historical buildings or properties while maintaining a reasonable degree of fire protection based primarily on the life safety of the occupants and firefighting personnel.
8-401.3 Scope. This chapter shall apply when required by the provisions of Section 8-102.
SECTION 8-402 — FIRE-RESISTIVE CONSTRUCTION
8-402.1 Exterior wall construction. The fire-resistance requirement for existing exterior walls and existing opening protection may be satisfied when an automatic sprinkler system designed for exposure protection is installed per the CHBC. The automatic sprinklers may be installed on the exterior with at least one sprinkler located over each opening required to be protected. Additional sprinklers shall also be distributed along combustible walls under the roof lines that do not meet the fire-resistive requirement due to relationship to property lines as required by regular code. Such sprinkler systems may be connected to the domestic water supply on the supply-main side of the building shut-off valve. A shut-off valve may be installed for the sprinkler system, provided it is locked in an open position.
8-402.2 One-hour construction. Upgrading an existing qualified historical building or property to one-hour fire-resistive construction and one-hour fire-resistive corridors shall not be required regardless of construction or occupancy when one of the following is provided:
- An automatic sprinkler system throughout. See Section 8-410 for automatic sprinkler systems.
- An approved life safety evaluation.
- Other alternative measures as approved by the enforcing agency.
8-402.3 Openings in fire-rated systems. Historical glazing materials and solid wood unrated doors in interior walls required to have one-hour fire rating may be approved when operable windows and doors are provided with appropriate smoke seals and when the area affected is provided with an automatic sprinkler system. See Section 8-410 for automatic sprinkler systems.
SECTION 8-403 — INTERIOR FINISH MATERIALS
CHBC § 2.3.10. Medium relevance — show source text
SECTION A106—MATERIALS REQUIREMENTS
[BS] A106.1 Condition of existing materials. Existing materials used as part of the required vertical load-carrying or seismic forceresisting system shall be evaluated by on-site investigation and: determined to be in good condition (free of degraded mortar, degraded masonry units or significant cracking); or shall be repaired, enhanced, retrofitted or removed and replaced with new materials. Mortar joint deterioration shall be patched by pointing or repointing of the eroded joint in accordance with Section A106.2.3.10. Existing significant cracks in solid unit unreinforced and solid grouted hollow unit masonry shall be repaired.
[BS] A106.2 Existing unreinforced masonry.
[BS] A106.2.1 General. Unreinforced masonry walls used to support vertical loads or seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this section. Masonry that does not meet the minimum requirements established by this chapter shall be repaired, enhanced, removed and replaced with new materials, or alternatively, shall have its structural functions replaced with new materials and shall be anchored to supporting elements.
[BS] A106.2.2 Lay-up of walls. Unreinforced masonry walls shall be laid in a running bond pattern.
[BS] A106.2.2.1 Header in multiple-wythe solid brick. The facing and backing wythes of multiple-wythe walls shall be bonded so that not less than 10 percent of the exposed face area is composed of solid headers extending not less than 4 inches (102 mm) into the backing wythes. The clear distance between adjacent header courses shall not exceed 24 inches (610 mm) vertically or horizontally. Where backing consists of two or more wythes, the headers shall extend not less than 4 inches (102 mm) into the most distant wythe, or the backing wythes shall be bonded together with separate headers for which the area and spacing conform to the foregoing. Wythes of walls not meeting these requirements shall be considered to be veneer, and shall not be included in the effective thickness used in calculating the height-to-thickness ratio and the shear capacity strength of the wall. Exception: Where S D 1 is 0.3 g or less, veneer wythes anchored and made composite with backup masonry are permitted to be used for calculation of the effective thickness.
[BS] A106.2.2.2 Lay-up patterns. Lay-up patterns other than those specified in Section A106.2.2.1 are allowed if their performance can be justified.
[BS] A106.2.3 Testing of masonry.
[BS] A106.2.3.1 Concrete masonry units and structural clay load-bearing tile. Grouted or ungrouted hollow concrete masonry units shall be tested in accordance with ASTM C140. Grouted or ungrouted structural clay load-bearing tile shall be tested in accordance with ASTM C67.
APPENDIX A-6 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A—GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING BUILDINGS
[BS] A106.2.3.2 In-place mortar joint shear tests. Mortar joint shear test values, v to, shall be obtained by one of the following:
- ASTM C1531.
Frequently asked questions
When is original historic masonry allowed to be reused without meeting the regular code?
Localized repairs or infills may be reconstructed in a manner similar to the original without conforming to the regular code — see § 8-805.3. Document the limited scope for the enforcing agency.
If I reuse every brick from a historic wall, do I still need to follow modern code?
Yes — if the wall is totally reconstructed using original units you must construct it in accordance with the regular code per § 8-805.3.
What about stone walls — are they treated the same as brick?
Stone masonry has special rules. Some stone walls may be treated like solid brick masonry if testing/anchors verify solid connections; independent face wythes likely need ties/anchors and a reinforcing element near the top per § 8-805.2.
Can I perform an in-kind repair using historic mortar and techniques?
Yes—repairs may be made in-kind with historical materials and methods under CHBC conditions (see § 8-105.1). The enforcing agency may require testing or mitigation if life‑safety issues are present. file
Do I need to perform testing or a structural survey for repairs?
The CHBC expects evaluation of existing conditions via a structural survey (see § 8-804 referencing § 8-703) and permits representative testing where applicable; architects/engineers assign allowable strengths based on inspection/testing and enforcing‑agency concurrence. file
More in California Historical Building Code
Ask about the CHBC
Get cited, plain-English answers on the California Historical Building Code for your project — any code section, any scenario.
Start Free Trial