CFC · California Fire Code

Means-of-egress retrofit rules & marking

This hub orients readers to CFC Chapter 10 retrofit and marking rules for means of egress (notably §§1008, 1013, 1025) and points to existing‑building rules that affect upgrade scope.

Last reviewed: July 6, 2026

Overview

This hub covers California Fire Code (CFC) requirements that govern retrofit and marking of means of egress — including illumination, exit signs, low‑level/floor‑level exit signs, and luminous/photoluminescent path and door markings. These provisions live in Chapter 10 (Means of Egress) of the CFC and the luminous‑marking details are concentrated in sections such as §1008 (egress illumination), §1013 (exit and floor‑level signs / path marking) and §1025 (luminous egress path markings and door/hardware demarcation) .

Why it matters: properly retrofitting egress marking reduces confusion and speeds safe evacuation during power loss or smoke conditions — the code requires emergency illumination duration (90 minutes), continuous path delineation in applicable corridors, and listed luminous materials or systems that perform without electrical power when required . For retrofits to existing buildings, CFC Chapter 11 and the California Existing Building Code provide the procedural and upgrade framework that can affect which egress upgrades are required and how they are applied .

In this section

Code references

Grounded in the retrieved California Fire Code — click a citation to read the verbatim passage:

  • CFC § 1025.2.4.2 High relevance — show source text

    Exception: Demarcation lines shall not extend in front of exit discharge doors that lead out of an exit and through which occupants must travel to complete the exit path.

    [BE] 1025.2.4.2 Wall-mounted demarcation lines. Perimeter demarcation lines shall be placed on the wall with the bottom edge of the stripe not more than 4 inches (102 mm) above the finished floor. At the top or bottom of the stairs, demarcation lines shall drop vertically to the floor within 2 inches (51 mm) of the step or landing edge. Demarcation lines on walls shall transition vertically to the floor and then extend across the floor where a line on the floor is the only practical method of outlining the path. Where the wall line is broken by a door, demarcation lines on walls shall continue across the face of the door or transition to the floor and extend across the floor in front of such door.

    Exception: Demarcation lines shall not extend in front of exit discharge doors that lead out of an exit and through which occupants must travel to complete the exit path.

    10-50 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    [BE] 1025.2.4.3 Transition. Where a wall-mounted demarcation line transitions to a floor-mounted demarcation line, or viceversa, the wall-mounted demarcation line shall drop vertically to the floor to meet a complimentary extension of the floormounted demarcation line, thus forming a continuous marking.

    [BE] 1025.2.5 Obstacles. Obstacles at or below 6 feet 6 inches (1981 mm) in height and projecting more than 4 inches (102 mm) into the egress path shall be outlined with markings not less than 1 inch (25 mm) in width comprised of a pattern of alternating equal bands, of luminous material and black, with the alternating bands not more than 2 inches (51 mm) thick and angled at 45 degrees (0.79 rad). Obstacles shall include, but are not limited to, standpipes, hose cabinets, wall projections, and restricted height areas. However, such markings shall not conceal any required information or indicators including but not limited to instructions to occupants for the use of standpipes.

    Exception: The minimum width of 1 inch (25 mm) shall not apply to markings listed in accordance with UL 1994.

    [BE] 1025.2.6 Doors within the exit path. Doors through which occupants must pass in order to complete the exit path shall be provided with markings complying with Sections 1025.2.6.1 through 1025.2.6.3.

    [BE] 1025.2.6.1 Emergency exit symbol. The doors shall be identified by a low-location luminous emergency exit symbol complying with NFPA 170. The exit symbol shall be not less than 4 inches (102 mm) in height and shall be mounted on the door, centered horizontally, with the top of the symbol not higher than 18 inches (457 mm) above the finished floor.

  • CFC § 1013.8 High relevance — show source text

    1013.8 Path marking. When exit signs are required by Chapter 10, in addition to approved floor-level exit signs, approved path marking shall be installed at floor level or no higher than 8 inches (203 mm) above the floor level in all interior rated exit corridors of unsprinklered Group A, R-1 and R-2 occupancies.

    2025 CALIFORNIA BUILDING CODE 10-35

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    Such marking shall be continuous except as interrupted by door-ways, corridors or other such architectural features in order to provide a visible delineation along the path of travel.

    Note: Pursuant to Health and Safety Code Section 13143, the California amendments of this section shall apply to all newly constructed buildings or structures subject to this section for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.

    SECTION 1014—HANDRAILS

    [DSA-AC] In addition to the requirements of this section, means of egress, which provide access to, or egress from, buildings or facilities where accessibility is required for applications listed in Section 1.9.1 regulated by the Division of the State Architect—Access Compliance, shall also comply with Chapter 11A or Chapter 11B, Section 11B-505, as applicable.

    1014.1 Where required. Handrails serving flights of stairways, ramps, stepped aisles and ramped aisles shall be adequate in strength and attachment in accordance with Section 1607.9. Handrails required for flights of stairways by Section 1011.11 shall comply with Sections 1014.2 through 1014.10. Handrails required for ramps by Section 1012.8 shall comply with Sections 1014.2 through 1014.9. Handrails for stepped aisles and ramped aisles required by Section 1030.16 shall comply with Sections 1014.2 through 1014.9.

    1014.2 Height. Handrail height, measured from a line connecting the nosings of flights of stairs or finish surface of ramp slope, shall be uniform, not less than 34 inches (864 mm) and not more than 38 inches (965 mm). Handrail height of alternating tread devices and ship’s ladders, measured from a line connecting the nosings, shall be uniform, not less than 30 inches (762 mm) and not more than 34 inches (864 mm).

    Exceptions:

    1. Where handrail fittings or bendings are used to provide continuous transition between flights, the fittings or bendings shall be permitted to exceed the maximum height.
    2. In Group R-3 occupancies; within dwelling units in Group R-2 occupancies; and in Group U occupancies that are associated with a Group R-3 occupancy or associated with individual dwelling units in Group R-2 occupancies; where handrail fittings or bendings are used to provide continuous transition between flights, transition at winder treads, transition from handrail to guard, or where used at the start of a flight, the handrail height at the fittings or bendings shall be permitted to exceed the maximum height.
    3. Handrails on top of a guard where permitted along stepped aisles and ramped aisles in accordance with Section 1030.16.
  • CFC § 1013.8 High relevance — show source text

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    The bottom of the sign shall not be less than 6 inches (152 mm) or more than 8 inches (203 mm) above the floor level and shall indicate the path of exit travel. For exit and exit-access doors, the sign shall be on the door or adjacent to the door with the closest edge of the sign or marker within 4 inches (102 mm) of the door frame.

    Note: Pursuant to Health and Safety Code Section 13143, this California amendment applies to all newly constructed buildings or structures, subject to this section, for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.

    1013.8 Path marking. When exit signs are required by Chapter 10, in addition to approved floor-level exit signs, approved path marking shall be installed at floor level or no higher than 8 inches (203 mm) above the floor level in all interior-rated exit corridors of unsprin- klered Group A, R-1 and R-2 occupancies.

    Such marking shall be continuous, except as interrupted by door-ways, corridors or other such architectural features, in order to provide a visible delineation along the path of travel.

    Note: Pursuant to Health and Safety Code Section 13143, the California amendments of this section shall apply to all newly constructed buildings or structures, subject to this section, for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.

    SECTION 1014—HANDRAILS

    [BE] 1014.1 Where required. Handrails serving flights of stairways, ramps, stepped aisles and ramped aisles shall be adequate in strength and attachment in accordance with Section 1607.9 of the California Building Code . Handrails required for flights of stairways by Section 1011.11 shall comply with Sections 1014.2 through 1014.10. Handrails required for ramps by Section 1012.8 shall comply with Sections 1014.2 through 1014.9. Handrails for stepped aisles and ramped aisles required by Section 1030.16 shall comply with Sections 1014.2 through 1014.9.

    [BE] 1014.2 Height. Handrail height, measured from a line connecting the nosings of flights of stairs or finish surface of ramp slope, shall be uniform, not less than 34 inches (864 mm) and not more than 38 inches (965 mm). Handrail height of alternating tread devices and ship’s ladders, measured from a line connecting the nosings, shall be uniform, not less than 30 inches (762 mm) and not more than 34 inches (864 mm).

    Exceptions:

    1. Where handrail fittings or bendings are used to provide continuous transition between flights, the fittings or bendings shall be permitted to exceed the maximum height.
  • CFC § 1030.14.1.3 High relevance — show source text

    [BE] 1030.14.1.3 Edge protection. Ramped aisles shall have edge protection in accordance with Sections 1012.10 and 1012.10.1.

    Exception: In assembly spaces with fixed seating, edge protection is not required on the sides of ramped aisles where the ramped aisles provide access to the adjacent seating and aisle accessways.

    [BE] 1030.14.2 Stepped aisles. Aisles with a slope exceeding 1 unit vertical in 8 units horizontal (12.5-percent slope) shall consist of a series of risers and treads that extends across the full width of aisles and complies with Sections 1030.14.2.1 through 1030.14.2.4.

    [BE] 1030.14.2.1 Treads. Tread depths shall be not less than 11 inches (279 mm) and shall have dimensional uniformity. Exception: The tolerance between adjacent treads shall not exceed [3] / 16 inch (4.8 mm).

    2025 CALIFORNIA FIRE CODE 10-59

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    [BE] 1030.14.2.2 Risers. Where the gradient of stepped aisles is to be the same as the gradient of adjoining seating areas, the riser height shall be not less than 4 inches (102 mm) nor more than 8 inches (203 mm) and shall be uniform within each flight.

    Exceptions:

    1. Riser height nonuniformity shall be limited to the extent necessitated by changes in the gradient of the adjoining seating area to maintain adequate sightlines. Where nonuniformities exceed [3] / 16 inch (4.8 mm) between adjacent risers, the exact location of such nonuniformities shall be indicated with a distinctive marking stripe on each tread at the nosing or leading edge adjacent to the nonuniform risers. Such stripe shall be not less than 1 inch (25 mm), and not more than 2 inches (51 mm), wide. The edge marking stripe shall be distinctively different from the contrasting marking stripe.
    2. Riser heights not exceeding 9 inches (229 mm) shall be permitted where they are necessitated by the slope of the adjacent seating areas to maintain sightlines.

    [BE] 1030.14.2.2.1 Construction tolerances. The tolerance between adjacent risers on a stepped aisle that were designed to be equal height shall not exceed [3] / 16 inch (4.8 mm). Where the stepped aisle is designed in accordance with Exception 1 of Section 1030.14.2.2, the stepped aisle shall be constructed so that each riser of unequal height, determined in the direction of descent, is not more than [3] / 8 inch (9.5 mm) in height different from adjacent risers where stepped aisle treads are less than 22 inches (560 mm) in depth and [3] / 4 inch (19.1 mm) in height different from adjacent risers where stepped aisle treads are 22 inches (560 mm) or greater in depth.

  • CFC § 1013.6.3 High relevance — show source text

    [BE] 1013.6.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 1203. Group I-2 exit sign illumination shall not be provided by unit equipment batteries only.

    Exception: Approved exit sign illumination types that provide continuous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be connected to an emergency electrical system.

    1013.7 Floor-level exit signs. Where exit signs are required by Chapter 10, additional approved low-level exit signs which are internally or externally illuminated photoluminescent or self-luminous shall be provided in all interior corridors of Group A, E, I and R-2.1 occupan- cies and in all areas serving guest rooms of hotels in Group R, Division 1 occupancies.

    Exceptions: 1. Group A occupancies that are protected throughout by an approved supervised fire sprinkler system. 2. Group E occupancies where direct exits have been provided from each classroom. 3. Group I and R-2.1 occupancies which are provided with smoke barriers constructed in accordance with Section 407.5 of the California Building Code.

    4. Group I-3 occupancies.

    10-36 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    The bottom of the sign shall not be less than 6 inches (152 mm) or more than 8 inches (203 mm) above the floor level and shall indicate the path of exit travel. For exit and exit-access doors, the sign shall be on the door or adjacent to the door with the closest edge of the sign or marker within 4 inches (102 mm) of the door frame.

    Note: Pursuant to Health and Safety Code Section 13143, this California amendment applies to all newly constructed buildings or structures, subject to this section, for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.

    1013.8 Path marking. When exit signs are required by Chapter 10, in addition to approved floor-level exit signs, approved path marking shall be installed at floor level or no higher than 8 inches (203 mm) above the floor level in all interior-rated exit corridors of unsprin- klered Group A, R-1 and R-2 occupancies.

    Such marking shall be continuous, except as interrupted by door-ways, corridors or other such architectural features, in order to provide a visible delineation along the path of travel.

    Note: Pursuant to Health and Safety Code Section 13143, the California amendments of this section shall apply to all newly constructed buildings or structures, subject to this section, for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.

    SECTION 1014—HANDRAILS

  • CFC § 1013.7 Medium relevance — show source text

    Exception: Approved exit sign illumination types that provide continuous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be connected to an emergency electrical system.

    1013.7 Floor-level exit signs. Where exit signs are required by Chapter 10, additional approved low-level exit signs which are internally or externally illuminated photoluminescent or self-luminous, shall be provided in all interior corridors of Group A, E, I and R-2.1 occupan- cies and in all areas serving guest rooms of hotels in Group R, Division 1 occupancies.

    Exceptions: 1. Group A occupancies that are protected throughout by an approved supervised fire sprinkler system. 2. Group E Occupancies where direct exits have been provided from each classroom. 3. Group I and R-2.1 occupancies which are provided with smoke barriers constructed in accordance with Section 407.5.

    4. Group I-3 occupancies.

    The bottom of the sign shall not be less than 6 inches (152 mm) or more than 8 inches (203 mm) above the floor level and shall indicate the path of exit travel. For exit and exit-access doors, the sign shall be on the door or adjacent to the door with the closest edge of the sign or marker within 4 inches (102 mm) of the door frame.

    Note: Pursuant to Health and Safety Code Section 13143, this California amendment applies to all newly constructed buildings or structures subject to this section for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.

    1013.8 Path marking. When exit signs are required by Chapter 10, in addition to approved floor-level exit signs, approved path marking shall be installed at floor level or no higher than 8 inches (203 mm) above the floor level in all interior rated exit corridors of unsprinklered Group A, R-1 and R-2 occupancies.

    2025 CALIFORNIA BUILDING CODE 10-35

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    Such marking shall be continuous except as interrupted by door-ways, corridors or other such architectural features in order to provide a visible delineation along the path of travel.

    Note: Pursuant to Health and Safety Code Section 13143, the California amendments of this section shall apply to all newly constructed buildings or structures subject to this section for which a building permit is issued (or construction commenced, where no building permit is issued) on or after January 1, 1989.

    SECTION 1014—HANDRAILS

    [DSA-AC] In addition to the requirements of this section, means of egress, which provide access to, or egress from, buildings or facilities where accessibility is required for applications listed in Section 1.9.1 regulated by the Division of the State Architect—Access Compliance, shall also comply with Chapter 11A or Chapter 11B, Section 11B-505, as applicable.

  • CFC § 12-10 Medium relevance — show source text

    (e) Fault condition introduced. Under each possible fault condition that affects the power supply with the sliding leaf or leaves retracted one-half the leaf width into its or their pocket(s) each swinging section shall open to the 90-degree position with an applied pressure at the normal location of the push plate not exceeding 40 pounds.

    (f) Sliding doors without swing-out section. Power-operated sliding doors which are not provided with a swing-out section may be evaluated for conformance to the mechanical requirements and endurance tests provided in this standard. Power-operated sliding doors which are not provided with a swing-out section shall not be listed for use in locations where required exits are specified in Part 2, Title 24, California Code of Regulations.

    (g) Activating carpets, safety mats. Activating carpets and safety mats shall conform to Section 12-10-102 (f).

    MARKING

    Sec. 12-10-104. The name of the manufacturer, or trademark by which the manufacturer can be readily identified, shall be legibly marked on the operating equipment where it can be seen after installation. The type, model number or letter designation identifying the product as a listed device shall be provided on a label attached in a location as indicated in its listing.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 75

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    76 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    SINGLE-POINT LATCHING OR LOCKING DEVICES

    STANDARD 12-10-2

    STATE FIRE MARSHAL

    SCOPE

    Sec. 12-10-200.

    (a) Builders hardware, exit doors. These design requirements and testing procedures apply to builders hardware, single-point latches and locks, intended for use on required means of egress doors in other than Group R and M Occupancies with an occupant load of 10 or less. It is the intent that devices designed and tested in accordance with these procedures will develop data to enable the State Fire Marshal to determine the suitability of latches and locks on means of egress doors. Alternate designs and materials may be submitted with substantiating test data. If, after evaluation, devices are found to comply with the intent of these procedures, they may also be recognized for approval and listing by the State Fire Marshal.

    (b) Fire doors. Builders hardware single-point latches and locks intended for use on doors bearing a fire-retardant classification shall also conform to the construction standards and performance tests specified in Fire Door Assembly Tests, SFM 12-7-4, Section 12-7-400.

    (c) Listing by approved listing agency. Listing by an approved listing agency shall not be construed as necessarily indicating compliance in all respects with the requirements of these design requirements and test procedures for single-point latching or locking devices. The test report of the approved listing agency may be filed for review and after evaluation, if it is found to provide evidence of conformance, the single-point latching or locking device may be recognized for approval and listing.

    (d) Definitions.

    1. Inside knob. Inside knob means the knob, lever, bar or paddle on the side of the door which must be turned or depressed to unlatch or unlock the door to permit egress.
    2. Outside knob. Outside knob means the knob on the corridor side of room to corridor doors, or the knob on the exterior side of a door leading to the exterior.
  • CFC § 2.3. Medium relevance — show source text

    2.3. Exit passageways. 2.4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.2. 2.5. Exterior landings as required by Section 1010.1.5 for exit doorways that lead directly to the exit discharge. 3. In other rooms and spaces: 3.1. Electrical equipment rooms.

    3.2. Fire command centers.

    3.3. Fire pump rooms.

    3.4. Generator rooms.

    3.5. Public restrooms with an area greater than 300 square feet (27.87 m [2] ). 4. Group I-2 exit discharge stairways, ramps, aisles, walkways and escalators leading to a public way or to a safe dispersal area in accordance with Section 1028.5.

    [BE] 1008.3.1 Duration. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the California Building Code .

    [BE] 1008.3.2 Illumination level under emergency power. Emergency lighting facilities shall be arranged to provide initial illumination that is not less than an average of 1 footcandle (11 lux) and a minimum at any point of 0.1 footcandle (1 lux) measured

    10-16 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06 footcandle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded. In Group I-2 occupancies, failure of a single lamp in a luminaire shall not reduce the illumination level to less than 0.2 footcandle (2.2 lux).

    SECTION 1009—ACCESSIBLE MEANS OF EGRESS

    [BE] 1009.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress in at least the same number as required by Section 1006.2 or 1006.3. In addition to the requirements of this chapter, means of egress, which provide access to, or egress from, buildings for persons with disabilities, shall also comply with the requirements of Chap- ter 11A or 11B of the California Building Code, as applicable. Exceptions:

    1. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1009.3, 1009.4 or 1009.5 and Chapter 11A or 11B of the California Building Code.
  • CFC § 10-37 Medium relevance — show source text

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-37

    1015 Guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-38

    1016 Exit Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-40

    1017 Exit Access Travel Distance. . . . . . . . . . . . . . . . . . . . 10-41

    1018 Aisles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-42

    1019 Exit Access Stairways and Ramps . . . . . . . . . . . . . . 10-43 1020 Corridors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-44

    1021 Egress Balconies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-46 1022 Exits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-46

    1023 Interior Exit Stairways and Ramps. . . . . . . . . . . . . .10-46 1024 Exit Passageways. . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-49 1025 Luminous Egress Path Markings. . . . . . . . . . . . . . . .10-50 1026 Horizontal Exits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-51

    1027 Exterior Exit Stairways and Ramps . . . . . . . . . . . . .10-52 1028 Exit Discharge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-53 1029 Egress Courts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-54 1030 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-54 1031 Emergency Escape and Rescue . . . . . . . . . . . . . . . .10-61 1032 Maintenance of the Means of Egress . . . . . . . . . . . .10-64

    CHAPTER 11 CONSTRUCTION REQUIREMENTS FOR

    EXISTING BUILDINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-3

  • CFC § 0.6 Medium relevance — show source text

    MEANS OF EGRESS

    along the path of egress at floor level. Illumination levels shall be permitted to decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06 footcandle (0.6 lux) at the end of the emergency lighting time duration. A maximum-to-minimum illumination uniformity ratio of 40 to 1 shall not be exceeded. In Group I-2 occupancies, failure of a single lamp in a luminaire shall not reduce the illumination level to less than 0.2 footcandle (2.2 lux).

    SECTION 1009—ACCESSIBLE MEANS OF EGRESS

    [BE] 1009.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress in at least the same number as required by Section 1006.2 or 1006.3. In addition to the requirements of this chapter, means of egress, which provide access to, or egress from, buildings for persons with disabilities, shall also comply with the requirements of Chap- ter 11A or 11B of the California Building Code, as applicable. Exceptions:

    1. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1009.3, 1009.4 or 1009.5 and Chapter 11A or 11B of the California Building Code.
    2. In assembly areas with ramped aisles or stepped aisles, one accessible means of egress is permitted where the common path of travel is accessible and meets the requirements in Section 1030.8 and Chapter 11A or 11B of the California Building Code.

    [BE] 1009.2 Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components:

    1. Accessible routes complying with and Chapter 11A or 11B of the California Building Code.
    2. Interior exit stairways complying with Sections 1009.3 and 1023 of this code and Chapter 11A or 11B of the California Building Code.
    3. Exit access stairways complying with Sections 1009.3 and 1019.3 or 1019.4 of this code and Chapter 11A or 11B of the Califor- nia Building Code.
    4. Exterior exit stairways complying with Sections 1009.3 and 1027 and serving levels other than the level of exit discharge of this code and Chapter 11A or 11B of the California Building Code.
    5. Elevators complying with Section 1009.4 of this code and Chapter 11A or 11B of the California Building Code.
    6. Platform lifts complying with Section 1009.5 of this code and Chapter 11A or 11B of the California Building Code.
    7. Horizontal exits complying with Section 1026.
    8. Ramps complying with Section 1012 of this code and Chapter 11A or 11B of the California Building Code.
    9. Areas of refuge complying with Section 1009.6.
  • CFC § 411.3 Medium relevance — show source text

    Exception: Automatic sprinklers are not required where the total floor area of a temporary, less than 180 days, special amusement area is less than 1,000 square feet (93 m [2] ) and the exit access travel distance from any point in the special amusement area to an exit is less than 50 feet (15 240 mm).

    [F] 411.3 Detection and alarm systems. Buildings containing special amusement areas shall be equipped throughout with an automatic smoke detection system and an emergency voice/alarm communications system in accordance with Section 907. Presignal alarms and alarm activation shall comply with Sections 411.3.1 and 411.3.2. Emergency voice/alarm communications systems shall comply with Section 411.3.3.

    [F] 411.3.1 Alarm presignal. Activation of any single smoke detector, the automatic sprinkler system or any other single automatic fire-detection device shall immediately initiate an audible and visible alarm at a constantly attended location at the special amusement area from which emergency action, including the manual requirements in Section 411.3.2, can be initiated.

    [F] 411.3.2 Alarm activation. Activation of two or more smoke detectors, a single smoke detector equipped with an alarm verification feature, two or more other approved fire detection devices, the automatic sprinkler system, or a manual control located at the constantly attended station required by Section 411.3.1 shall automatically accomplish all of the following:

    1. Illumination of the means of egress with an illumination level not less than 1 footcandle (11 lux) at the walking surface level.
    2. Cessation of conflicting or confusing sounds and visual distractions.
    3. Activation of approved directional exit markings.
    4. Activation of a prerecorded message, audible throughout the special amusement area, instructing occupants to proceed to the nearest exit. Alarm signals used in conjunction with the prerecorded message shall produce a sound that is distinct from other sounds used during normal operation of the special amusement area.

    [F] 411.3.3 Emergency voice/alarm communications system. An emergency voice/alarm communications system complying with Section 907.5.2.2 shall be installed in and audible throughout special amusement areas. The emergency voice/alarm communications system is allowed to also serve as a public address system.

    [BE] 411.4 Exit marking. Exit signs shall be installed at the required exit or exit access doorways serving special amusement areas in accordance with this section and Section 1013. Approved directional exit markings shall be provided. Where mirrors, mazes or other designs disguise the path of egress travel such that the path of egress travel is not apparent, approved and listed low-level exit signs that comply with Section 1013.5, and directional path markings listed in accordance with UL 1994, shall be provided and located not more than 8 inches (203 mm) above the walking surface and on or near the path of egress travel. Such markings shall become visible in an emergency. The directional exit marking shall be activated by the automatic smoke detection system and the automatic sprinkler system in accordance with Section 411.3.2.

    [BE] 411.4.1 Photoluminescent exit signs. Where photoluminescent exit signs are installed, such signs shall be listed and the activating light source and viewing distance shall be in accordance with the listing and markings on the signs.

    411.5 Interior finish. Interior wall and ceiling finish materials in special amusement areas shall meet the flame spread index and smoke-developed index requirements for Class A in accordance with Section 803.1.

Frequently asked questions

When are path markings required?

Path marking is required where exit signs are required by Chapter 10; the California amendment specifically requires approved path marking at floor level (or no higher than 8 in.) in interior rated exit corridors of unsprinklered Group A, R‑1 and R‑2 occupancies, and such marking must be continuous except where interrupted by doorways or other architectural features .

What types of markings and locations does the code mandate?

Luminous egress path markings may be self‑luminous or photoluminescent and must meet listed standards (for example UL 1994 where referenced). Markings include wall or floor demarcation lines, outlining of obstacles, low‑location exit symbols on doors, hardware markings (minimum luminous area and continuous strips on panic bars), and continuous 1–2 in. frame stripes around doors in the exit path — see §1025 for sizes, placement and transition details .

Must retrofits always upgrade existing buildings to these exact new markings?

Not always. Retrofit triggers, scope and timing are governed by the CFC’s provisions for existing buildings (Chapter 11) and by the California Existing Building Code; those chapters direct when egress elements must be upgraded and allow some compliance methods or exceptions based on the extent of work, occupancy and protection (sprinklers, etc.) .

More in California Fire Code

Ask about the CFC

Get cited, plain-English answers on the California Fire Code for your project — any code section, any scenario.

Start Free Trial

Related in the CFC