CFC · California Fire Code
Fire-safety requirements & fire protection systems
Chapter 9 of the CFC sets where and how fire‑protection systems (sprinklers, alarms, standpipes, extinguishers, smoke control) must be installed, tested and maintained.
Last reviewed: July 6, 2026
Overview
This area of the California Fire Code (CFC) covers active and integrated fire-protection measures—automatic sprinkler and alternative extinguishing systems, standpipes, portable extinguishers, fire alarm and detection systems, smoke control and related equipment—together with the administrative rules that govern their installation, testing, maintenance and acceptance. Chapter 9 of the CFC lays out these provisions and the topic-specific sections such as §903 (automatic sprinkler systems) and §907 (fire alarm and detection) are collected there.
Fire protection requirements are tied to occupancy, building height and area and are coordinated with the California Building Code; the CFC also sets the procedural requirements for permits, acceptance tests and supervision under §901. Installation, inspection, testing and maintenance frequencies reference national consensus standards (for example NFPA 25 for water-based systems) and California’s Title 19 inspection/testing rules. See §901 for administration and system requirements and Title 19 §904 for required inspection/testing frequencies.
Key topic sections you’ll want to consult in Chapter 9 include §903 Automatic Sprinkler Systems, §904 Alternative Automatic Fire‑Extinguishing Systems, §905 Standpipe Systems, §906 Portable Fire Extinguishers, §907 Fire Alarm and Detection Systems, §909 Smoke Control Systems, and related provisions on integrated testing and records (for example §901.6 and §901.6.3). These sections explain where systems are required, how they must be installed and monitored, and which referenced standards apply.
In this section
Code references
Grounded in the retrieved California Fire Code — click a citation to read the verbatim passage:
CFC § 904.2 High relevance — show source text
[California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies.
(a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspec- tion, testing and maintenance and additional procedures.
[California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies.
(1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D and G as amended by the State of California. (Published as NFPA 25, 2013 Califor- nia Edition.)
[California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies.
(b) When proof of the installation date of standpipe systems or automatic fire sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985.
[California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements.
(a) All testing and maintenance on automatic fire extinguishing systems in accordance with Health & Safety Code Section 13195 shall be performed by those licensed in accordance with Health and Safety Code Section 13196.5.
Exceptions:
(1) The State Fire Marshal may waive, in writing, licensing of fire departments which conduct fire sprinkler and standpipe system testing and maintenance.
(2) Service on fire alarm systems and industrial systems as specified in Health and Safety Code Sections 13196.5(b) and (c) may be conducted without a license.
(3) Testing and maintenance on automatic fire extinguishing systems exempted in writing by the State Fire Marshal, when the building owner or occupant has the staff and equipment to conduct testing and maintenance.
9-8 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FIRE PROTECTION AND LIFE SAFETY SYSTEMS
[California Code of Regulations, Title 19, Division 1, §904.2(b)] Testing and Maintenance Requirements.
(b) Any testing and maintenance of automatic fire extinguishing systems shall be performed in accordance with these requirements.
Exceptions:
(1) The State Fire Marshal may waive, in writing, the requirement that testing and maintenance be performed in accordance with these requirements when a licensee can demonstrate that a system cannot functionally be tested and maintained in accor- dance with the California Code of Regulations, Title 19, Division 1, Chapter 5.
(2) If at any time a licensee encounters a specialized or modified system which cannot be tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5, the licensee shall contact the State Fire Marshal and test and maintain the system as directed.
(A) The intent of this section is to cover automatic fire extinguishing systems as originally designed, installed and approved by the Authority Having Jurisdiction. It is not, however, intended to require that such systems be upgraded to current adopted standards.
[California Code of Regulations, Title 19, Division 1, §904.2(h)] Testing and Maintenance Requirements.
CFC § 701 High relevance — show source text
Chapter 7 Fire and Smoke Protection Features
The maintenance of assemblies required to be fire-resistance rated is a key component in a passive fire protection philosophy. Chapter 7 sets forth requirements to maintain required fire-resistance ratings of building elements and limit fire spread. Section 701 addresses the basics of what construction elements such as fire barriers and smoke barriers need to be maintained as well as defining the owner’s responsibility. Sections 703 through 708, deals with various fire and smoke protection features that must also be maintained.
xiv 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Chapter 8 Interior Finish, Decorative Materials and Furnishings
The overall purpose of Chapter 8 is to regulate interior finishes, decorative materials and furnishings in new and existing buildings so that they do not significantly add to or create fire hazards within buildings. This chapter is consistent with Chapter 8 of the CBC, which regulates the interior finishes of new buildings.
Chapter 9 Fire Protection and Life Safety Systems
Chapter 9 prescribes the minimum requirements for active systems of fire protection equipment to perform the following functions: detect a fire, alert the occupants or fire department of a fire emergency, and control smoke and control or extinguish the fire. Generally, the requirements are based on the occupancy, the height and the area of the building because these are the factors that most affect firefighting capabilities and the relative hazard of a specific building or portion thereof. This chapter parallels and is substantially duplicated in Chapter 9 of the CBC; however, this chapter also contains periodic testing criteria that are not contained in the CBC. In addition, the special fire protection system requirements based on use and occupancy found in CBC Chapter 4 are duplicated in CFC Chapter 9 as a user convenience.
Chapter 10 Means of Egress
The criteria in Chapter 10 regulating the design of the means of egress system are established as the primary method for protection of occupants by allowing timely relocation or evacuation. Both prescriptive and performance language is utilized for determination of a safe exiting system. It addresses all portions of the means of egress system (i.e., exit access, exits and exit discharge) and includes design requirements as well as provisions regulating individual components. The requirements detail the size, arrangement, number and protection of means of egress components. The means of egress protection requirements work in coordination with other sections of the code, such as protection of vertical openings (see Chapter 7 of the CBC), interior finish (see Chapter 8 of the CBC), fire suppression and detection systems (see Chapter 9) and numerous others, all having an impact on life safety. Chapter 10 of the CBC is duplicated in Chapter 10 of the CFC; however, the CFC contains one additional section on the maintenance of the means of egress system in existing buildings.
Chapter 11 Construction Requirements for Existing Buildings
Chapter 11 applies to existing buildings constructed prior to the adoption of the code and intends to provide a minimum degree of fire and life safety to persons occupying existing buildings by providing for retroactive requirements to install or upgrade fire safety features to such buildings that do not comply with the minimum requirements of the CBC. Prior to the 2009 edition, its content existed in the CFC but in a random manner that was neither efficient nor user-friendly. In the 2007/2008 International Code Council (ICC) code development cycle, a code change (F294-07/ 08) was approved that consolidated the retroactive elements of CFC into a single chapter for easier and more efficient reference and application to existing buildings.
Chapter 12 Energy Systems
CFC § 701 High relevance — show source text
PART I—ADMINISTRATIVE
Chapter 1 Scope and Administration.
Chapter 1 establishes the limits of applicability of the code and describes how the code is to be applied and enforced. The provisions of Chapter 1 establish the authority and duties of the code official appointed by the authority having jurisdiction and also establish the rights and privileges of the design professional, contractor and property owner.
Chapter 2 Definitions.
Chapter 2 is the repository of the definitions of terms used in the body of the code. The user of the code should be familiar with and consult this chapter because the definitions are essential to the correct interpretation of the code and because the user may not be aware that a term is defined.
PART II—GENERAL SAFETY PROVISIONS
Chapter 3 General Requirements
General regulations contained in Chapter 3, are intended to improve premises safety for everyone, including construction workers, tenants, operations and maintenance personnel, and emergency response personnel.
Chapter 4 Emergency Planning and Preparedness
Chapter 4 addresses the human contribution to life safety during emergencies. Continuous training and scheduled fire, evacuation and lockdown drills can be as important as the required periodic inspections and maintenance of built-in fire protection features. The level of preparation by the occupants also improves the emergency responders’ abilities during an emergency.
PART III—BUILDING AND EQUIPMENT DESIGN FEATURES
Chapter 5 Fire Service Features
The requirements of Chapter 5 apply to all buildings and occupancies and pertain to access roads, access to building openings and roofs, premises identification, key boxes, fire protection water supplies, fire command centers, fire department access to equipment, and in-building emergency responder communication system coverage.
Chapter 6 Building Services and Systems
Chapter 6 provides a more systematic view of building systems and services as they relate to potential safety hazards and when and how they should be installed.
Chapter 7 Fire and Smoke Protection Features
The maintenance of assemblies required to be fire-resistance rated is a key component in a passive fire protection philosophy. Chapter 7 sets forth requirements to maintain required fire-resistance ratings of building elements and limit fire spread. Section 701 addresses the basics of what construction elements such as fire barriers and smoke barriers need to be maintained as well as defining the owner’s responsibility. Sections 703 through 708, deals with various fire and smoke protection features that must also be maintained.
xiv 2025 CALIFORNIA FIRE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Chapter 8 Interior Finish, Decorative Materials and Furnishings
The overall purpose of Chapter 8 is to regulate interior finishes, decorative materials and furnishings in new and existing buildings so that they do not significantly add to or create fire hazards within buildings. This chapter is consistent with Chapter 8 of the CBC, which regulates the interior finishes of new buildings.
Chapter 9 Fire Protection and Life Safety Systems
Chapter 9 prescribes the minimum requirements for active systems of fire protection equipment to perform the following functions: detect a fire, alert the occupants or fire department of a fire emergency, and control smoke and control or extinguish the fire. Generally, the requirements are based on the occupancy, the height and the area of the building because these are the factors that most affect firefighting capabilities and the relative hazard of a specific building or portion thereof. This chapter parallels and is substantially duplicated in Chapter 9 of the CBC; however, this chapter also contains periodic testing criteria that are not contained in the CBC. In addition, the special fire protection system requirements based on use and occupancy found in CBC
CFC § 8-3 High relevance — show source text
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CONTENTS
802 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
803 Interior Wall and Ceiling Finish in Existing Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4 804 Interior Wall and Ceiling Trim and Interior Floor Finish in New and Existing Buildings . . . . . . . . . . . . 8-7 805 Upholstered Furniture and Mattresses in New and Existing Buildings . . . . . . . . . . . . . . . . . . . . . . . . . 8-8 806 Natural Decorative Vegetation in New and Existing Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-10 807 Decorative Materials and Artificial Decorative Vegetation in New and Existing Buildings. . . . . . . 8-10 808 Furnishings Other than Upholstered Furniture and Mattresses or Decorative Materials in New and Existing Buildings. . . . . . . . . . . . . . . . . . . . 8-14
CHAPTER 9 FIRE PROTECTION AND LIFE SAFETY
SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
901 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
902 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-11
903 Automatic Sprinkler Systems. . . . . . . . . . . . . . . . . . . . 9-13 904 Alternative Automatic Fire-Extinguishing Systems . 9-24 905 Standpipe Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-28 906 Portable Fire Extinguishers. . . . . . . . . . . . . . . . . . . . . . 9-31 907 Fire Alarm and Detection Systems . . . . . . . . . . . . . . . 9-39 908 Emergency Alarm Systems . . . . . . . . . . . . . . . . . . . . . . 9-57 909 Smoke Control Systems. . . . . . . . . . . . . . . . . . . . . . . . . 9-57 910 Smoke and Heat Removal. . . . . . . . . . . . . . . . . . . . . . . 9-66
CFC § 901.4.3 High relevance — show source text
901.4.3 Alterations in buildings and structures. For any alteration within a building or structure, the fire protection and life safety systems shall be extended, altered or augmented to maintain and continue protection within the building or structure. Persons shall not remove or modify any fire protection or life safety system installed or maintained under the provisions of this code or the California Building Code without approval from the fire code official.
901.4.4 Fire areas. Where buildings, or portions thereof, are divided into fire areas so as not to exceed the limits established for requiring a fire protection system in accordance with this chapter, such fire areas shall be separated by fire barriers constructed in accordance with Section 707 of the California Building Code or horizontal assemblies constructed in accordance with Section 711 of the California Building Code, or both, having a fire-resistance rating of not less than that determined in accordance with Section 707.3.10 of the California Building Code .
901.4.5 Additional fire protection systems. In occupancies of a hazardous nature, where special hazards exist in addition to the normal hazards of the occupancy, or where the fire code official determines that access for fire apparatus is unduly difficult, the fire code official shall have the authority to require additional safeguards and fire protection systems. Fire protection and life safety systems required under this section shall be installed in accordance with this code and the applicable referenced standards.
901.4.6 Appearance of equipment. Any device that has the physical appearance of life safety or fire protection equipment but that does not perform that life safety or fire protection function shall be prohibited.
901.4.7 Pump and riser room size. Where provided, fire pump rooms and automatic sprinkler system riser rooms shall be designed with adequate space for all equipment necessary for the installation, as defined by the manufacturer, with sufficient working space around the stationary equipment. Clearances around equipment to elements of permanent construction, including other installed equipment and appliances, shall be sufficient to allow inspection, service, repair or replacement without removing such elements of permanent construction or disabling the function of a required fire-resistance-rated assembly. Fire
2025 CALIFORNIA FIRE CODE 9-7
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FIRE PROTECTION AND LIFE SAFETY SYSTEMS
pump and automatic sprinkler system riser rooms shall be provided with doors and unobstructed passageways large enough to allow removal of the largest piece of equipment.
901.4.7.1 Access. Automatic sprinkler system risers, fire pumps and controllers shall be provided with ready access. Where located in a fire pump room or automatic sprinkler system riser room, the door shall be permitted to be locked provided that the key is available at all times.
901.4.7.2 Marking on access doors. Access doors for automatic sprinkler system riser rooms and fire pump rooms shall be labeled with an approved sign. The lettering shall be in contrasting color to the background. Letters shall have a minimum height of 2 inches (51 mm) with a minimum stroke of [3] / 8 inch (10 mm).
901.4.7.3 Environment. Automatic sprinkler system riser rooms and fire pump rooms shall be maintained at a temperature of not less than 40°F (4°C). Heating units shall be permanently installed.
901.4.7.4 Lighting. Permanently installed artificial illumination shall be provided in the automatic sprinkler system riser rooms and fire pump rooms.
CFC § 906.10 High relevance — show source text
[F] 906.10 Wheeled units. Wheeled fire extinguishers shall be conspicuously located in a designated location.
SECTION 907—FIRE ALARM AND DETECTION SYSTEMS
[F] 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components.
[F] 907.1.1 Construction documents. Construction documents for fire alarm systems shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code, the Califor- nia Fire Code ; and relevant laws, ordinances, rules and regulations, as determined by the fire code official.
[F] 907.1.2 Fire alarm shop drawings. Shop drawings for fire alarm systems shall be prepared in accordance with NFPA 72 and submitted for review and approval prior to system installation.
[F] 907.1.3 Equipment. Systems and components shall be California State Fire Marshal listed and approved in accordance with California Code of Regulations, Title 19, Division 1 for the purpose for which they are installed.
[F] 907.1.4 Fire-walls and fire barrier walls. For the purpose of Section 907 fire walls and fire barrier walls shall not define separate buildings.
[F] 907.1.5 Fire alarm use. A fire alarm system shall not be used for any purpose other than fire warning or mass notification and where permitted by NFPA 72.
[F] 907.2 Where required—new buildings and structures. An approved fire alarm system installed in accordance with the provisions of this code and NFPA 72 shall be provided in new buildings and structures in accordance with Sections 907.2.1 through 907.2.29 and provide occupant notification in accordance with Section 907.5, unless other requirements are provided by another section of this code.
Not fewer than one manual fire alarm box shall be provided in an approved location to initiate a fire alarm signal for fire alarm systems employing automatic fire detectors or waterflow detection devices. Where other sections of this code allow elimination of fire alarm boxes due to sprinklers, or automatic fire alarm systems, a single fire alarm box shall be installed at a location approved by the enforcing agency.
Exceptions:
- The manual fire alarm box is not required for fire alarm control units dedicated to elevator recall control and supervisory service and fire sprinkler monitoring.
- The manual fire alarm box is not required for Group R-2 occupancies unless required by the fire code official to provide a means for fire watch personnel to initiate an alarm during a sprinkler system impairment event. Where provided, the manual fire alarm box shall not be located in an area that is open to the public. 3. The manual fire alarm box is not required to be installed when approved by the fire code official.
CFC § 904.2 High relevance — show source text
(A) The intent of this section is to cover automatic fire extinguishing systems as originally designed, installed and approved by the Authority Having Jurisdiction. It is not, however, intended to require that such systems be upgraded to current adopted standards.
[California Code of Regulations, Title 19, Division 1, §904.2(h)] Testing and Maintenance Requirements.
(h) At the time of testing and maintenance, building management shall be consulted to avoid unnecessary disturbance of normal building operation.
[California Code of Regulations, Title 19, Division 1, §904.2(i)] Testing and Maintenance Requirements.
(i) The licensee shall contact the local fire authority having jurisdiction prior to testing and maintenance of a system when required by the local fire authority having jurisdiction to do so.
901.6.1 Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1 and California Code of Regulations, Title 19, Division 1, Chapters 3 and 5.
[California Code of Regulations, Title 19, Division 1, §904.1(a)] Inspection Requirements.
(a) A license shall not be required to perform inspections. Inspections may be conducted by any person designated by the building owner or occupant who has developed competence through training and experience.
[California Code of Regulations, Title 19, Division 1, §904.2(g)] Testing and Maintenance Requirements.
(g) Prior to activating any fire alarm component of an automatic fire extinguishing system, the licensee shall ensure that the licensee is capable of restoring the fire alarm system.
TABLE 901.6.1—FIRE PROTECTION SYSTEM INSPECTION, TESTING AND MAINTENANCE STANDARDS Col2 SYSTEM STANDARD Portable fire extinguishers California Code of Regulations, Title 19, Division 1, Chapter 3 Carbon dioxide fire-extinguishing systems NFPA 12 Halon 1301 fire-extinguishing systems NFPA 12A Dry-chemical extinguishing systems NFPA 17 Wet-chemical extinguishing systems NFPA 17A Water-based fire protection systems California Code of Regulations, Title 19, Division 1, Chapter 5 Fire alarm systems NFPA 72 Fire dampers NFPA 80 Smoke dampers NFPA 105 Smoke and heat vents NFPA 204 Water-mist systems NFPA 750 Clean-agent extinguishing systems NFPA 2001 Aerosol fire-extinguishing systems NFPA 2010 901.6.2 Integrated testing. Where two or more fire protection or life safety systems are interconnected, the intended response of subordinate fire protection and life safety systems shall be verified when required testing of the initiating system is conducted. In addition, integrated testing shall be performed in accordance with Sections 901.6.2.1 and 901.6.2.2.
CFC § 901.5.1 High relevance — show source text
901.5.1 Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire protection and life safety systems have been tested and approved.
901.6 Inspection, testing and maintenance. Fire protection and life safety systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected, tested and maintained or removed in accordance with Section 901.8.
All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by these regulations shall be maintained in an operable condition at all times in accordance with this code and California Code of Regulations, Title 19, Division 1. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment, material or systems to their original normal and operational condition.
[California Code of Regulations, Title 19, Division 1, §1.14] Maintenance.
Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fire-resistive assembly or any other fire safety assembly, device, material or equipment installed and retained in service in any building or structure subject to California Code of Regulations, Title 19, Division 1 regulations shall be maintained in an operable condition at all times in accordance with California Code of Regula- tions, Title 19, Division 1 regulations and with their intended use.
[California Code of Regulations, Title 19, Division 1, §3.24] Maintenance of Equipment.
All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equip- ment, material or systems required by California Code of Regulations, Title 19, Division 1 shall be maintained in an operable condition at all times. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment material or systems to their original normal and operational condition.
[California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies.
(a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspec- tion, testing and maintenance and additional procedures.
[California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies.
(1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D and G as amended by the State of California. (Published as NFPA 25, 2013 Califor- nia Edition.)
[California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies.
(b) When proof of the installation date of standpipe systems or automatic fire sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985.
[California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements.
CFC § 904.2 High relevance — show source text
[California Code of Regulations, Title 19, Division 1, §904.2(g)] Testing and Maintenance Requirements.
(g) Prior to activating any fire alarm component of an automatic fire extinguishing system, the licensee shall ensure that the licensee is capable of restoring the fire alarm system.
TABLE 901.6.1—FIRE PROTECTION SYSTEM INSPECTION, TESTING AND MAINTENANCE STANDARDS Col2 SYSTEM STANDARD Portable fire extinguishers California Code of Regulations, Title 19, Division 1, Chapter 3 Carbon dioxide fire-extinguishing systems NFPA 12 Halon 1301 fire-extinguishing systems NFPA 12A Dry-chemical extinguishing systems NFPA 17 Wet-chemical extinguishing systems NFPA 17A Water-based fire protection systems California Code of Regulations, Title 19, Division 1, Chapter 5 Fire alarm systems NFPA 72 Fire dampers NFPA 80 Smoke dampers NFPA 105 Smoke and heat vents NFPA 204 Water-mist systems NFPA 750 Clean-agent extinguishing systems NFPA 2001 Aerosol fire-extinguishing systems NFPA 2010 901.6.2 Integrated testing. Where two or more fire protection or life safety systems are interconnected, the intended response of subordinate fire protection and life safety systems shall be verified when required testing of the initiating system is conducted. In addition, integrated testing shall be performed in accordance with Sections 901.6.2.1 and 901.6.2.2.
901.6.2.1 High-rise buildings. For high-rise buildings, integrated testing shall comply with NFPA 4, with an integrated test performed prior to issuance of the certificate of occupancy and at intervals not exceeding 10 years, unless otherwise specified by an integrated system test plan prepared in accordance with NFPA 4. If an equipment failure is detected during integrated testing, a repeat of the integrated test shall not be required, except as necessary to verify operation of fire protection or life safety functions that are initiated by equipment that was repaired or replaced.
901.6.2.2 Smoke control systems. Where a fire alarm system is integrated with a smoke control system as outlined in Section 909, integrated testing shall comply with NFPA 4, with an integrated test performed prior to issuance of the certificate of occu
2025 CALIFORNIA FIRE CODE 9-9
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FIRE PROTECTION AND LIFE SAFETY SYSTEMS
pancy and at intervals not exceeding 10 years, unless otherwise specified by an integrated system test plan prepared in accordance with NFPA 4. If an equipment failure is detected during integrated testing, a repeat of the integrated test shall not be required, except as necessary to verify operation of fire protection or life safety functions that are initiated by equipment that was repaired or replaced.
901.6.3 Records. Records of all system inspections, tests and maintenance shall be maintained in accordance with Section 110.3.
[California Code of Regulations, Title 19, Division 1, §904.1(b)] Inspection Requirements.
(b) Records of all inspections shall be retained on the premises by the building or system owner for a period of five years after the next required inspection.
CFC § 901.2.1 High relevance — show source text
901.2.1 Statement of compliance. Before requesting final approval of the installation, where required by the fire code official, the installing contractor shall furnish a written statement to the fire code official that the subject fire protection or life safety system has been installed in accordance with approved plans and has been tested in accordance with the manufacturer’s specifications and the appropriate installation standard. Any deviations from the design standards shall be noted and copies of the approvals for such deviations shall be attached to the written statement.
901.3 Permits. Permits shall be required as set forth in Sections 105.5 and 105.6.
901.4 Fire protection and life safety systems. Fire protection and life safety systems shall be installed, repaired, operated and maintained in accordance with this code and the California Building Code .
901.4.1 Required fire protection and life safety systems. Fire protection and life safety systems required by this code or the California Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. A fire protection or life safety system for which a design option, exception or reduction to the provisions of this code or the California Building Code has been granted shall be considered to be a required system.
901.4.2 Nonrequired fire protection and life safety systems. Fire protection and life safety systems or portion thereof not required by this code or the California Building Code shall be allowed to be furnished for partial or complete protection provided that such installed systems meet the applicable requirements of this code and the California Building Code .
901.4.3 Alterations in buildings and structures. For any alteration within a building or structure, the fire protection and life safety systems shall be extended, altered or augmented to maintain and continue protection within the building or structure. Persons shall not remove or modify any fire protection or life safety system installed or maintained under the provisions of this code or the California Building Code without approval from the fire code official.
901.4.4 Fire areas. Where buildings, or portions thereof, are divided into fire areas so as not to exceed the limits established for requiring a fire protection system in accordance with this chapter, such fire areas shall be separated by fire barriers constructed in accordance with Section 707 of the California Building Code or horizontal assemblies constructed in accordance with Section 711 of the California Building Code, or both, having a fire-resistance rating of not less than that determined in accordance with Section 707.3.10 of the California Building Code .
901.4.5 Additional fire protection systems. In occupancies of a hazardous nature, where special hazards exist in addition to the normal hazards of the occupancy, or where the fire code official determines that access for fire apparatus is unduly difficult, the fire code official shall have the authority to require additional safeguards and fire protection systems. Fire protection and life safety systems required under this section shall be installed in accordance with this code and the applicable referenced standards.
901.4.6 Appearance of equipment. Any device that has the physical appearance of life safety or fire protection equipment but that does not perform that life safety or fire protection function shall be prohibited.
CFC § 903.3.1.1. High relevance — show source text
Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
d. Group H occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5.1.
e. Group R-3 and R-4 buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where auto-
matic sprinkler systems are permitted in accordance with Section 903.3.1.3.
f.
Not permitted in nonsprinklered Group I-3 occupancies.|For SI: 1 foot = 304.8 mm.
a. See the following sections for modifications to exit access travel distance requirements:
Section 402.8 of the_California Building Code_: For the distance limitation in malls.
Section 407.4 of the_California Building Code_: For the distance limitation in Group I-2.
Section 408.3.10 of the California Building Code: For increased limitation in Group I-3.
Sections 408.6.1 and 408.8.1 of the_California Building Code_: For the distance limitations in Group I-3.
Section 411.2 of the_California Building Code_: For the distance limitation in special amusement areas.
Section 412.6 of the_California Building Code_: For the distance limitations in aircraft manufacturing facilities.
Section 422.3.4 of the California Building Code: For the distance limitation in ambulatory care facilities.
Section 1006.2.2.2: For the distance limitation in refrigeration machinery rooms.
Section 1006.2.2.3: For the distance limitation in refrigerated rooms and spaces.
Section 1006.3.4: For buildings with one exit.
Section 1017.2.2: For increased distance limitation in Groups F-1 and S-1.
Section 1017.2.3: For increased distance limitation in Group H-5.
Section 1030.7: For increased limitation in assembly seating.
Section 3103.4 of the_California Building Code_: For temporary structures.
Section 3104.9 of the_California Building Code_: For pedestrian walkways.
b. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic
sprinkler systems are permitted in accordance with Section 903.3.1.2.
c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
d. Group H occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5.1.
e. Group R-3 and R-4 buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where auto-
matic sprinkler systems are permitted in accordance with Section 903.3.1.3.
f.
Not permitted in nonsprinklered Group I-3 occupancies.|For SI: 1 foot = 304.8 mm.
a. See the following sections for modifications to exit access travel distance requirements:
Section 402.8 of the_California Building Code_: For the distance limitation in malls.
Section 407.CFC § 9-7 High relevance — show source text
CHAPTER 9 FIRE PROTECTION AND LIFE SAFETY
SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
901 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-7
902 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-11
903 Automatic Sprinkler Systems. . . . . . . . . . . . . . . . . . . . 9-13 904 Alternative Automatic Fire-Extinguishing Systems . 9-24 905 Standpipe Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-28 906 Portable Fire Extinguishers. . . . . . . . . . . . . . . . . . . . . . 9-31 907 Fire Alarm and Detection Systems . . . . . . . . . . . . . . . 9-39 908 Emergency Alarm Systems . . . . . . . . . . . . . . . . . . . . . . 9-57 909 Smoke Control Systems. . . . . . . . . . . . . . . . . . . . . . . . . 9-57 910 Smoke and Heat Removal. . . . . . . . . . . . . . . . . . . . . . . 9-66
911 Explosion Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-67 912 Fire Department Connections . . . . . . . . . . . . . . . . . . . 9-69 913 Fire Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-70 914 Fire Protection Based on Special Detailed Requirements of Use and Occupancy . . . . . . . . . . 9-71 915 Carbon Monoxide (CO) Detection . . . . . . . . . . . . . . . . 9-75 916 Gas Detection Systems . . . . . . . . . . . . . . . . . . . . . . . . . 9-77 917 Mass Notification Systems . . . . . . . . . . . . . . . . . . . . . . 9-78
CHAPTER 10 MEANS OF EGRESS. . . . . . . . . . . . . . . . . . . . 10-5
1001 Administration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
1002 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
1003 General Means of Egress . . . . . . . . . . . . . . . . . . . . .
Frequently asked questions
Which CFC sections tell me when sprinklers or fire alarms are required?
Section 903 (automatic sprinkler systems) and Section 907 (fire alarm and detection systems) set the primary requirements; applicability is generally determined by occupancy, height and area and by cross‑references to the CBC and other CFC sections. Check Chapter 9 for the specific triggers.
How often must systems be inspected, tested and maintained?
Inspection and testing follow the standards listed in Table 901.6.1 and California’s Title 19 frequencies; water‑based systems use NFPA 25 schedules, while fire alarms reference NFPA 72. Title 19 §904 provides California‑specific inspection/testing and maintenance requirements.
What records must I keep after inspections and tests?
Records of inspections, tests and maintenance must be retained per the CFC’s recordkeeping rules (see §901.6.3) and Title 19, which requires that inspection records be kept on the premises for specified periods.
More in California Fire Code
- Administration and Definitions
- General Requirements and Emergency Planning
- Fire Service Features and Fire Department Access
- Referenced Standards and Adoptable Appendices (Chapter 80; Appendices A–Q)
- Fire and Smoke Protection Features (fire‑resistance, barriers)
- Interior Finish, Decorative Materials and Furnishings
- Fire Protection and Life‑Safety Systems (sprinklers, alarms, smoke control)
- Means of Egress (exit design and maintenance)
- Construction Requirements for Existing Buildings (retrofit rules)
- Energy Systems and Stationary Energy Storage (ESS)
- Special Occupancies and Operations (chapters 20–41, 48–49)
- Hazardous Materials — Storage, Use and Handling (Chapters 50–67)
Ask about the CFC
Get cited, plain-English answers on the California Fire Code for your project — any code section, any scenario.
Start Free Trial