Title 24 · California Energy Code

How to calculate the minimum PV capacity for a new building

For most new California buildings you calculate required PV two ways — (1) multiply conditioned floor area by a W/ft2 factor from the code table and divide by 1000, and (2) compute a roof‑area limit (SARA × 18 W/ft2 steep or ×14 low‑slope). The code requires the smaller result, subject to minimum thresholds and exceptions; see §§ 140.10(a), 170.2(g), and 150.1(c)14 for the precise formulas and tables.

Last reviewed: July 6, 2026

What the code requires — plain English

The California Energy Code requires most newly constructed buildings to have a minimum photovoltaic (PV) system sized either by an area‑based factor tied to the building’s conditioned floor area (CFA) or by the building’s available solar access roof area (SARA) — whichever produces the smaller system capacity. The capacity equations are set in the prescriptive sections for nonresidential/hotel/motel (§ 140.10(a)) and multifamily and single‑family dwelling rules (§ 170.2(g) and § 150.1(c)14). See Equation 140.10‑A, Equation 170.2‑D, and Equation 150.1‑C for the exact formulas and the tables of capacity factors.

The single most important rule: size the PV to the smaller of (A) the equation based on conditioned floor area (kW PVdc = CFA × A / 1000) or (B) the capacity limited by usable roof area (SARA × 18 W/ft2 for steep roofs or SARA × 14 W/ft2 for low‑sloped roofs).


Requirements in detail

Key defined terms (first use is bold)

  • CFA (Conditioned Floor Area) — the building floor area subject to the PV requirement. § 140.10(a) / § 170.2(g) / § 150.1(c)14 define where CFA is used.
  • SARA (Solar Access Roof Area) — roof area capable of structurally supporting PV and meeting solar access rules; some roof areas are explicitly excluded in the code. See list of inclusions/exclusions under § 140.10(a) and § 170.2(g).
  • kW PVdc — the minimum rated PV system capacity in direct current kilowatts (what the equations produce).

Core sizing equations and decision points

Use the following equations (code text paraphrased):

Decision dimension Formula (paraphrase) When to use / notes Code Reference
PV capacity from conditioned floor area kW PVdc = (CFA × A) / 1000 A = PV capacity factor (W/ft2) from the appropriate table for building type and climate zone. Apply for §140.10 and §170.2 situations. § 140.10(a) — Equation 140.10‑A
Multifamily (>3 stories) same formula kW PVdc = (CFA × A) / 1000 Uses Table 170.2‑U capacity factors (A) for building type & climate zone. § 170.2(g) — Equation 170.2‑D
Single‑family (annual output form) kW PV = (CFA × A)/1000 + (N_DU × B) Single‑family/smaller multifamily use Equation 150.1‑C with CFA and dwelling‑unit adjustments from Table 150.1‑C. § 150.1(c)14 — Equation 150.1‑C
SARA (roof area) cap kW PVdc (SARA limit) = (SARA ft2 × 18 W/ft2) / 1000 for steep roofs OR (SARA ft2 × 14 W/ft2) /1000 for low‑slope roofs The PV required is the smaller of the number from the CFA equation or this SARA limit.
BESS reduction PV size may be reduced by 25% if installed with a qualifying BESS (meets Joint Appendix JA12 and min cycling capacity) Applies where code explicitly allows the reduction (single family, multifamily, other sections cite this allowance).

Decision‑relevant thresholds / automatic exceptions

  • No PV required when total SARA < 3% of CFA.
  • Minimum PV size exceptions: many sections set a floor under which PV is not required. Typical values in the code: 4 kW (nonresidential/multifamily prescriptive), 1.8 kW (single‑family Exception 2) — check the specific section applicable to your building type.
  • Minimum contiguous SARA for installation: 80 square feet — if SARA is not at least 80 contiguous ft2, the PV requirement may not apply.

Other sizing rules to watch

  • For mixed‑occupancy buildings, apply the CFA‑based equation to each listed building type and sum the capacities.
  • For nonresidential multitenant buildings small tenant spaces (<= 2,000 ft2) with separate HVAC and meter can be excluded from the Equation 140.10‑A CFA calculation (see exception text).
  • The SARA calculation for steep slope roofs excludes northerly azimuth roof areas in some steep‑slope rules; read the steep/low slope clarifications in the applicable section.

Exceptions & special cases

  • Exception: If the PV computed by the equation is below the section’s minimum threshold (e.g., 4 kW per § 140.10(a) for nonresidential / § 170.2(g) for multifamily), then no PV is required. Confirm the exact threshold in the applicable section for your building.
  • Exception for small contiguous roof area: if SARA < 80 contiguous ft2, PV may not be required.
  • BESS interaction: Where the code allows, you may reduce the PV size by 25% when you install a qualifying battery energy storage system (BESS), but the BESS must meet the Joint Appendix JA12 requirements (including minimum cycling capacity) to qualify. The BESS sizing and exceptions are spelled out in Sections 140.10(b) and 170.2(h).
  • Multifamily >3 stories: Section 170.2(g) uses the same CFA‑based formula but with its own A‑table (Table 170.2‑U) and separate exceptions (including the possibility of reduced PV when BESS is provided).

If a particular nuance (for example, a local program that compensates PV via virtual net billing) applies, the code provides exceptions or alternate compliance paths — read the specific exception language in the referenced section.


Common mistakes

  • Using the wrong basis: applying the SARA multiplier when you must use the CFA equation (or vice versa). Remember: the required PV is the smaller of the CFA‑equation result or the SARA limit.
  • Forgetting to check minimum thresholds (e.g., 4 kW or 1.8 kW): if your calculation produces a value below the threshold, you may not be required to install PV.
  • Mis‑reading units: the A / B factors are in watts per square foot (W/ft2) — you must divide by 1000 in the formula to produce kW.
  • Ignoring mixed‑occupancy rules: for mixed‑use projects you must compute per listed building type and sum.
  • Incorrect SARA computation: exclude roof areas with < 70% annual solar access and other specified exclusions in the code when calculating SARA.

Worked example — hotel in Climate Zone 1 (concrete numbers tied to the code)

Situation (inputs you must verify):

  • Building type: Hotel/Motel subject to § 140.10(a).
  • Conditioned floor area (CFA): 25,000 ft2.
  • Climate Zone: CZ 1 (use the code table column for CZ1).
  • Table 140.10‑A (PV capacity factor A) lists 1.69 W/ft2 for Hotel/Motel in CZ1 (table excerpt).
  • SARA: assume 3,000 ft2 of usable roof area available; roof is low‑sloped (uses 14 W/ft2 factor for SARA limit).

Step 1 — CFA‑based PV (Equation 140.10‑A):
kW PVdc = (CFA × A) / 1000 = (25,000 ft2 × 1.69 W/ft2) / 1000 = 42.25 kWdc.

Step 2 — SARA limit (SARA × 14 W/ft2 for low slope):
kW PVdc (SARA limit) = (3,000 ft2 × 14 W/ft2) / 1000 = 42.0 kWdc.

Decision: Code requires the smaller of the two values, so required minimum PV = 42.0 kWdc (SARA‑limited).

Step 3 — check exceptions/thresholds: the required PV is > the typical 4 kW minimum exception so the requirement stands (no exception applies). Also check contiguous SARA (≥ 80 ft2) and SARA ≥ 3% of CFA: 3% of CFA = 750 ft2; here SARA = 3,000 ft2 so OK.

Optional: If the project installs a qualifying BESS and meets JA12 minimums, the owner may be permitted to reduce the PV size by 25% where the section allows that option — confirm whether the specific section for your building type authorizes the BESS reduction and whether the BESS meets JA12. If authorized here, 42.0 kW × 0.75 = 31.5 kWdc (after the 25% reduction). Confirm BESS qualification and any local adoption rules.


Related provisions (quick links to code sections to read)

  • § 140.10(a) — Photovoltaic requirements; Equation 140.10‑A (CFA method) and SARA limits.
  • § 140.10(b) — Battery energy storage (BESS) sizing & exceptions tied to PV in § 140.10.
  • § 170.2(g) — Photovoltaic requirements for multifamily buildings > 3 habitable stories; Equation 170.2‑D.
  • § 170.2(h) — BESS requirements for multifamily > 3 stories (sizing equations and exceptions).
  • § 150.1(c)14 — Single‑family residential annual PV sizing Equation 150.1‑C and related exceptions and BESS allowance.
  • Joint Appendix JA11 — PV system minimum qualification requirements (equipment/install). See reference in §§ 140.10 / 170.2 / 150.1.
  • Joint Appendix JA12 — BESS qualification and cycling capacity required for BESS reductions/exceptions.

Code references

Grounded in the retrieved California Energy Code — click a citation to read the verbatim passage:

  • § 140.10 High relevance — show source text

    (b) Battery energy storage system (BESS) requirements. All buildings that are required by Section 140.10(a) to have a PV system shall also have a BESS meeting the minimum qualification requirements of Reference Joint Appendix JA12. The rated energy capacity shall be not less than the Minimum Rated Useable Energy Capacity determined using Equation 140.10-B or 140.10-C if SARA was used to determine the PV capacity in Section 140.10(a). The rated power capacity shall be not less than the Minimum Power Capacity determined using Equation 140.10-D. In mixed occupancy buildings, the total battery system capacity for the building shall be determined by applying the Minimum Rated Usable Energy Capacity to each of the listed building types and summing the capacities determined for each.

    EQUATION 140.10-B—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY kWh batt = [(CFA × B)/(1,000 × C [0.5] )]

    EQUATION 140.10-C—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY, SARA-ADJUSTED kWh batt = [(CFA × B)/(1,000 × C [0.5] )] x (kW PVdc,SARA /kW PVdc )

    where:

    kWh batt = Minimum Rated Usable Energy Capacity of the BESS in kWh.

    CFA = Conditioned floor area that is subject to the PV system requirements of Section 140.10(a) in square feet.

    kW PVdc = Minimum Rated PV System Capacity in kW from Equation 140.10-A. kW PVdc, SARA = Minimum Rated PV System Capacity in kW from the SARA calculation. B = BESS Capacity Factor in Wh/square foot as specified in Table 140.10-B for the building type. C = Rated single charge-discharge cycle AC to AC (round-trip) efficiency of the BESS.

    EQUATION 140.10-D—BESS MINIMUM RATED POWER CAPACITY

    kW batt = kW batt /4

    where:

    kW batt = Minimum Rated Power Capacity of the BESS in kWdc. kW PVdc = Minimum Rated Useable Energy Capacity of the BESS in kWh. Exception 1 to Section 140.10(b): No BESS is required if the installed PV system capacity is less than 15 percent of the capacity determined by Equation 140.10-A.

    Exception 2 to Section 140.10(b): No BESS is required if the rated usable energy capacity determined by Equation 140.10-B or Equation 140.10-C is less than 10 kWh.

    Exception 3 to Section 140.10(b): For multitenant buildings, the energy capacity of the BESS shall be based on the tenant spaces with more than 5,000 square feet of conditioned floor area. For single-tenant buildings with less than 5,000 square feet of conditioned floor area, no BESS is required.

    146 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE

    COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY

    |TABLE 140.

  • § 1.27 High relevance — show source text

    63|1.27|1.63|1.27|1.63|1.63|1.63|1.63|1.63|1.63|1.63|1.63|1.63|2.46|1.27| |Warehouse|0.39|0.44|0.39|0.44|0.39|0.44|0.44|0.44|0.44|0.44|0.44|0.44|0.44|0.44|0.58|0.39| |Religious Worship|4.25|4.65|3.49|4.52|3.72|4.29|4.64|5.89|5.30|5.67|5.89|4.99|5.78|4.63|7.57|3.90| |Sports & Recreation|2.47|1.97|1.54|2.03|1.60|1.84|1.98|2.63|2.47|2.60|2.75|2.20|2.72|2.15|4.03|1.81| |Multifamily > 3 stories|1.82|2.21|1.82|2.21|1.82|2.21|2.21|2.21|2.21|2.21|2.21|2.21|2.21|2.21|2.77|1.82|

    (h) Battery energy storage system (BESS) requirements—more than three habitable stories. All buildings that are required by Section 170.2(g) to have a PV system shall also have a BESS meeting the minimum qualification requirements of Reference Joint Appendix JA12. The rated energy capacity shall be not less than the Minimum Rated Useable Energy Capacity determined by Equation 170.2-E, or by Equation 170.2-F if SARA was used to determine the PV capacity in Section 170.2-D, and the rated power capacity shall be not less than the Minimum Power Capacity determined by Equation 170.2-G. In mixed occupancy buildings, the total battery system capacity for the building shall be determined by applying the Minimum Rated Usable Energy Capacity to each of the listed building types and summing the capacities determined for each.

    EQUATION 170.2-E—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY kWh batt = k((CFA × B)/(1000 × C [0.5] ))

    EQUATION 170.2-F BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY, SARA-ADJUSTED kWh batt = k((CFA × B)/(1000 × C [0.5] )) × (kWP Vdc,SARA /kWP Vdc )

    268 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES

    where:

    kWh batt = Minimum Rated Usable Energy Capacity of the BESS in kWh.

    kW PVdc = Minimum Rated PV System Capacity in kW from Equation 170.2D. kW PVdc, SARA = Minimum Rated PV System Capacity in kW from the SARA calculation. CFA = Conditioned floor area that is subject to the PV system requirements of Section 170.2(g) in square feet.

  • § 140.9 High relevance — show source text
    1. In a jurisdiction where gas heating is allowed.

    Exception 4 to Section 140.9(c)6: Buildings with an exhaust air heat recovery system and heat recovery chillers designed to provide at least 40 percent of the peak heating load from exhaust heat recovery.

    Exception 5 to Section 140.9(c)6: Exhaust systems requiring wash down systems such as exhaust systems dedicated to perchloric acid fume hoods.

    Exception to Section 140.9(c): Healthcare facilities.

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8 and 25943, Public Resources Code.

    SECTION 140.10—PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS

    (a) Photovoltaic requirements. All newly constructed building types specified in Table 140.10-A, or mixed occupancy buildings where at least 80 percent of the floor area of the building serves one or more of these building types, shall have a newly installed photovoltaic (PV) system meeting the minimum qualification requirements of Reference Joint Appendix JA11. The PV capacity in kW dc shall not be less than the smaller of the minimum rated PV system capacity determined by Equation 140.10-A, or the total of all available solar access roof areas (SARA) multiplied by 18 for steep-sloped roofs or multiplied by 14 for low-sloped roofs. In mixed occupancy buildings, the minimum rated PV system capacity for the building shall be determined by applying Equation 140.10-A to the conditioned floor area of each of the listed building types and summing the capacities determined for each.

    1. SARA includes the area of the building’s roof space capable of structurally supporting a PV system, and the area of all roof space on covered parking areas, carports and all other newly constructed structures on the site that are compatible with supporting a PV system per Title 24, Part 2, Section 1511.10.

    2. SARA does NOT include:

    A. Any area that has less than 70 percent annual solar access. Annual solar access is determined by dividing the total annual solar insolation (accounting for shading obstructions) by the total annual solar insolation if the same areas were unshaded by those obstructions. For all roofs, all obstructions, including those that are external to the building, and obstructions that are part of the building design and elevation features may be considered for the annual solar access calculations.

    B. Occupied roofs as specified by CBC Section 503.1.4. C. Roof area that is otherwise not available due to compliance with: i. Other state building code requirements; or ii. Local building code requirements if the local building code requirements are confirmed by the Executive Director.

    2025 CALIFORNIA ENERGY CODE 145

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE

    COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY

    EQUATION 140.10-A—PHOTOVOLTAIC DIRECT CURRENT CAPACITY

    kW PVdc = (CFA × A)/1000

    where:

    kW PVdc = Minimum rated PV system capacity in kW.

  • § 140.10 High relevance — show source text

    Exception 1 to Section 140.10(a): No PV system is required where the total of all available SARA is less than 3 percent of the conditioned floor area.

    Exception 2 to Section 140.10(a): No PV system is required where the required PV system capacity is less than 4 kW dc .

    Exception 3 to Section 140.10(a): No PV system is required if the SARA contains less than 80 contiguous square feet.

    Exception 4 to Section 140.10(a): Buildings with enforcement-authority-approved roof designs, where the enforcement authority determines it is not possible for the PV system, including panels, modules, components, supports and attachments to the roof structure, to meet ASCE 7-16, Chapter 7, Snow Loads.

    Exception 5 to Section 140.10(a): For nonresidential and hotel/motel multitenant buildings, the PV capacity determined by Equation 140.10-A shall be calculated without including tenant spaces meeting all of the following: i. The tenant space is less than or equal to 2,000 square feet of conditioned space; ii. The tenant space is served by an HVAC system that does not serve other tenant spaces in the building; and iii. The tenant space has an individual utility meter to track electricity consumption that does not include the electricity consumption of other tenant spaces in the building.

    This exception does not apply where the Commission has approved a community solar program for showing compliance as specified in Title 24, Part 1, Section 10-115, or where a load-serving entity provides a program where PV generation is compensated through virtual energy bill credits for occupants of nonresidential and hotel/motel tenant spaces to receive energy bill benefits from netting of energy generation and consumption.

    (b) Battery energy storage system (BESS) requirements. All buildings that are required by Section 140.10(a) to have a PV system shall also have a BESS meeting the minimum qualification requirements of Reference Joint Appendix JA12. The rated energy capacity shall be not less than the Minimum Rated Useable Energy Capacity determined using Equation 140.10-B or 140.10-C if SARA was used to determine the PV capacity in Section 140.10(a). The rated power capacity shall be not less than the Minimum Power Capacity determined using Equation 140.10-D. In mixed occupancy buildings, the total battery system capacity for the building shall be determined by applying the Minimum Rated Usable Energy Capacity to each of the listed building types and summing the capacities determined for each.

    EQUATION 140.10-B—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY kWh batt = [(CFA × B)/(1,000 × C [0.5] )]

    EQUATION 140.10-C—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY, SARA-ADJUSTED kWh batt = [(CFA × B)/(1,000 × C [0.5] )] x (kW PVdc,SARA /kW PVdc )

    where:

    kWh batt = Minimum Rated Usable Energy Capacity of the BESS in kWh.

    CFA = Conditioned floor area that is subject to the PV system requirements of Section 140.10(a) in square feet.

  • § 170.2 High relevance — show source text

    The PV capacity in kW dc shall not be less than the smaller of the minimum rated PV system capacity determined by Equation 170.2-D, or the total of all available solar access roof areas (SARA) multiplied by 18 for steep-sloped roofs or multiplied by 14 for low-sloped roofs. In mixed occupancy buildings, the minimum rated PV system capacity for the building shall be determined by applying Equation 170.2-D to the conditioned floor area of each of the listed building types and summing the capacities determined for each.

    1. SARA include the area of the building’s roof space capable of structurally supporting a PV system, and the area of all roof space on covered parking areas, carports and all other newly constructed structures on the site that are compatible with supporting a PV system per Title 24, Part 2, Section 1511.10.

    2. SARA does not include:

    A. Any area that has less than 70 percent annual solar access. Annual solar access is determined by dividing the total annual solar insolation (accounting for shading obstructions) by the total annual solar insolation if the same areas were unshaded by those obstructions. For all roofs, all obstructions including those that are external to the building,

    2025 CALIFORNIA ENERGY CODE 267

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES

    and obstructions that are part of the building design and elevation features, may be considered for the annual solar access calculations.

    B. Occupied roofs as specified by CBC Section 503.1.4. C. Roof area that is otherwise not available due to compliance with: i. Other state building code requirements, or ii. Local building code requirements if the local building code requirements are confirmed by the Executive Director.

    EQUATION 170.2-D—PHOTOVOLTAIC DIRECT CURRENT CAPACITY

    kW PVdc = (CFA × A)/1000

    where:

    kW PVdc = Minimum rated PV system capacity in kW.

    CFA = Conditioned floor area in square feet.

    A = PV capacity factor in W/square foot as specified in Table 170.2-U for the building type.

    Exception 1 to Section 170.2(g): No PV system is required where the total of all available SARA is less than 3 percent of the conditioned floor area.

    Exception 2 to Section 170.2(g): No PV system is required where the required PV system capacity is less than 4 kW dc .

    Exception 3 to Section 170.2(g): No PV system is required if the SARA contains less than 80 contiguous square feet.

    Exception 4 to Section 170.2(g): Buildings with enforcement-authority-approved roof designs, where the enforcement authority determines it is not possible for the PV system, including panels, modules, components, supports and attachments to the roof structure, to meet ASCE 7-16, Chapter 7, Snow Loads.

  • § 140.10 Medium relevance — show source text

    EQUATION 140.10-D—BESS MINIMUM RATED POWER CAPACITY

    kW batt = kW batt /4

    where:

    kW batt = Minimum Rated Power Capacity of the BESS in kWdc. kW PVdc = Minimum Rated Useable Energy Capacity of the BESS in kWh. Exception 1 to Section 140.10(b): No BESS is required if the installed PV system capacity is less than 15 percent of the capacity determined by Equation 140.10-A.

    Exception 2 to Section 140.10(b): No BESS is required if the rated usable energy capacity determined by Equation 140.10-B or Equation 140.10-C is less than 10 kWh.

    Exception 3 to Section 140.10(b): For multitenant buildings, the energy capacity of the BESS shall be based on the tenant spaces with more than 5,000 square feet of conditioned floor area. For single-tenant buildings with less than 5,000 square feet of conditioned floor area, no BESS is required.

    146 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE

    COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY

    TABLE 140.10-A—PV CAPACITY FACTORS (W/ft2 of conditioned floor area) Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 Col11 Col12 Col13 Col14 Col15 Col16 Col17
    BUILDING TYPE CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7 CZ 8 CZ 9 CZ 10 CZ 11 CZ 12 CZ 13 ** CZ 14** ** CZ 15** ** CZ 16**
    Events & Exhibits 3.48 4.28 3.66 4.32 3.77 4.05 4.28 4.83 4.63 4.80 5.04 4.44 4.95 4.36 5.48 3.38
    Library 0.39 3.23 2.59 3.25 2.48 2.74 3.04 3.49 3.32 3.69 3.79 3.32 3.79 3.37 4.49 2.84
    Hotel/Motel 1.69 1.90 1.66 1.97 1.69 1.87 1.94 2.22 2.09 2.20 2.30 2.05 2.30 2.02 2.72 1.73
    Office, Financial
    Institution, Unleased
    Tenant Space, Medical
    Office Building/Clinic
    2.59 3.13 2.59 3.13 2.59 3.13 3.13 3.
  • § 140.9 Medium relevance — show source text

    Exception 3 to Section 140.9(c)5: Systems dedicated to vivarium spaces or to spaces classified as biosafety level 3 or higher. Exception 4 to Section 140.9(c)5: Systems that:

    1. Are located where the outdoor dew point temperature is greater than or equal to 64°F at the ASHRAE 2 percent annual dehumidification design condition; and

    2. Include heating and cooling capacity at each zone; and

    3. Do not mechanically cool air handler supply air below 80°F when the outdoor dew point temperature is below 60°F.

    4. Exhaust air heat recovery. Buildings with greater than 10,000 cfm of laboratory exhaust shall include an exhaust air heat recovery system that meets the following: A. A sensible energy recovery ratio of at least 45 percent at heating design conditions and 25 percent at cooling design conditions. B. Heat is recovered from at least 75 percent of all lab exhaust air volume. C. The system includes a run-around coil pump or other means to disable heat recovery. D. The system includes a bypass damper or other means so that the exhaust air pressure drop through the heat exchanger does not exceed 0.4 inch w.g. when heat recovery is disabled.

    Exception 1 to Section 140.9(c)6: Additions or alterations to existing laboratory exhaust systems that do not include exhaust air heat recovery. Exception 2 to Section 140.9(c)6: Buildings where the total laboratory exhaust rate exceeds 20 cfm/ft [2] of roof area.

    Exception 3 to Section 140.9(c)6: Locations that meet both of the following:

    1. In Climate Zone 6 or 7; and

    2. In a jurisdiction where gas heating is allowed.

    Exception 4 to Section 140.9(c)6: Buildings with an exhaust air heat recovery system and heat recovery chillers designed to provide at least 40 percent of the peak heating load from exhaust heat recovery.

    Exception 5 to Section 140.9(c)6: Exhaust systems requiring wash down systems such as exhaust systems dedicated to perchloric acid fume hoods.

    Exception to Section 140.9(c): Healthcare facilities.

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8 and 25943, Public Resources Code.

    SECTION 140.10—PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS

    (a) Photovoltaic requirements. All newly constructed building types specified in Table 140.10-A, or mixed occupancy buildings where at least 80 percent of the floor area of the building serves one or more of these building types, shall have a newly installed photovoltaic (PV) system meeting the minimum qualification requirements of Reference Joint Appendix JA11. The PV capacity in kW dc shall not be less than the smaller of the minimum rated PV system capacity determined by Equation 140.10-A, or the total of all available solar access roof areas (SARA) multiplied by 18 for steep-sloped roofs or multiplied by 14 for low-sloped roofs.

  • § 170.2 Medium relevance — show source text

    The rated energy capacity shall be not less than the Minimum Rated Useable Energy Capacity determined by Equation 170.2-E, or by Equation 170.2-F if SARA was used to determine the PV capacity in Section 170.2-D, and the rated power capacity shall be not less than the Minimum Power Capacity determined by Equation 170.2-G. In mixed occupancy buildings, the total battery system capacity for the building shall be determined by applying the Minimum Rated Usable Energy Capacity to each of the listed building types and summing the capacities determined for each.

    EQUATION 170.2-E—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY kWh batt = k((CFA × B)/(1000 × C [0.5] ))

    EQUATION 170.2-F BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED USABLE ENERGY CAPACITY, SARA-ADJUSTED kWh batt = k((CFA × B)/(1000 × C [0.5] )) × (kWP Vdc,SARA /kWP Vdc )

    268 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES

    where:

    kWh batt = Minimum Rated Usable Energy Capacity of the BESS in kWh.

    kW PVdc = Minimum Rated PV System Capacity in kW from Equation 170.2D. kW PVdc, SARA = Minimum Rated PV System Capacity in kW from the SARA calculation. CFA = Conditioned floor area that is subject to the PV system requirements of Section 170.2(g) in square feet.

    B = BESS Capacity Factor in Wh/square foot as specified in Table 170.2-V for the building type.

    C = Rated single charge-discharge cycle AC to AC (round-trip) efficiency of the BESS.

    EQUATION 170.2-G—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED POWER CAPACITY

    kW batt = kW batt /4

    where:

    kW batt = Minimum Rated Power Capacity of the BESS in kW dc .

    kWh batt = Minimum Rated Usable Energy Capacity of the BESS in kWh.

    Exception 1 to Section 170.2(h): No BESS is required if the installed PV system capacity is less than 15 percent of the capacity determined by Equation 170.2-D.

    Exception 2 to Section 170.2(h): No BESS is required in buildings with BESS requirements with less than 10 kWh minimum rated usable energy capacity.

    |TABLE 170.

  • § 170.2 Medium relevance — show source text

    268 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES

    where:

    kWh batt = Minimum Rated Usable Energy Capacity of the BESS in kWh.

    kW PVdc = Minimum Rated PV System Capacity in kW from Equation 170.2D. kW PVdc, SARA = Minimum Rated PV System Capacity in kW from the SARA calculation. CFA = Conditioned floor area that is subject to the PV system requirements of Section 170.2(g) in square feet.

    B = BESS Capacity Factor in Wh/square foot as specified in Table 170.2-V for the building type.

    C = Rated single charge-discharge cycle AC to AC (round-trip) efficiency of the BESS.

    EQUATION 170.2-G—BATTERY ENERGY STORAGE SYSTEM MINIMUM RATED POWER CAPACITY

    kW batt = kW batt /4

    where:

    kW batt = Minimum Rated Power Capacity of the BESS in kW dc .

    kWh batt = Minimum Rated Usable Energy Capacity of the BESS in kWh.

    Exception 1 to Section 170.2(h): No BESS is required if the installed PV system capacity is less than 15 percent of the capacity determined by Equation 170.2-D.

    Exception 2 to Section 170.2(h): No BESS is required in buildings with BESS requirements with less than 10 kWh minimum rated usable energy capacity.

    TABLE 170.2-V—BESS CAPACITY FACTORS (Wh/ft2 of conditioned floor area) Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 Col11 Col12 Col13 Col14 Col15 Col16 Col17
    BUILDING TYPE CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7 CZ 8 CZ 9 CZ 10 CZ 11 CZ 12 CZ 13 CZ 14 CZ 15 CZ 16
    Event & Exhibit 1.82 1.95 1.74 2.12 1.91 2.13 2.24 2.30 2.36 2.47 2.62 2.16 2.64 2.68 3.22 1.89
    Library 0.37 7.17 5.97 6.75 5.64 6.08 6.19 7.13 7.18 7.56 7.17 6.93 6.88 6.81 7.93 6.40
    Hotel/Motel 0.86 0.84 0.77 0.92 0.81 0.89 0.90 1.01 1.00 1.11 1.14 0.96 1.18 1.18 1.49 0.85
    Office, Financial Institution,
  • § 170.2 Medium relevance — show source text

    b. Roof areas that are not allowed to have PVs by the mandatory conditions of approval shall not be considered in determining the SARA.

    Exception 5 to Section 170.2(f): PV system sizes determined using Equation 170.2-C may be reduced by 25 percent if installed in conjunction with a BESS. The BESS shall meet the qualification requirements specified in Joint Appendix JA12 and have a minimum cycling capacity of 7.5 kWh as defined in Joint Appendix JA12.

    TABLE 170.2-T—CFA AND DWELLING UNIT ADJUSTMENT FACTORS Col2 Col3
    CLIMATE ZONE A—CFA B—DWELLING UNITS
    1 0.793 1.27
    2 0.621 1.22
    3 0.628 1.12
    4 0.586 1.21
    5 0.585 1.06
    6 0.594 1.23
    7 0.572 1.15
    8 0.586 1.37
    9 0.613 1.36
    10 0.627 1.41
    11 0.836 1.44
    12 0.613 1.40
    13 0.894 1.51
    14 0.741 1.26
    15 1.56 1.47
    16 0.59 1.22

    (g) Photovoltaic requirements—more than three habitable stories. All newly constructed building types specified in Table 170.2-U, or mixed occupancy buildings where at least 80 percent of the floor area of the building serves one or more of these building types, shall have a newly installed photovoltaic (PV) system meeting the minimum qualification requirements of Reference Joint Appendix JA11. The PV capacity in kW dc shall not be less than the smaller of the minimum rated PV system capacity determined by Equation 170.2-D, or the total of all available solar access roof areas (SARA) multiplied by 18 for steep-sloped roofs or multiplied by 14 for low-sloped roofs. In mixed occupancy buildings, the minimum rated PV system capacity for the building shall be determined by applying Equation 170.2-D to the conditioned floor area of each of the listed building types and summing the capacities determined for each.

    1. SARA include the area of the building’s roof space capable of structurally supporting a PV system, and the area of all roof space on covered parking areas, carports and all other newly constructed structures on the site that are compatible with supporting a PV system per Title 24, Part 2, Section 1511.10.

    2. SARA does not include:

    A. Any area that has less than 70 percent annual solar access. Annual solar access is determined by dividing the total annual solar insolation (accounting for shading obstructions) by the total annual solar insolation if the same areas were unshaded by those obstructions. For all roofs, all obstructions including those that are external to the building,

    2025 CALIFORNIA ENERGY CODE 267

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES

    and obstructions that are part of the building design and elevation features, may be considered for the annual solar access calculations.

  • § 1511.10. Medium relevance — show source text
    1. SARA includes the area of the building’s roof space capable of structurally supporting a PV system, and the area of all roof space on covered parking areas, carports and all other newly constructed structures on the site that are compatible with supporting a PV system per Title 24, Part 2, Section 1511.10.

    2. SARA does NOT include:

    A. Any area that has less than 70 percent annual solar access. Annual solar access is determined by dividing the total annual solar insolation (accounting for shading obstructions) by the total annual solar insolation if the same areas were unshaded by those obstructions. For all roofs, all obstructions, including those that are external to the building, and obstructions that are part of the building design and elevation features may be considered for the annual solar access calculations.

    B. Occupied roofs as specified by CBC Section 503.1.4. C. Roof area that is otherwise not available due to compliance with: i. Other state building code requirements; or ii. Local building code requirements if the local building code requirements are confirmed by the Executive Director.

    2025 CALIFORNIA ENERGY CODE 145

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE

    COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY

    EQUATION 140.10-A—PHOTOVOLTAIC DIRECT CURRENT CAPACITY

    kW PVdc = (CFA × A)/1000

    where:

    kW PVdc = Minimum rated PV system capacity in kW.

    CFA = Conditioned floor area in square feet.

    A = PV capacity factor in W/square foot as specified in Table 140.10-A for the building type.

    Exception 1 to Section 140.10(a): No PV system is required where the total of all available SARA is less than 3 percent of the conditioned floor area.

    Exception 2 to Section 140.10(a): No PV system is required where the required PV system capacity is less than 4 kW dc .

    Exception 3 to Section 140.10(a): No PV system is required if the SARA contains less than 80 contiguous square feet.

    Exception 4 to Section 140.10(a): Buildings with enforcement-authority-approved roof designs, where the enforcement authority determines it is not possible for the PV system, including panels, modules, components, supports and attachments to the roof structure, to meet ASCE 7-16, Chapter 7, Snow Loads.

    Exception 5 to Section 140.10(a): For nonresidential and hotel/motel multitenant buildings, the PV capacity determined by Equation 140.10-A shall be calculated without including tenant spaces meeting all of the following: i. The tenant space is less than or equal to 2,000 square feet of conditioned space; ii. The tenant space is served by an HVAC system that does not serve other tenant spaces in the building; and iii. The tenant space has an individual utility meter to track electricity consumption that does not include the electricity consumption of other tenant spaces in the building.

    This exception does not apply where the Commission has approved a community solar program for showing compliance as specified in Title 24, Part 1, Section 10-115, or where a load-serving entity provides a program where PV generation is compensated through virtual energy bill credits for occupants of nonresidential and hotel/motel tenant spaces to receive energy bill benefits from netting of energy generation and consumption.

  • § 6.1507 Medium relevance — show source text

    LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|

    A6.207.1.2 Controls for heat pumps with supplementary electric resistance heaters. Heat pumps with supplementary electric resistance heaters shall have controls:

    A6.207.1.2.1 That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and

Frequently asked questions

How do I know whether to use Equation 140.10‑A or the SARA cap?

Compute both: (1) the CFA‑based value from the formula kW = (CFA × A)/1000, and (2) the SARA‑based value (SARA × 18 W/ft2 for steep roofs or × 14 W/ft2 for low slopes, divided by 1000). The code requires the smaller of the two.

Where do I find the A (W/ft2) factor?

The A factors are in the code tables that correspond to the section you are using: Table 140.10‑A for § 140.10, Table 170.2‑U for § 170.2, and Table 150.1‑C for single‑family Equation 150.1‑C. Use the column for your climate zone and the row for your building type.

Can I reduce the PV size if I add batteries?

In many of the prescriptive scenarios the code allows a 25% PV size reduction if a qualifying BESS is installed and meets Joint Appendix JA12 requirements (including minimum cycling capacity); verify the specific section for your building.

What are the simple “no‑PV” exceptions to check first?

Check whether (a) SARA < 3% of CFA, (b) the required PV is below the section’s minimum kW threshold (example: 4 kW in some prescriptive sections, 1.8 kW in certain single‑family rules), or (c) SARA < 80 contiguous ft2. If any apply, PV may not be required.

Do I need to adjust for mixed‑use buildings?

Yes — for mixed occupancy where at least 80% of the building area is one of the listed types, or when multiple listed types exist, apply the CFA equation per listed building type and sum the resulting capacities.

More in California Energy Code

Ask about the California Energy Code

Get cited, plain-English answers on the California Energy Code for your project — any code section, any scenario.

Start Free Trial

Related in the California Energy Code