Title 24 · California Energy Code

What does the code require for EV capable spaces, raceways and panel capacity at commercial sites?

In plain terms: the California code (see **§ 5.106.5.3.1**) requires commercial parking to provide a specified number of EV‑capable spaces, each served by a minimum **1‑inch** raceway back to the service panel and reserved panel space + load for a **208/240 V, 40 A** branch circuit (with **30 A** delivery to an EVSE). Mark the reserved breaker space and raceway as **“EV CAPABLE,”** ensure overall service/transformer capacity, and follow Table 5.106.5.3.1 for counts and reductions if EV chargers are already installed.

Last reviewed: July 6, 2026

What the code requires — 2-4 sentences

The California code requires that commercial parking provide a specified number of EV capable spaces (see Table 5.106.5.3.1) and that each EV capable space be served by a reserved raceway and reserved panel space / electrical load capacity sized to allow a future dedicated 208/240‑volt, 40‑ampere branch circuit (delivering 30 amperes minimum to an installed EVSE). The controlling rule is § 5.106.5.3.1 — which mandates the raceway size, branch‑circuit reservation, system capacity, and visible “EV CAPABLE” marking for the panel and raceway termination.

The single most important requirement: provide a listed raceway (minimum 1‑inch) from the service panel/subpanel to each EV capable space and reserve panel space + capacity for a 208/240 V, 40 A branch circuit for every EV capable space. § 5.106.5.3.1

Requirements in detail

Short list (plain)

  • Provide the number of EV capable spaces required by Table 5.106.5.3.1 (round up per table note). § 5.106.5.3.1
  • Provide one or more listed raceways (minimum 1‑inch / 25 mm) originating at the service panel or subpanel and terminating near each EV capable space. A common raceway may serve multiple spaces. § 5.106.5.3.1
  • Reserve panel space and electrical load capacity for a dedicated 208/240‑volt, 40‑ampere minimum branch circuit for each EV capable space, with delivery of 30 amperes minimum to an installed EVSE. § 5.106.5.3.1
  • Ensure the electrical system and any on‑site distribution transformers have sufficient capacity to supply full rated amperage at each EV capable space. § 5.106.5.3.1
  • Identify reserved breaker space(s) in the panel directory and mark the raceway termination location as “EV CAPABLE.” § 5.106.5.3.1

Decision‑relevant dimensions / values (quick table)

Requirement Required value / action Code reference
Minimum raceway inside diameter 1‑inch (25 mm) § 5.106.5.3.1
Branch circuit reserved per EV capable space 208/240 V — 40 A minimum (dedicated) § 5.106.5.3.1
Minimum delivery from installed EVSE 30 A § 5.106.5.3.1
Panel directory marking Reserved overcurrent device space(s) labeled “EV CAPABLE” § 5.106.5.3.1
Raceway termination marking Permanently and visibly marked “EV CAPABLE” § 5.106.5.3.1
Number of required EV capable spaces See Table 5.106.5.3.1 (examples in table rows) § 5.106.5.3.1 / Table 5.106.5.3.1
Rounding rule for counts Round up to nearest whole space Table note, § 5.106.5.3.1
Reduction when EVCS already installed Each EVCS reduces the number of required EV capable spaces by the same number (per table note) Table note, § 5.106.5.3.1
At least one Level 2 EVSE At least one Level 2 EVSE required where EVCS are provided Table note, § 5.106.5.3.1 and § 5.106.5.3.2

Notes: The table in the code (Table 5.106.5.3.1) lists specific counts for ranges of total parking spaces (e.g., 10–25, 26–50, etc.) — consult Table 5.106.5.3.1 in § 5.106.5.3.1 for the exact required counts.

Additional technical details (related items cited in code)

  • A common raceway may serve multiple EV capable spaces (helps reduce trenching/cost). § 5.106.5.3.1
  • The requirement is tied to providing capacity for a future EVSE: raceway must terminate into a listed cabinet/box/enclosure in close proximity to the proposed parking location. § 5.106.5.3.1
  • Where EVCS are installed, Section 5.106.5.3.2 explains EVSE types, receptacle configurations, and how installation of DCFC or multiple connectors may reduce the number of required EV capable spaces and the required panel load. § 5.106.5.3.2
  • Automatic Load Management Systems (ALMS) are permitted and, when used, may reduce required electrical load capacity; ALMS‑controlled EVSE must still deliver 30 A when charging a single vehicle and 3.3 kW minimum while simultaneously charging multiple vehicles. § 5.106.5.3.3

Exceptions & special cases

  • The code allows exceptions where compliance is not feasible because: no local utility power supply, the utility cannot supply adequate power, or additional utility infrastructure requirements would unreasonably increase construction cost — these are evaluated case‑by‑case by the enforcing agency. See § 5.106.5.3 (Exceptions).
  • Parking served by parking lifts or automated mechanical parking systems may be excluded if the facility is incapable of supporting EV charging. § 5.106.5.3 (Exceptions) and § 5.106.5.3.1 notes.
  • Installing a DCFC EVSE or two low‑power Level 2 receptacles can reduce the number of required EV capable spaces per the reductions described in § 5.106.5.3.2 (see the reductions allowed and how they affect electrical load).

Common mistakes

  • Installing a raceway smaller than 1‑inch or not routing it from the service panel/subpanel — the minimum size and origin are explicit in § 5.106.5.3.1.
  • Failing to reserve panel space or failing to plan the panel directory identification “EV CAPABLE.” Inspectors commonly see missing reserved breaker spaces even when raceway is provided. § 5.106.5.3.1
  • Miscounting required spaces or not rounding up per the table note in Table 5.106.5.3.1. Always apply the table and round up. § 5.106.5.3.1 / Table 5.106.5.3.1
  • Assuming a smaller conductor or different receptacle standard will be acceptable — the code prescribes a reserved 208/240 V, 40 A circuit (30 A delivery) as the baseline for EV capable space readiness. § 5.106.5.3.1
  • Not marking the raceway termination location visibly as “EV CAPABLE.” This is required by the section. § 5.106.5.3.1

Worked example — 120‑space commercial parking (non‑office/retail)

Scenario: A commercial site (not office or retail) provides 120 actual parking spaces.

  1. Determine number of required EV capable spaces: consult Table 5.106.5.3.1 — the row 101–150 requires 25 EV capable spaces. Round rules already covered; 120 falls in that range so you need 25. § 5.106.5.3.1 / Table 5.106.5.3.1
  2. Required EVCS (EVSE installed): for “other than office and retail” the same row lists 12 required EVCS. That means if you elect to install EVCS now, you must provide 12 EV charging stations (Level 2 or as allowed by § 5.106.5.3.2). § 5.106.5.3.1 / Table 5.106.5.3.1
  3. Raceway and panel reservations: For each of the 25 EV capable spaces you must provide:
    • a listed raceway (minimum 1‑inch) originating at the service panel/subpanel and terminating near the parking space into a listed box/enclosure (a common raceway may be used where applicable), and
    • reserved panel space and electrical load capacity for a dedicated 208/240 V, 40 A branch circuit for each space (deliver 30 A minimum when EVSE is installed). § 5.106.5.3.1
  4. System capacity check: ensure the service, distribution transformers, and feeders are sized so they can supply the full rated amperage at each EV capable space if all were simultaneously charging; otherwise, discuss ALMS or power allocation alternatives per the code. § 5.106.5.3.1 and § 5.106.5.3.3

Practical notes: you can use a common raceway to reduce trenching; you must mark reserved breaker spaces “EV CAPABLE”; and adding DC fast chargers or other permitted configurations can change the number of required EV capable spaces per § 5.106.5.3.2.

Related provisions

  • § 5.106.5.3.2 — Electric vehicle charging stations (EVCS): EVSE types, receptacle configurations, and how installed EVCS reduce required EV capable spaces.
  • § 5.106.5.3.3 — Use of Automatic Load Management Systems (ALMS) and reduced load allowances for ALMS‑controlled EVSE.
  • § 5.106.5.3 — Overall EV charging section including exceptions for feasibility and parking lifts.
  • Table references: Table 5.106.5.3.1 (required EV capable spaces / EVCS counts) — see § 5.106.5.3.1.
  • Appendix A5 tables (A5.106.5.3.2, A5.106.5.3.3, A5.106.5.3.4) — voluntary power allocation methods and kVA calculations (useful for design and power planning).

Code references

Grounded in the retrieved California Energy Code — click a citation to read the verbatim passage:

  • § 5.106.5.3.1 High relevance — show source text
    1. Areas of parking facilities served by parking lifts, including but not limited to, automated mechanical-access open parking garages as defined in the California Building Code ; or parking facilities otherwise incapable of supporting electric vehicle charging. 5.106.5.3.1 EV capable spaces. [N] EV capable spaces shall be provided in accordance with Table 5.106.5.3.1 and the following requirements:

    2. Raceways complying with the California Electrical Code and no less than 1-inch (25 mm) diameter shall be provided and shall originate at a service panel or a subpanel(s) serving the area, and shall terminate in close proximity to the proposed location of the EV capable space and into a suitable listed cabinet, box, enclosure or equivalent. A common raceway may be used to serve multiple EV capable spaces.

    3. A service panel or subpanel(s) shall be provided with panel space and electrical load capacity for a dedicated 208/240 volt, 40-ampere minimum branch circuit for each EV capable space, with delivery of 30-ampere minimum to an installed EVSE at each EVCS.

    4. The electrical system and any on-site distribution transformers shall have sufficient capacity to supply full rated amperage at each EV capable space.

    5. The service panel or subpanel circuit directory shall identify the reserved overcurrent protective device space(s) as “EV CAPABLE”. The raceway termination location shall be permanently and visibly marked as “EV CAPABLE.” Note: A parking space served by electric vehicle supply equipment or designed as a future EV charging space shall count as at least one standard automobile parking space only for the purpose of complying with any applicable minimum parking space requirements established by an enforcement agency. See Vehicle Code Section 22511.2 for further details.

    TABLE 5.106.5.3.1—EV CAPABLE SPACES AND EVCS Col2 Col3 Col4
    TOTAL NUMBER OF ACTUAL
    PARKING SPACES
    NUMBER OF REQUIRED EV
    CAPABLE SPACES
    OTHER THAN OFFICE AND
    RETAIL
    NUMBER OF REQUIRED EVCS2, 3
    OFFICE AND RETAIL
    NUMBER OF REQUIRED EVCS2, 3
    1–9 0 0 0
    10–25 4 2 3
    26–50 8 4 6
    51–75 13 6 8
    76–100 17 8 13
    101–150 25 12 19
    151–200 35 18 26
    201 and over 20 percent of actual parking
    spaces1
    50 percent of EV capable spaces1 75 percent of EV capable spaces1
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.
    1.
  • § 5.106.5 High relevance — show source text

    5.106.5 Electric vehicle (EV) charging.

    5.106.5.1 Reserved.

    5.106.5.2 Reserved.

    5.106.5.3 Electric vehicle (EV) charging. [N] [BSC-CG] Construction to provide electric vehicle infrastructure and facilitate electric vehicle charging shall comply with Section 5.106.5.3.1 EV capable spaces, Section 5.106.5.3.2 Electric vehicle charging stations and associated Table 5.106.5.3.1, or Section 5.106.5.3.6 Electric vehicle charging stations (EVCS)—Power allocation method and associated Table 5.106.5.3.6, and shall be provided in accordance with regulations in the California Building Code and the California Electrical Code. Exceptions:

    1. On a case-by-case basis where the local enforcing agency has determined compliance with this section is not feasible based upon one of the following conditions: a. Where there is no local utility power supply. b. Where the local utility is unable to supply adequate power. c. Where there is evidence suitable to the local enforcement agency substantiating that additional local utility infrastructure design requirements, directly related to the implementation of Section 5.106.5.3, may adversely impact the construction cost of the project.

    2. Areas of parking facilities served by parking lifts, including but not limited to, automated mechanical-access open parking garages as defined in the California Building Code ; or parking facilities otherwise incapable of supporting electric vehicle charging. 5.106.5.3.1 EV capable spaces. [N] EV capable spaces shall be provided in accordance with Table 5.106.5.3.1 and the following requirements:

    3. Raceways complying with the California Electrical Code and no less than 1-inch (25 mm) diameter shall be provided and shall originate at a service panel or a subpanel(s) serving the area, and shall terminate in close proximity to the proposed location of the EV capable space and into a suitable listed cabinet, box, enclosure or equivalent. A common raceway may be used to serve multiple EV capable spaces.

    4. A service panel or subpanel(s) shall be provided with panel space and electrical load capacity for a dedicated 208/240 volt, 40-ampere minimum branch circuit for each EV capable space, with delivery of 30-ampere minimum to an installed EVSE at each EVCS.

    5. The electrical system and any on-site distribution transformers shall have sufficient capacity to supply full rated amperage at each EV capable space.

    6. The service panel or subpanel circuit directory shall identify the reserved overcurrent protective device space(s) as “EV CAPABLE”. The raceway termination location shall be permanently and visibly marked as “EV CAPABLE.” Note: A parking space served by electric vehicle supply equipment or designed as a future EV charging space shall count as at least one standard automobile parking space only for the purpose of complying with any applicable minimum parking space requirements established by an enforcement agency. See Vehicle Code Section 22511.2 for further details.

  • § 5.106.5.3.1 High relevance — show source text

    Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|

    A5.106.5.3.3 Tier 2. Comply with Section 5.106.5.3.1 EV capable spaces, Section 5.106.5.3.2 Electric vehicle charging stations and associated Table A5.106.5.3.3, or Section A5.106.5.3.4 Electric vehicle charging stations (EVCS)—power allocation method and associated Table A5.106.5.3.4.

    Refer to Section 5.106.5.3.2 for the permitted use of Level 2 or Direct Current Fast Charger (DCFC) to create EVCS. Refer to Section 5.106.3.2.1 for the allowed use of DCFC to comply with both EV capable spaces and Level 2 EVSE. Refer to Section 5.106.5.3.3 for the allowed use of Automatic Load Management System (ALMS).

    TABLE A5.106.5.3.3—TIER 2 EV CAPABLE SPACES AND EVCS Col2 Col3 Col4
    TOTAL NUMBER OF
    ACTUAL PARKING SPACES
    NUMBER OF
    REQUIRED EV CAPABLE SPACES
    OTHER THAN OFFICE AND RETAIL
    NUMBER OF REQUIRED EVCS2, 3
    OFFICE AND RETAIL
    NUMBER OF REQUIRED EVCS2, 3
    1–9 3 2 2
    10–25 8 4 6
    26–50 17 9 13
    51–75 28 14 21
    76–100 40 20 30
    101–150 57 29 43
    151–200 79 40 59
    201 and over 45 percent of actual parking spaces1 50 percent of EV capable spaces1 75 percent of EV capable spaces1
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.
    1.
  • § 6.6 High relevance — show source text

    6|Total required kVA = P× .45× 6.6
    Where P = Parking spaces in facility|Total required kVA = P× .45× 6.6
    Where P = Parking spaces in facility| |1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|

    A5.106.6 Parking capacity. Design parking capacity to meet but not exceed minimum local zoning requirements.

    A5.106.6.1 Reduce parking capacity. With the approval of the enforcement authority, employ strategies to reduce on-site parking area by

    1. Use of on street parking or compact spaces, illustrated on the site plan or
    2. Implementation and documentation of programs that encourage occupants to carpool, ride share or use alternate transportation.

    Note: Strategies for programs may be obtained from local TMAs.

    A5.106.7 Exterior wall shading. Meet requirements in the current edition of the California Energy Code and comply with either Section A5.106.7.1 or A5.106.7.2 for wall surfaces. If using vegetative shade, plant species documented to reach desired coverage within 5 years of building occupancy.

    A5.106.7.1 Fenestration. Provide vegetative or man-made shading devices for all fenestration on east-, south- and west-facing walls.

  • § 106.5.3.2 High relevance — show source text

    Power allocation method shall include the following:

    1. Use any kVA combination of EV capable spaces, low power Level 2, Level 2 or DCFC EVSEs.
    2. At least one Level 2 EVSE shall be provided.
    TABLE A5.106.5.3.2—TIER 1 EVCS—POWER ALLOCATION METHOD Col2 Col3 Col4
    TOTAL NUMBER OF
    ACTUAL PARKING SPACES
    MINIMUM TOTAL kVA
    @ 6.6 kVA
    OTHER THAN OFFICE AND RETAIL
    TOTAL kVA REQUIRED
    IN ANY COMBINATION OF EV
    CAPABLE3, 4, LOW POWER LEVEL 2
    LEVEL 21, 2, OR DCFC
    OFFICE AND RETAIL
    TOTAL kVA REQUIRED
    IN ANY COMBINATION OF EV
    CAPABLE3, 4, LOW POWER LEVEL 2
    LEVEL 21, 2, OR DCFC
    1–9 13.2 13.2 13.2
    10–25 33 33 33
    26–50 72.6 72.6 72.6
    51–75 125.4 125.4 125.4
    76–100 171.6 171.6 171.6
    101–150 250.8 250.8 250.8
    151–200 349.8 349.8 349.8
    201 and over 30 percent of
    actual parking spaces× 6.6
    Total required kVA = P× .30× 6.6
    Where P = Parking spaces in facility
    Total required kVA = P× .30× 6.6
    Where P = Parking spaces in facility
    1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.
    1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.
    1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.
    1.
  • § 5.106.5.6.1 High relevance — show source text

    proposed location of the EV capable space and into a suitable listed cabinet, box, enclosure or equivalent. A common raceway may be used to serve multiple EV capable spaces. 2. A service panel or subpanel(s) shall be provided with panel space and electrical load capacity for a dedicated 208/240 volt, 40-ampere minimum branch circuit for each EV capable space, with delivery of 30-ampere minimum to an installed EVSE at each EVCS.

    1. The electrical system and any on-site distribution transformers shall have sufficient capacity to supply full rated amperage at each EV capable space.
    2. The service panel or subpanel circuit directory shall identify the reserved overcurrent protective device space(s) as “EV CAPABLE.” The raceway termination location shall be permanently and visibly marked as “EV CAPABLE.”
    TABLE 5.106.5.6.1 Col2 Col3
    TOTAL NUMBER OF PARKING SPACES NUMBER OF REQUIRED EV CAPABLE SPACES NUMBER OF REQUIRED EVCS2
    0–9 0 0
    10–25 4 1
    26–50 8 2
    51–75 13 3
    76–100 17 4
    101–150 25 6
    151–200 35 9
    201 and over 20 percent of total1 25 percent of EV capable spaces1
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.

    5.106.5.6.2 Electric vehicle charging stations (EVCS). EV capable spaces shall be provided with EVSE to create EVCS in the number indicated in Table 5.106.5.6.1 and shall comply with Section 5.106.5.6.2. EVCS shall be serviced by Level 2 or Direct Current Fast Charging (DCFC) EVSE, or with EVSE in any combination of Level 2 and DCFC. Accessible EVCS shall be provided in accordance with California Building Code Chapter 11B .

    5.106.5.6.2.1 Reduced number of EV capable spaces. The installation of each DCFC EVSE shall be permitted to reduce the minimum number of required EV capable spaces indicated in Table 5.106.5.6.1 by five and reduce proportionally the required electrical load capacity to the service panel or subpanel.

    5.106.5.6.2.2 Multiple connectors. EVSE with multiple vehicle connectors capable of charging multiple EVs simultaneously shall be permitted if the electrical load capacity required by Section 5.106.5.6.1 for each EV capable space is accumulatively supplied to the EVSE.

  • § 6.6 High relevance — show source text

    6|Total required kVA = P× .30× 6.6
    Where P = Parking spaces in facility|Total required kVA = P× .30× 6.6
    Where P = Parking spaces in facility| |1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 67 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|

    A5.106.5.3.3 Tier 2. Comply with Section 5.106.5.3.1 EV capable spaces, Section 5.106.5.3.2 Electric vehicle charging stations and associated Table A5.106.5.3.3, or Section A5.106.5.3.4 Electric vehicle charging stations (EVCS)—power allocation method and associated Table A5.106.5.3.4.

    Refer to Section 5.106.5.3.2 for the permitted use of Level 2 or Direct Current Fast Charger (DCFC) to create EVCS. Refer to Section 5.106.3.2.1 for the allowed use of DCFC to comply with both EV capable spaces and Level 2 EVSE. Refer to Section 5.106.5.3.3 for the allowed use of Automatic Load Management System (ALMS).

  • § 5.106.5.3.1 High relevance — show source text

    At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|

    5-6 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL MANDATORY MEASURES

    5.106.5.3.6.1 Receptacle configurations. 208/240V EV charging receptacles shall comply with one of the following configurations:

    1. For 20-ampere receptacles, NEMA 6-20R.
    2. For 30-ampere receptacles, NEMA 14-30R.
    3. For 50-ampere receptacles, NEMA 14-50R.

    5.106.5.3.6.2 EV Charger connectors. EV chargers shall be equipped with SAE J1772 with a maximum output 240 Volts AC or SAE J3400 connectors. When using level 2 SAE J3400 connectors, supplied by a 480 V 3-phase service, at least 20 percent of the EV charger connectors shall be SAE J1772 with a maximum output 240 Volts AC.

    5.106.5.3.6.3 Raceway capacity requirements. To allow for future upgrades to the electrical conductors serving low power Level 2 charging receptacles, the listed raceway serving such receptacles shall be sized to allow the installation of a dedicated 208/240-volt 40-ampere branch circuit. Where no raceway is used, the conductors shall be sized to accommodate a 208/240-volt 40-ampere receptacle.

  • § 5.106.5.3.1 High relevance — show source text

    If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.|

    A5.106.6 Parking capacity. Design parking capacity to meet but not exceed minimum local zoning requirements.

    A5.106.6.1 Reduce parking capacity. With the approval of the enforcement authority, employ strategies to reduce on-site parking area by

    1. Use of on street parking or compact spaces, illustrated on the site plan or
    2. Implementation and documentation of programs that encourage occupants to carpool, ride share or use alternate transportation.

    Note: Strategies for programs may be obtained from local TMAs.

    A5.106.7 Exterior wall shading. Meet requirements in the current edition of the California Energy Code and comply with either Section A5.106.7.1 or A5.106.7.2 for wall surfaces. If using vegetative shade, plant species documented to reach desired coverage within 5 years of building occupancy.

    A5.106.7.1 Fenestration. Provide vegetative or man-made shading devices for all fenestration on east-, south- and west-facing walls.

    A5.106.7.1.1 East and west walls. Shading devices shall have 30-percent coverage to a height of 20 feet or to the top of the exterior wall, whichever is less. Calculate shade coverage on the summer solstice at 10 AM for east-facing walls and at 3 PM for west-facing walls.

    A5.106.7.1.2 South walls. Shading devices shall have 60-percent coverage to a height of 20 feet or to the top of the exterior wall, whichever is less.

    A5.106.7.2 Opaque wall areas. Use wall surfacing with minimum SRI 25 (aged), for 75 percent of opaque wall areas.

    Exception: Use of vegetated shade in Wildland-Urban Interface Areas as defined in Chapter 7A (Materials and Construction Methods for Exterior Wildfire Exposure) of the California Building Code shall meet the requirements of that chapter.

    Note: If not available from the manufacturer, aged SRI value calculations may be found at the California Energy Commis-sion’s web site at www.energy.ca.gov.

    A5.106.8 Reserved.

    A5.106.9 Reserved.

    A5.106.10 Reserved.

    A5.106.11 Reduction of heat island effect. Reduce heat islands by requiring Section A5.106.11.1 Hardscape alternatives, Section A5.106.11.2 Cool roofs, or Section A5.106.11.3 Shade trees.

  • § 106.5.3.4 High relevance — show source text

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    TABLE A5.106.5.3.4—TIER 2 EVCS—POWER ALLOCATION METHOD Col2 Col3 Col4
    TOTAL NUMBER OF
    ACTUAL PARKING
    SPACES
    MINIMUM TOTAL kVA
    @ 6.6 kVA
    OTHER THAN OFFICE AND RETAIL
    TOTAL kVA REQUIRED
    IN ANY COMBINATION OF EV CAPABLE3,
    4, LOW POWER LEVEL 2
    LEVEL 21, 2, OR DCFC
    OFFICE AND RETAIL
    TOTAL kVA REQUIRED
    IN ANY COMBINATION OF EV CAPABLE3,
    4, LOW POWER LEVEL 2
    LEVEL 21, 2, OR DCFC
    1–9 19.8 19.8 19.8
    10–25 52.8 52.8 52.8
    26–50 112.2 112.2 112.2
    51–75 184.8 184.8 184.8
    76–100 264.0 264 264
    101–150 376.2 376.2 376.2
    151–200 521.4 521.4 521.4
    201 and over 45 percent of
    actual parking spaces× 6.6
    Total required kVA = P× .45× 6.6
    Where P = Parking spaces in facility
    Total required kVA = P× .45× 6.6
    Where P = Parking spaces in facility
    1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.
    1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.
    1. Level 2 EVSE @ 6.6 kVA minimum.
    2. At least one Level 2 EVSE shall be provided.
    3. Maximum allowed kVA to be utilized for EV capable spaces is 75 percent.
    4. If EV capable spaces are utilized, they shall meet the requirements of Section 5.106.5.3.1 EV capable spaces.
    5. For office and retail buildings the maximum allowed kVA to be utilized for EV capable spaces is 25 percent.
    1.
  • § 5-5 High relevance — show source text

    Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.|1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.|1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.|1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    3. At least one Level 2 EVSE shall be provided.|

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 5-5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL MANDATORY MEASURES

    5.106.5.3.2 Electric vehicle charging stations (EVCS). EV capable spaces shall be provided with electric vehicle supply equipment (EVSE) to create EVCS in the number indicated in Table 5.106.5.3.1. The EVCS required by Table 5.106.5.3.1 shall be provided with Level 2 EVSE or DCFC as permitted in Section 5.106.5.3.2.3. At least one Level 2 EVSE shall be provided. One EV charger with multiple connectors capable of charging multiple EVs simultaneously shall be permitted if the electrical load capacity required by Section 5.106.5.3.1 for each EV capable space is accumulatively supplied to the EV charger.

    5.106.5.3.2.1 Receptacle configurations. 208/240V EV charging receptacles shall comply with one of the following configurations:

    1. For 20-ampere receptacles, NEMA 6-20R
    2. For 30-ampere receptacles, NEMA 14-30R
    3. For 50-ampere receptacles, NEMA 14-50R

    5.106.5.3.2.2 EV charger connectors. EV chargers shall be equipped with SAE J1772 with a maximum output 240 Volts AC or SAE J3400 connectors.

    When using level 2 SAE J3400 SAE connectors, supplied by a 480 V 3-phase service, at least 20 percent of the EV charger connectors shall be SAE J1772 with a maximum output 240 Volts AC.

    5.106.5.3.2.3 The installation of each DCFC EVSE shall be permitted to reduce the minimum number of required EV capable spaces without EVSE or EVCS with Level 2 EVSE by five, and reduce proportionally the required electrical load capacity to the service panel or subpanel.

    5.106.5.3.2.4 The installation of two low power Level 2 EV charging receptacles shall be permitted to reduce the minimum number of required EV capable spaces without EVSE in Table 5.106.5.3.1 by one.

  • § 5.106.5.6 High relevance — show source text

    000 to 256,000|1 or 2|200| |Warehouse|20,000 to 256,000|3 or Greater|400| |Warehouse|Greater than 256,000|1 or Greater|400|

    5.106.5.6 Electric vehicle (EV) charging at public schools and community colleges. [DSA-SS] Electric vehicle infrastructure and electric vehicle charging stations shall comply with Section 5.106.5.6 and shall be provided in accordance with regulations in the California Building Code and the California Electrical Code.

    Exceptions:

    1. On a case-by-case basis where compliance with this section has been demonstrated to be not feasible based upon one of the following conditions, and with concurrence by the Division of the State Architect (DSA), compliance with Section 5.106.5.6 shall not be required. a. Where there is no local utility power supply. b. Where the local utility is unable to supply adequate power. c. The installation of EVCS is impracticable.
    2. Parking spaces accessible only by automated mechanical car parking systems are not required to comply with Section 5.106.5.6.

    5.106.5.6.1 EV capable spaces. EV capable spaces shall be provided in accordance with Table 5.106.5.6.1 and the following requirements:

    1. Raceways complying with the California Electrical Code and no less than 1-inch (25 mm) diameter shall be provided and shall originate at a service panel or a subpanel(s) serving the area and shall terminate in close proximity to the

    5-8 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL MANDATORY MEASURES

    proposed location of the EV capable space and into a suitable listed cabinet, box, enclosure or equivalent. A common raceway may be used to serve multiple EV capable spaces. 2. A service panel or subpanel(s) shall be provided with panel space and electrical load capacity for a dedicated 208/240 volt, 40-ampere minimum branch circuit for each EV capable space, with delivery of 30-ampere minimum to an installed EVSE at each EVCS.

    1. The electrical system and any on-site distribution transformers shall have sufficient capacity to supply full rated amperage at each EV capable space.
    2. The service panel or subpanel circuit directory shall identify the reserved overcurrent protective device space(s) as “EV CAPABLE.” The raceway termination location shall be permanently and visibly marked as “EV CAPABLE.”
    TABLE 5.106.5.6.1 Col2 Col3
    TOTAL NUMBER OF PARKING SPACES NUMBER OF REQUIRED EV CAPABLE SPACES NUMBER OF REQUIRED EVCS2
    0–9 0 0
    10–25 4 1
    26–50 8 2
    51–75 13 3
    76–100 17 4
    101–150 25 6
    151–200 35 9
    201 and over 20 percent of total1 25 percent of EV capable spaces1
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    1. Calculation for spaces shall be rounded up to the nearest whole number.
    2. Each EVCS shall reduce the number of required EV capable spaces by the same number.
    1.

Frequently asked questions

How is an “EV capable space” counted if an EV charger is already installed?

If an EVCS (installed EV charger) is already provided, each installed EVCS reduces the number of required EV capable spaces by the same number, per the table notes in § 5.106.5.3.1.

Do I have to install conduit all the way to each parking stall?

You must provide a listed raceway (minimum 1‑inch) that originates at a service panel or subpanel and terminates in close proximity to the proposed EV capable space into a listed cabinet/box/enclosure. A common raceway may serve multiple spaces. § 5.106.5.3.1

Can I use Automatic Load Management (ALMS) to avoid upsizing the service?

Yes — § 5.106.5.3.3 permits ALMS and allows reduced required electrical load capacity for EVSE under ALMS, subject to the delivery minimums laid out in that section.

What marking is required at the panel and at the raceway termination?

The panel directory must identify reserved overcurrent protective device space(s) as “EV CAPABLE”, and the raceway termination location must be permanently and visibly marked “EV CAPABLE.” § 5.106.5.3.1

Are there feasibility exceptions?

Yes — the enforcing agency may grant exceptions where local utility power is absent or inadequate or where required utility infrastructure would unreasonably affect construction cost; also parking lifts/automated parking may be excepted. See § 5.106.5.3 exceptions.

More in California Energy Code

Ask about the California Energy Code

Get cited, plain-English answers on the California Energy Code for your project — any code section, any scenario.

Start Free Trial

Related in the California Energy Code