Skip to content

Title 17 — BUILDINGS AND CONSTRUCTION›Part 10 — REFERENCED STANDARDS

§ 8.3

San Jose Municipal Code · 2026-09 edition · updated 2026-09-29 · San Jose

8.3.4 Sprinklers shall be required in garages and carports.

Sprinklers shall be required under open attached

porches, exterior roofs, canopies, balconies, decks, or similar projections exceeding 4 feet in width and in.

8.3.5.1 is deleted.

Exceptions & meaning →

8.3.5.1.1 is deleted.

8.3.5.1.2 is deleted.

8.3.5.1.3 is deleted.

8.3.5.1.4 is deleted.

8.3.5.1.5 is deleted.

8.3.11 Pilot Sprinklers.

Pilot sprinklers shall be provided in attics spaces and between floors where

floor/ceiling assemblies consist of open web wood joists or trusses. Pilot sprinklers shall be intermediate temperature rated, K=4.2, quick response. Pilot sprinklers shall be located within twelve inches of the structure and/or at the apex of each ridgeline where applicable. A sprinkler is required where the ridgeline and hips converge. Sprinklers shall be spaced at maximum thirty-foot centers (maximum fifteen feet from outside walls) and shall be located at all fuel-fired equipment, including furnaces, hot water heaters, etc.

10.4.9 is deleted.