Title 17 — BUILDINGS AND CONSTRUCTION›Part 10 — REFERENCED STANDARDS
§ 8.3
San Jose Municipal Code · 2026-09 edition · updated 2026-09-29 · San Jose
8.3.4 Sprinklers shall be required in garages and carports.¶
Sprinklers shall be required under open attached
porches, exterior roofs, canopies, balconies, decks, or similar projections exceeding 4 feet in width and in.
8.3.5.1 is deleted.
8.3.5.1.1 is deleted.¶
8.3.5.1.2 is deleted.¶
8.3.5.1.3 is deleted.¶
8.3.5.1.4 is deleted.¶
8.3.5.1.5 is deleted.¶
8.3.11 Pilot Sprinklers.¶
Pilot sprinklers shall be provided in attics spaces and between floors where
floor/ceiling assemblies consist of open web wood joists or trusses. Pilot sprinklers shall be intermediate temperature rated, K=4.2, quick response. Pilot sprinklers shall be located within twelve inches of the structure and/or at the apex of each ridgeline where applicable. A sprinkler is required where the ridgeline and hips converge. Sprinklers shall be spaced at maximum thirty-foot centers (maximum fifteen feet from outside walls) and shall be located at all fuel-fired equipment, including furnaces, hot water heaters, etc.
10.4.9 is deleted.