10.6.11.8 Where the engine-driven generator is not constantly attended, audible and…¶
powered by a source other than the engine starting batteries and not exceeding 125 volts shall be provided at a point of constant attendance or to a listed central station. These alarms shall indicate the following:
Engine running (separate signal).
The controller main switch has been turned to "off" or "manual" position (separate signal).
Low fuel and trouble on the controller or engine (separate or common signals).