18.14.12 The system shall comply with all of the following:

(1)

Monitoring for integrity of the system shall comply with chapter 10 of NFPA 72.

(2)

System supervisory signals shall include the following:

(a)

Signal Source malfunction

(b)

Active RF-emitting device failure

(c)

Low-battery capacity indication when numerical 70% of the 12-hour operating battery capacity has been depleted

(d)

Active and passive system component (distribution antenna loop) failure

(3)

Power supply supervisory signals shall include the following for each RF-emitting device and active systems components:

(a)

Loss of normal ac power

(b)

Failure of battery charger

(4)

The communications link between the fire alarm system and the in-building emergency responder communications enhancement system shall be monitored for integrity.

(5)

Where approved by the AHJ, a single supervisory input to the fire alarm system to monitor all system supervisory signals shall be permitted.

Exceptions & meaning →

18.14.2.2 The annunciator shall provide visual and labeled indications of the following…

component and RF-emitting device:

(1)

Normal ac power

(2)

Loss of normal ac power

(3)

Battery charger failure

(4)

Low-battery capacity (i.e., to 70 percent depletion

(5)

Signal source malfunction

(6)

Active RF-emitting device malfunction

(7)

Active and passive system component (distribution antenna loop) malfunction.

(Ord. 31258.)