San Francisco Building Inspection Commission Codes Art. 760 Fire Alarm Systems

San Francisco Building Inspection Commission Codes · 2026-08 edition · updated 2026-09-23 · San Francisco

Cite as: San Francisco Building Inspection Commission Codes Article 760 · Text as of 2026-09-23

760.46 Revise this section as follows:

760.46 NPLFA Circuit Wiring. Installation of non-power-limited fire alarm circuits shall be in accordance with 110.3(B), 300.7, 300.11, 300.15, 300.17, 300.19(B), and other appropriate articles of Chapter 3. Conductors shall be installed in metallic raceways or concrete-encased nonmetallic raceways.

Exception No. 1: As provided in Sections 760.48 through 760.53.

[ ← ]

The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.

[ Editor’s Note: Exception 2 is deleted by local amendment.]

760.130(A) Revise Exception No. 2 of this section as follows:

(A) NPLFA Wiring Methods and Materials. [ ← ]

The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.

Installation shall be [ ← ]

The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.

in accordance with 760.46, [ ← ]

The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.

and conductors shall be solid or stranded copper. [ ← ]

The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.

Exception No. 2: Conductors and multiconductor cables described in and installed in accordance with 760.49 shall be permitted.

760.130(B) Revise the first paragraph of this section as follows:

760.130(B) PLFA Wiring Methods and Materials. Power-limited fire alarm conductors and cables described in 760.179 shall be installed [ ← ]

The arrow represents the location of language that has been deleted by San Francisco from the applicable California Code.

in metallic raceway in accordance with 760.46. Devices shall be installed in accordance with 110.3(B), 300.7, 300.11(A), and 300.15.

760.180 Add the following new section: